16.5.27 
  Outdoor High Pressure Switch Abnormal (F27) 
Malfunction Decision Conditions: 
During compressor stop, and outdoor high pressure switch is remain opened. 
 
Malfunction Caused: 
1  Faulty connector connection. 
2  Faulty switch. 
3  Faulty outdoor unit PCB (main). 
 
Abnormality Judgment: 
Continue for 1 minute. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
122 
16.5.28 
Indoor Water Outlet Temperature Sensor 2 Abnormality (F30) 
Malfunction Decision Conditions: 
During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet 
temperature sensor 2 are used to determine sensor error. 
 
Malfunction Caused: 
1  Faulty connector connection. 
2  Faulty sensor. 
3  Faulty indoor unit PCB. 
 
Abnormality Judgment: 
Continue for 5 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
123 
16.5.29 
  Outdoor Air Temperature Sensor Abnormality (F36) 
Malfunction Decision Conditions: 
During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature 
sensor are used to determine sensor error. 
 
Malfunction Caused: 
1  Faulty connector connection. 
2  Faulty sensor. 
3  Faulty outdoor unit PCB (main). 
 
Abnormality Judgment: 
Continue for 5 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
124 
16.5.30 
  Indoor Water Inlet Temperature Sensor Abnormality (F37) 
Malfunction Decision Conditions: 
During startup and operation of cooling and heating, the temperatures detected by the indoor water inlet 
temperature sensor are used to determine sensor error. 
 
Malfunction Caused: 
1  Faulty connector connection. 
2  Faulty sensor. 
3  Faulty indoor unit PCB (main). 
 
Abnormality Judgment: 
Continue for 5 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 127