Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ▷ View online
1-1-2-27
1
1
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
: If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
: η
s,c
and
η
s,h
classification is at 230V(400V) only in accordance with EN-14825. For heating,
η
s,h
indicates the value of only Average heating season.
Single -Type
1-1. Unit Specifications
PE1
2. Ceiling Type S-140PT2E5B / U-140PE1E8A
INDOOR
MODEL
S-140PT2E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-140PE1E8A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz
1ø 50Hz
3ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
3.3
15.0
BTU/h
47800
47800
47800
-
-
-
11300
51200
Current
A
0.94
0.91
0.88
7.30
6.95
6.70
-
-
Input power
W
120
120
120
4.530k
4.530k
4.530k
-
-
TOTAL W
-
4.650k
4.650k
4.650k
840
5.650k
Annual consumption
TOTAL kWh *
4
-
-
2325
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.01
3.01 / B
3.01
3.93
2.65
Erp
*
6
Pdesign
kW
-
-
-
-
14.0
-
-
-
η
s,c
%
-
-
-
-
210.7
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
94
94
94
-
-
Noise indoor
dB-A (H/M/L)
47/41/37
-
-
-
-
-
Power Level dB
65/59/55
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
54/-
-
-
Power Level dB
-
71/-
-
-
H
E
A
T
I
N
G
Capacity
kW
16.0
16.0
16.0
-
-
-
4.1
18.0
BTU/h
54600
54600
54600
-
-
-
14000
61400
Current
A
0.94
0.91
0.88
6.85
6.50
6.25
-
-
Input power
W
120
120
120
4.240k
4.240k
4.240k
-
-
TOTAL W
-
4.360k
4.360k
4.360k
900
5.930k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.67
3.67 / A
3.67
4.56
3.04
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
14.0
-
-
-
Tbivalent
°C
-
-
-
-
-7
-
-
-
η
s,h
%
-
-
-
-
145.0
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
94
94
94
-
-
Noise indoor
dB-A (H/M/L)
47/41/37
-
-
-
Power Level dB
65/59/55
-
-
-
Noise outdoor
dB-A (H/L)
-
55/-
-
-
Power Level dB
-
71/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.94/120
0.91/120
0.88/120
11.0/6.81k
11.0/7.16k
11.0/7.43k
-
Starting current(A) / Comp output(W)
-
-
-
7.30/3.0k
6.95/3.0k
6.70/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
111
90×2
-
Moisture removal volume
L/h(Pt/h)
9.0
(18.9)
-
-
External static pressure
Pa
-
-
-
Indoor
Air flow
Cooling
m³/min (ft³/min)
35.0/29.0/25.0 (1236)/(1024)/(883)
-
-
-
Heating
m³/min (ft³/min)
35.0/29.0/25.0 (1236)/(1024)/(883)
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
135.0
(4767)
-
-
Heating
m³/min (ft³/min)
-
120.0
(4238)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
235 (9-1/4)
1416 (55-3/4)
-
Width
mm(inch)
1590 (62-19/32)
940 (37-1/32)
-
Depth
mm(inch)
690 (27-5/32)
340 (13-13/32)
-
Packing dimension
Height mm(inch)
360
1556
-
Width
mm(inch)
1655
1055
-
Depth
mm(inch)
820
485
-
Weight
(NET)
kg(lb)
40 (88)
98 (216)
-
(GROSS) kg(lb)
49 (108)
108 (238)
-
Layers limit (actually)
9 (10)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m
(0.538)
-
Pipe length for additional gas m (ft)
30m
(98.4)
-
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 27
19/09/26 17:01:24
1-1-3-1
1
1
Single -Type
1-1. Unit Specifications
PE2
3. Wall Mounted Type S-36PK2E5B / U-36PE2E5A
INDOOR
MODEL
S-36PK2E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-36PE2E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151 / EN14511 / EN12102/ EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
3.6
3.6
3.6
-
-
-
1.5
4.0
BTU/h
12300
12300
12300
-
-
-
5100
13600
Current
A
0.35
0.34
0.33
3.85
3.70
3.55
-
-
Input power
W
20
0.770k
0.770k
0.770k
-
-
TOTAL W
-
0.790k
0.790k
0.790k
240
930
Annual consumption
TOTAL kWh *
4
-
-
-
-
395
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.56
4.56/A
4.56
6.25
4.30
Erp
*
6
Pdesign
kW
-
-
-
-
3.6
-
-
-
SEER
(W/W)
-
-
-
-
6.4
-
-
-
Annual consumption
kWh
-
-
-
-
197
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
91
91
91
-
-
Noise indoor
dB-A (H/M/L) *
7
35/31/27
-
-
-
Power Level dB
51/47/43
-
-
-
Noise outdoor
dB-A (H/L)
-
45/-
-
-
Power Level dB
-
64/-
-
-
H
E
A
T
