81 
13.  Protection Control 
13.1  Protection Control for All Operations 
13.1.1  Time Delay Safety Control 
1  The compressor will not start for three minutes after stop of operation. 
13.1.2  30 Seconds Forced Operation 
1  Once the compressor starts operation, it will not stop its operation for 30 seconds. 
2  However, it can be stopped using control panel at indoor unit. 
13.1.3  Total Running Current Control 
1  When the outdoor running current exceeds X value, the compressor frequency will decrease. 
2  If the outdoor running current does not exceed X value, the compressor frequency will return to normal 
operating frequency. 
3  If the outdoor running current continue to increase till exceed Y value, compressor will stop, and if this occurs 
3 times within 20 minutes, system will stop operation and OFF/ON control panel LED will blink (F16 error 
occurs). 
 
 
UD07FE5 
UD09FE5 
Operation Mode 
X (A) 
Y (A) 
X (A) 
Y (A) 
Heating 
21.0 
27.9 
22.8 
27.9 
Cooling 
13.8 
27.9 
14.5 
27.9 
 
A.  DC Peak Current Control 
1  When the current to IPM exceeds set value of 34 A, compressor will stop. Compressor will restart after three 
minutes. 
2  If the set value exceeds again for more than 30 seconds after the compressor restarts, operation will restart 
after two minutes.  
3  If the set value exceeds again for within 30 seconds after the compressor restarts, operation will restart after 
one minute. If this condition repeats continuously for seven times, system will stop operation and OFF/ON 
control panel LED will blink (F23 error occurs). 
13.1.4  Compressor Overheating Prevention Control 
  The compressor operating frequency is regulated in accordance to compressor tank temperature as shown in 
below figures. When the compressor tank temperature exceeds 107°C, compressor will stop, and if this occurs 4 
times within 30 minutes, system will stop operation and OFF/ON control panel LED will blink (F20 error occurs). 
 
Compressor = OFF
Free
110°C
108°C
Compressor tank temperature
97°C
112°C
97°C
97°C
Compressor
Frequency Reduced
Compressor
Frequency Maintain
 
 
 
 
 
 
 
 
82 
13.1.5  Low Frequency Protection Control 2 
  When all the below conditions comply, the minimum compressor frequency will change to lower frequency. 
 
Temperature, T, for: 
Heating 
Cooling 
Outlet water (°C) 
T < 14 or T ≥ 48 
T < 14 or T ≥ 30 
Outdoor air (°C) 
T < 4 or T ≥ 24 
T < 13 or T ≥ 38 
Indoor heat exchanger (°C) 
T ≥ 0 
T < 30 
13.1.6  High Pressure Sensor Control 
  Purpose: 
- To protect the system operation. 
  Detection period: 
- After compressor on for 1 minute. 
  Detection conditions: 
- When abnormal high voltage detection, 5 V or when open circuit detection 0V for 5 seconds continuously. 
  After detection: 
- When abnormality is detected 4 times within 120 minutes, unit stop operation. 
- OFF/ON control panel LED will blink (H64 error occurs). 
13.1.7  Outside Temperature Current Control 
 
23°C
21°C
14°C
12°C
-25°C
-28°C
Compressor stop
Outdoor temperature
Max.
current
value is
regulated
 
13.1.8    Crank Case Heater Control 
  Purpose: 
- For compressor protection during low outdoor ambient operation (during heating low temperature operation). 
  Control content: 
a.  Trigger heater START condition 
o
 
When the outdoor air temperature is below than 5°C, and discharge temperature is 11°C or below. 
b.  Resetting heater STOP condition 
1. 
When the outdoor air temperature exceeds entry condition (2°C) 
2. 
When the discharge temperature exceeds entry condition (5°C) 
83 
13.2  Protection Control for Heating Operation 
13.2.1  Outdoor Air Temperature Control 
The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid 
compressor overloading. 
13.2.2  Deice Operation 
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor 
stop. 
 
  Deice judging condition 
 
-30
-30
-20
-10
0
10
20
30
-25
-20
-15
-10
-5
0
5
10
O
D
 P
ip
T
e
m
p
e
rat
u
re 
C)
Outdoor Unit Deice Control
line for continuous 3 minutes
and Pipe Temperature below this
When Heating Time > 35 minutes
Outdoor Temperature (°C)
3. Heating accumulation time
1. Outdoor air sensor temp.
2. Outdoor pipe sensor temp.
Deice start depends:
 
 
Deice operation time diagram 
 
a.  Deice mode 1 control: 
 
OD fan
ID pump
Expansion valve
Four way valve
Compressor
Free
Free
ON
OFF
OFF
ON
ON
Free
5
7
6
4
9
8
3
2
1
ON
ON
Free
Free
max 9 minutes 30 seconds
deice 1
 
 
84 
13.3  Protection Control for Cooling Operation 
13.3.1  Outdoor Air Temperature Control 
  The Compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the 
diagram below. 
  This control will begin 1 minute after the compressor starts. 
  Compressor frequency will adjust base on outdoor air temperature. 
 
 
 
13.3.2  Freeze Prevention Control 1 
1  When indoor heat exchanger temperature is lower than 0°C continuously for 10 seconds, compressor will 
stop operating. 
2  Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 1°C. 
3  Indoor heat exchanger freeze prevention (H99) will memory in error history. 
4  in error history. 