Tank Temperature Sensor Abnormality (H72) 
Malfunction Decision Conditions: 
When tank connection is set to ON, the temperatures detected by the tank temperature sensor are used to 
determine sensor error. 
 
Malfunction Caused: 
1  Faulty connector connection. 
2  Faulty sensor. 
3  Faulty indoor unit PCB (main). 
 
Abnormality Judgment: 
Continue for 5 seconds. 
 
 
106 
16.5.12 
Indoor-Control Panel Communication Abnormality (H76) 
Malfunction Decision Conditions: 
During standby and operation of cooling and heating, indoor-control panel error occur. 
 
Malfunction Caused: 
1  Faulty connector connection. 
2  Faulty control panel. 
3  Faulty indoor unit PCB (main). 
 
 
107 
16.5.13 
  Indoor/Outdoor Abnormal Communication (H90) 
Malfunction Decision Conditions: 
During operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is 
checked whether it is normal. 
 
Malfunction Caused: 
1  Faulty outdoor unit PCB (main). 
2  Faulty indoor unit PCB (main). 
3  Indoor-outdoor signal transmission error due to wrong wiring. 
4  Indoor-outdoor signal transmission error due to breaking of wire in the connection wires between the indoor 
and outdoor units. 
5  Indoor-outdoor signal transmission error due to disturbed power supply waveform. 
 
Abnormality Judgment: 
Continue for 1 minute after operation. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
108 
16.5.14 
  Tank Booster Heater OLP Abnormality (H91) 
Malfunction Decision Conditions: 
During operation of tank booster heater, and tank booster heater OLP open circuit. 
 
Malfunction Caused: 
1  Faulty connector connection. 
2  Faulty tank booster heater overload protector (OLP). 
3  Faulty indoor unit PCB (main). 
 
Abnormality Judgment: 
Continue for 60 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 127