I
N
G
Capacity
kW
4.0
4.0
4.0
-
-
-
1.5
5.0
BTU/h
13600
13600
13600
-
-
-
5100
17100
Current
A
0.36
0.35
0.34
4.15
3.95
3.80
-
-
Input power
W
20
0.830k
0.830k
0.830k
-
-
TOTAL W
-
0.850k
0.850k
0.850k
190
1.190k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.71
4.71/A
4.71
7.89
4.20
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
3.6
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
4.3
-
-
-
Annual consumption
kWh
-
-
-
-
1172
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
91
91
91
-
-
Noise indoor
dB-A (H/M/L) *
7
35/31/27
-
-
-
Power Level dB
51/47/43
-
-
-
Noise outdoor
dB-A (H/L)
-
46/-
-
-
Power Level dB
-
66/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.36/20
0.35/20
0.34/20
11.0/2.20k
11.0/2.30k
11.0/2.40k
-
Starting current(A) / Comp output(W)
-
-
-
4.15/1.1k
3.95/1.1k
3.80/1.1k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
54
60
-
Moisture removal volume
L/h(Pt/h)
0.9
(1.9)
-
-
External static pressure
Pa
-
-
-
Indoor
Air flow *
7
Cooling
m³/min (ft³/min)
13.0/11.0/9.0 (459)/(388)/(318)
-
-
-
Heating
m³/min (ft³/min)
13.0/11.0/9.0 (459)/(388)/(318)
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
38.0 (1342)
-
-
Heating
m³/min (ft³/min)
-
38.0 (1342)
-
-
Refrigerant type / amount g(oz)
-
R410A
1.40k
(49.4)
-
Product dimension
Height mm(inch)
302
(11-29/32)
619
(24-3/8)
-
Width
mm(inch)
1120
(44-3/32)
799
(31-29/64)
-
Depth mm(inch)
236
(9-9/32)
299
(11-49/64)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
282
(11-1/8)
688
-
Width
mm(inch)
1190
(46-7/8)
931
-
Depth
mm(inch)
378
(14-29/32)
422
-
Weight
(NET)
kg(lb)
13
(29)
39
(86)
-
(GROSS) kg(lb)
16
(36)
44
(97)
-
Panel (NET) kg(lb)
-
-
-
Layers limit (actually)
11(12)
5(6)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
3 ~ 40m (9.8 ~ 131.2)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
20g/m (0.215)
-
Pipe length for additional gas m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 1
19/09/26 17:01:24
1-1-3-2
1
1
Simultaneous (Twin) -Type
1-1. Unit Specifications
PE1
3. Wall Mounted Type S-36PK2E5B×2 / U-71PE1E5A
INDOOR
MODEL
S-36PK2E5B×2
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-71PE1E5A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO5151 / EN14511 / EN12102/ EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
7.1
7.1
7.1
-
-
-
2.5
8.0
BTU/h
24200
24200
24200
-
-
-
8500
27300
Current
A
0.35×2
0.34×2
0.33×2
9.80
9.50
9.20
-
-
Input power
W
20×2
20×2
20×2
2.050k
2.050k
2.050k
-
-
TOTAL W
-
2.090k
2.090k
2.090k
450
2.650k
Annual consumption
TOTAL kWh *
4
-
-
-
-
1045
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.40
3.40/A
3.40
5.56
3.02
Erp
*
6
Pdesign
kW
-
-
-
-
7.1
-
-
-
SEER
(W/W)
-
-
-
-
6.6
-
-
-
Annual consumption
kWh
-
-
-
-
377
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
95
94
93
-
-
Noise indoor
dB-A (H/M/L) *
7
35/31/27
-
-
-
Power Level dB
51/47/43
-
-
-
Noise outdoor
dB-A (H/L)
-
48/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
8.0
8.0
8.0
-
-
-
2.0
9.0
BTU/h
27300
27300
27300
-
-
-
6800
30700
Current
A
0.36×2
0.35×2
0.34×2
9.30
8.95
8.70
-
-
Input power
W
20×2
20×2
20×2
1.960k
1.960k
1.960k
-
-
TOTAL W
-
2.000k
2.000k
2.000k
400
2.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.00
4.00/A
4.00
5.00
3.10
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
7.1
-
-
-
Tbivalent
°C
-
-
-
-
-9
-
-
-
SCOP
(W/W)
-
-
-
-
4.1
-
-
-
Annual consumption
kWh
-
-
-
-
2424
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
96
95
94
-
-
Noise indoor
dB-A (H/M/L) *
7
35/31/27
-
-
-
Power Level dB
51/47/43
-
-
-
Noise outdoor
dB-A (H/L)
-
50/-
-
-
Power Level dB
-
67/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.36/20×2
0.35/20×2
0.34/20×2
18.0/3.80k
18.0/3.93k
18.0/4.06k
-
Starting current(A) / Comp output(W)
-
-
-
9.80/2.0k
9.50/2.0k
9.20/2.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
54
90
-
Moisture removal volume
L/h(Pt/h)
1.8
(0.9×2)
(3.8)
-
-
External static pressure
Pa
-
-
-
