  IPM Overheating (F22) 
Malfunction Decision Conditions: 
During operation of cooling and heating, when temperature 95°C is detected by the outdoor IPM temperature 
sensor. 
 
Malfunction Caused: 
1  Faulty outdoor unit fan motor. 
2  Faulty outdoor unit PCB (main). 
 
Abnormality Judgment: 
Continue 3 times in 30 minutes. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
118 
16.5.24 
  Output Over Current Detection (F23) 
Malfunction Decision Conditions: 
During operation of cooling and heating, when outdoor DC current is above 34 A is detected by the IPM DC Peak 
sensing circuitry in the outdoor unit PCB (main). 
 
Malfunction Caused: 
1  Faulty outdoor unit PCB (main). 
2  Faulty compressor. 
 
Abnormality Judgment: 
Continue for 7 times. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
119 
16.5.25 
  Refrigeration Cycle Abnormality (F24) 
Malfunction Decision Conditions: 
1  During operation of cooling and heating, compressor frequency > Frated. 
2  During operation of cooling and heating, running current: 0.65 A < I < 1.65 A. 
3  During operation of cooling, water inlet temperature - indoor refrigerant liquid temperature < 5°C. 
4  During operation of heating, indoor refrigerant liquid temperature - water inlet temperature < 5°C. 
 
Malfunction Caused: 
1  Faulty water inlet or indoor refrigerant liquid temperature sensors. 
2  2/3 way valve closed. 
3  Refrigerant shortage (refrigerant leakage). 
4  Clogged expansion valve or strainer. 
5  Faulty outdoor unit PCB (main). 
6  Poor compression of compressor. 
 
Abnormality Judgment: 
Continue 2 times in 20 minutes. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
120 
16.5.26 
  Four Way Valve Abnormality (F25) 
Malfunction Decision Conditions: 
1  During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C. 
2  During cooling operation, when the indoor pipe temperature of thermostat ON indoor unit > 45°C. 
 
Malfunction Caused: 
1  Faulty sensor. 
2  Faulty connector connection. 
3  Faulty outdoor unit PCB (noise filter/main). 
4  Faulty four way valve. 
 
Abnormality Judgment: 
Continue 4 times in 30 minutes. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 