16.5.3  Water Pump Abnormality (H20) 
Malfunction Decision Conditions: 
During startup and operation of cooling and heating, the rotation speed detected by the IPM of water pump motor 
during water pump operation is used to determine abnormal water pump (feedback of rotation > 6,000rpm or < 
1,000rpm). 
 
Malfunction Caused: 
1  Operation stop due to short circuit inside the water pump motor winding. 
2  Operation stop due to breaking of wire inside the water pump motor. 
3  Operation stop due to breaking of water pump lead wires. 
4  Operation stop due to water pump motor IPM malfunction. 
5  Operation error due to faulty indoor unit PCB. 
 
Abnormality Judgment: 
Continue for 5 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
98 
16.5.4  Indoor Refrigerant Liquid Temperature Sensor Abnormality (H23) 
Malfunction Decision Conditions: 
During startup and operation of cooling and heating, the temperatures detected by the indoor refrigerant liquid 
temperature sensor are used to determine sensor error. 
 
Malfunction Caused: 
1  Faulty connector connection. 
2  Faulty sensor. 
3  Faulty indoor unit PCB (main). 
 
Abnormality Judgment: 
Continue for 5 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
99 
16.5.5  Service Valve Error (H27) 
Malfunction Decision Conditions: 
During cooling operation, when:- 
[a] Indoor refrigerant pipe temperature at compressor startup - present indoor refrigerant pipe temperature < 2°C 
[b] Present high pressure - high pressure at compressor startup < 5kg/cm
2
 
**Judgment only for first time cooling operation and not during pump down operation. 
 
Malfunction Caused: 
1  3 way valves closed. 
2  Faulty high pressure sensor. 
3  Faulty indoor refrigerant pipe temperature sensor 
4  Faulty outdoor unit PCB (main). 
 
Abnormality Judgment: 
Continue for 5 minutes. 
 
 
 
100 
16.5.6  Compressor Low Pressure Protection (H42) 
Malfunction Decision Conditions: 
During operation of heating and after 5 minutes compressor ON, when outdoor pipe temperature below -29°C or 
above 26°C is detected by the outdoor pipe temperature sensor. 
 
Malfunction Caused: 
1  Dust accumulation on the outdoor unit heat exchanger. 
2  Air short circuit at outdoor unit. 
3  2 way valve partially closed. 
4  Faulty outdoor unit fan motor. 
5  Refrigerant shortage (refrigerant leakage). 
6  Clogged expansion valve or strainer. 
7  Faulty outdoor pipe temperature sensor. 
8  Faulty outdoor unit main PCB (main). 
 
 