113
16.5.19
Compressor Rotation Failure (F14)
Malfunction Decision Conditions:
A compressor rotation failure is detected by checking the compressor running condition through the position
detection circuit.
detection circuit.
Malfunction Caused:
1 Compressor terminal disconnect.
2 Faulty outdoor unit PCB (main).
3 Faulty compressor.
2 Faulty outdoor unit PCB (main).
3 Faulty compressor.
Abnormality Judgment:
Continue 4 times in 20 minutes.
114
16.5.20
Outdoor Fan Motor (DC Motor) Mechanism Locked (F15)
Malfunction Decision Conditions:
The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine
abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm).
abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm).
Malfunction Caused:
1 Operation stop due to short circuit inside the fan motor winding.
2 Operation stop due to breaking of wire inside the fan motor.
3 Operation stop due to breaking of fan motor lead wires.
4 Operation stop due to fan motor Hall IC malfunction.
5 Operation error due to faulty outdoor unit PCB.
2 Operation stop due to breaking of wire inside the fan motor.
3 Operation stop due to breaking of fan motor lead wires.
4 Operation stop due to fan motor Hall IC malfunction.
5 Operation error due to faulty outdoor unit PCB.
Abnormality Judgment:
Continue 2 times in 30 minutes.
115
16.5.21
Input Over Current Detection (F16)
Malfunction Decision Conditions:
During operation of cooling and heating, when outdoor current above 24.1 A (Heating) and 16.4 A (Cooling)
[UD07FE5)] and 28.1 A (Heating) and 18.1 A (Cooling) [UD09FE5)] is detected by the current transformer (CT) in
the outdoor unit PCB.
[UD07FE5)] and 28.1 A (Heating) and 18.1 A (Cooling) [UD09FE5)] is detected by the current transformer (CT) in
the outdoor unit PCB.
Malfunction Caused:
1 Excessive refrigerant.
2 Faulty outdoor unit PCB (main).
2 Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 3 times in 20 minutes.
116
16.5.22
Compressor Overheating (F20)
Malfunction Decision Conditions:
During operation of cooling and heating, when temperature above 112°C is detected by the compressor tank
temperature sensor.
temperature sensor.
Malfunction Caused:
1 Faulty compressor tank temperature sensor.
2 2/3 way valve closed.
3 Refrigerant shortage (refrigerant leakage).
4 Clogged expansion valve or strainer.
5 Faulty outdoor unit PCB (main).
6 Faulty compressor.
2 2/3 way valve closed.
3 Refrigerant shortage (refrigerant leakage).
4 Clogged expansion valve or strainer.
5 Faulty outdoor unit PCB (main).
6 Faulty compressor.
Abnormality Judgment:
Continue 4 times in 30 minutes.