Indoor
Air flow *
7
Cooling
m³/min (ft³/min)
13.0×2/11.0×2/9.0×2 (459)×2/(388)×2/(318)×2
-
-
-
Heating
m³/min (ft³/min)
13.0×2/11.0×2/9.0×2 (459)×2/(388)×2/(318)×2
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
60.0 (2119)
-
-
Heating
m³/min (ft³/min)
-
60.0 (2119)
-
-
Refrigerant type / amount g(oz)
-
R410A
2.35k
(82.9)
-
Product dimension
Height mm(inch)
302
(11-29/32)
996
(39-7/32)
-
Width
mm(inch)
1120
(44-3/32)
940
(37-1/32)
-
Depth mm(inch)
236
(9-9/32)
340
(13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
282
(11-1/8)
1136
-
Width
mm(inch)
1190
(46-7/8)
1055
-
Depth
mm(inch)
378
(14-29/32)
485
-
Weight
(NET)
kg(lb)
13
(29)
69
(153)
-
(GROSS) kg(lb)
16
(36)
77
(170)
-
Panel (NET) kg(lb)
-
-
-
Layers limit (actually)
11(12)
2(3)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5.8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 50m (16.4 ~ 164.0)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 2
19/09/26 17:01:24
1-1-3-3
1
1
Simultaneous (Triple) -Type
1-1. Unit Specifications
PE1
3. Wall Mounted Type S-36PK2E5B×3 / U-100PE1E5A
INDOOR
MODEL
S-36PK2E5B×3
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-100PE1E5A
-
Branch pipe
MODEL
CZ-P3HPC2
Performance test condition
ISO5151 / EN14511 / EN12102/ EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
10.0
10.0
10.0
-
-
-
3.3
12.5
BTU/h
34100
34100
34100
-
-
-
11300
42700
Current
A
0.35×3
0.34×3
0.33×3
12.0
11.4
11.0
-
-
Input power
W
20×3
20×3
20×3
2.520k
2.520k
2.520k
-
-
TOTAL W
-
2.580k
2.580k
2.580k
840
3.700k
Annual consumption
TOTAL kWh *
4
-
-
-
-
1290
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.88
3.88/A
3.88
3.93
3.38
Erp
*
6
Pdesign
kW
-
-
-
-
10.0
-
-
-
SEER
(W/W)
-
-
-
-
6.2
-
-
-
Annual consumption
kWh
-
-
-
-
564
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
96
96
96
-
-
Noise indoor
dB-A (H/M/L) *
7
35/31/27
-
-
-
Power Level dB
51/47/43
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
H
E
A
T
I
N
G
Capacity
kW
11.2
11.2
11.2
-
-
-
4.1
14.0
BTU/h
38200
38200
38200
-
-
-
14000
47800
Current
A
0.36×3
0.35×3
0.34×3
13.1
12.5
12.0
-
-
Input power
W
20×3
20×3
20×3
2.700k
2.700k
2.700k
-
-
TOTAL W
-
2.760k
2.760k
2.760k
900
4.400k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.06
4.06/A
4.06
4.56
3.18
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
10.0
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
4.0
-
-
-
Annual consumption
kWh
-
-
-
-
3500
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
94
94
94
-
-
Noise indoor
dB-A (H/M/L) *
7
35/31/27
-
-
-
Power Level dB
51/47/43
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.36/20×3
0.35/20×3
0.34/20×3
25.0/5.34k
25.0/5.52k
25.0/5.70k
-
Starting current(A) / Comp output(W)
-
-
-
13.1/3.0k
12.5/3.0k
12.0/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
54
90×2
-
Moisture removal volume
L/h(Pt/h)
2.7
(0.9×3)
(5.7)
-
-
External static pressure
Pa
-
-
-
Indoor
Air flow *
7
Cooling
m³/min (ft³/min)
13.0×3/11.0×3/9.0×3 (459×3)/(388×3)/(318×3)
-
-
-
Heating
m³/min (ft³/min)
13.0×3/11.0×3/9.0×3 (459×3)/(388×3)/(318×3)
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
110.0 (3885)
-
-
Heating
m³/min (ft³/min)
-
95.0 (3355)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
302
(11-29/32)
1416
(55-3/4)
-
Width
mm(inch)
1120
(44-3/32)
940
(37-1/32)
-
Depth mm(inch)
236
(9-9/32)
340
(13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
282
(11-1/8)
1556
-
Width
mm(inch)
1190
(46-7/8)
1055
-
Depth
mm(inch)
378
(14-29/32)
485
-
Weight
(NET)
kg(lb)
13
(29)
98
(216)
-
(GROSS) kg(lb)
16
(36)
108
(238)
-
Panel (NET) kg(lb)
-
-
-
Layers limit (actually)
11(12)
1(2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 75m (16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas m (ft)
20m (65.6)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 3
19/09/26 17:01:25
Click on the first or last page to see other U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B service manuals if exist.