113 
16.5.19 
  Compressor Rotation Failure (F14) 
Malfunction Decision Conditions: 
A compressor rotation failure is detected by checking the compressor running condition through the position 
detection circuit. 
 
Malfunction Caused: 
1  Compressor terminal disconnect. 
2  Faulty outdoor unit PCB (main). 
3  Faulty compressor. 
 
Abnormality Judgment: 
Continue 4 times in 20 minutes. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
114 
16.5.20 
  Outdoor Fan Motor (DC Motor) Mechanism Locked (F15) 
Malfunction Decision Conditions: 
The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine 
abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm). 
 
Malfunction Caused: 
1  Operation stop due to short circuit inside the fan motor winding. 
2  Operation stop due to breaking of wire inside the fan motor. 
3  Operation stop due to breaking of fan motor lead wires. 
4  Operation stop due to fan motor Hall IC malfunction. 
5  Operation error due to faulty outdoor unit PCB. 
 
Abnormality Judgment: 
Continue 2 times in 30 minutes. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
115 
16.5.21 
  Input Over Current Detection (F16) 
Malfunction Decision Conditions: 
During operation of cooling and heating, when outdoor current above 24.1 A (Heating) and 16.4 A (Cooling) 
[UD07FE5)] and 28.1 A (Heating) and 18.1 A (Cooling) [UD09FE5)] is detected by the current transformer (CT) in 
the outdoor unit PCB. 
 
Malfunction Caused: 
1  Excessive refrigerant. 
2  Faulty outdoor unit PCB (main). 
 
Abnormality Judgment: 
Continue 3 times in 20 minutes. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
116 
16.5.22 
  Compressor Overheating (F20) 
Malfunction Decision Conditions: 
During operation of cooling and heating, when temperature above 112°C is detected by the compressor tank 
temperature sensor. 
 
Malfunction Caused: 
1  Faulty compressor tank temperature sensor. 
2  2/3 way valve closed. 
3  Refrigerant shortage (refrigerant leakage). 
4  Clogged expansion valve or strainer. 
5  Faulty outdoor unit PCB (main). 
6  Faulty compressor. 
 
Abnormality Judgment: 
Continue 4 times in 30 minutes. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 