DOWNLOAD Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ↓ Size: 129.09 MB | Pages: 127 in PDF or view online for FREE

Model
U-50PE2E5A U-100PE1E8A U-100PEY1E8 U-125PE1E8A U-125PEY1E8 U-140PE1E8A U-140PEY1E8 S-100PU2E5B S-125PU2E5B S-140PU2E5B S-71PU2E5B S-100PF1E5B S-125PF1E5B S-140PF1E5B S-71PF1E5B
Pages
127
Size
129.09 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
u-50pe2e5a-u-100pe1e8a-u-100pey1e8-u-125pe1e8a-u-1.pdf
Date

Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ▷ View online

1-1-2-11
1
1
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, 
Other fiche data indicates in an attached sheet.
Single -Type
1-1.  Unit Specifications
PE1
2. Ceiling Type S-71PT2E5B / U-71PE1E5A
INDOOR
MODEL
S-71PT2E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-71PE1E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151  /  EN14511  /  EN14825  /  EN12102
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
7.1
7.1
7.1
-
-
-
2.5
8.0
BTU/h
24200
24200
24200
-
-
-
8500
27300
Current
A
0.45
0.44
0.43
9.00
8.70
8.40
-
-
Input power
W
55
55
55
1.875k
1.875k
1.875k
-
-
TOTAL W
-
1.930k
1.930k
1.930k
450
2.780k
Annual consumption
TOTAL kWh *
4
-
-
965
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.68
3.68 / A
3.68
5.56
2.88
Erp
*
6
Pdesign
kW
-
-
-
-
7.1
-
-
-
SEER
(W/W)
-
-
-
-
6.2
-
-
-
Annual consumption
kWh
-
-
-
-
401
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
95
94
93
-
-
Noise indoor
dB-A (H/M/L)
39/35/31
-
-
-
-
-
Power Level dB
57/53/49
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
48/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
8.0
8.0
8.0
-
-
-
2.0
9.0
BTU/h
27300
27300
27300
-
-
-
6800
30700
Current
A
0.45
0.44
0.43
8.90
8.60
8.30
-
-
Input power
W
55
55
55
1.875k
1.875k
1.875k
-
-
TOTAL W
-
1.930k
1.930k
1.930k
400
2.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.15
4.15 / A
4.15
5.00
3.10
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
7.1
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
4.0
-
-
-
Annual consumption
kWh
-
-
-
-
2485
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
96
95
94
-
-
Noise indoor
dB-A (H/M/L)
39/35/31
-
-
-
Power Level dB
57/53/49
-
-
-
Noise outdoor
dB-A (H/L)
-
50/-
-
-
Power Level dB
-
67/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.45/55
0.44/55
0.43/55
18.0/3.76k
18.0/3.89k
18.0/4.02k
-
Starting current(A) / Comp output(W)
-
-
-
9.00/2.0k
8.70/2.0k
8.40/2.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
74
90
-
Moisture removal volume
L/h(Pt/h)
4.2
(8.8)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
21.0/18.0/15.5 (742) / (636) / (547)
-
-
-
Heating
m³/min (ft³/min)
21.0/18.0/15.5 (742) / (636) / (547)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
60.0
(2119)
-
-
Heating
m³/min (ft³/min)
-
60.0
(2119)
-
-
Refrigerant type / amount g(oz)
-
R410A
2.35k
(82.9)
-
Product dimension
Height mm(inch)
235   (9-1/4)
996   (39-7/32)
-
Width
mm(inch)
1275   (50-3/16)
940   (37-1/32)
-
Depth
mm(inch)
690   (27-5/32)
340   (13-13/32)
-
Packing dimension
Height mm(inch)
360
1136
-
Width
mm(inch)
1340
1055
-
Depth
mm(inch)
820
485
-
Weight
(NET)
kg(lb)
33   (73)
69   (152)
-
(GROSS)  kg(lb)
42   (93)
77   (170)
-
Layers limit (actually)
9 (10) 
2 (3) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 50m
(16.4 ~ 164)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   11
19/09/26   17:01:18
1-1-2-12
1
1
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:  η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
Simultaneous (Twin) -Type
1-1.  Unit Specifications
PE1
2. Ceiling Type S-71PT2E5B×2 / U-140PE1E5A
INDOOR
MODEL
S-71PT2E5B×2
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-140PE1E5A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
3.3
15.0
BTU/h
47800
47800
47800
-
-
-
11300
51200
Current
A
0.45×2
0.44×2
0.43×2
21.2
20.5
19.9
-
-
Input power
W
55×2
55×2
55×2
4.540k
4.540k
4.540k
-
-
TOTAL W
-
4.650k
4.650k
4.650k
840
5.650k
Annual consumption
TOTAL kWh *
4
-
-
2325
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.01
3.01 / B
3.01
3.93
2.65
Erp
*
6
Pdesign
kW
-
-
-
-
14.0
-
-
-
η 
s,c
%
-
-
-
-
221.9
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L)
39/35/31
-
-
-
-
-
Power Level dB
57/53/49
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
54/-
-
-
Power Level dB
-
71/-
-
-
H
E
A
T
I
N
G
Capacity
kW
16.0
16.0
16.0
-
-
-
4.1
18.0
BTU/h
54600
54600
54600
-
-
-
14000
61400
Current
A
0.45×2
0.44×2
0.43×2
19.9
19.2
18.6
-
-
Input power
W
55×2
55×2
55×2
4.250k
4.250k
4.250k
-
-
TOTAL W
-
4.360k
4.360k
4.360k
900
5.930k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.67
3.67 / A
3.67
4.56
3.04
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
14.0
-
-
-
Tbivalent
°C
-
-
-
-
-7
-
-
-
η 
s,h
%
-
-
-
-
145.5
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L)
39/35/31
-
-
-
Power Level dB
57/53/49
-
-
-
Noise outdoor
dB-A (H/L)
-
55/-
-
-
Power Level dB
-
71/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.45×2/55×2 0.44×2/55×2 0.43×2/55×2 30.0/6.40k
30.0/6.62k
30.0/6.84k
-
Starting current(A) / Comp output(W)
-
-
-
21.2/3.0k
20.5/3.0k
19.8/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
74
90×2
-
Moisture removal volume
L/h(Pt/h)
9.0
(4.5×2)
(18.9)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
21.0×2/18.0×2/15.5×2 (742)×2/(636)×2/(547)×2
-
-
-
Heating
m³/min (ft³/min)
21.0×2/18.0×2/15.5×2 (742)×2/(636)×2/(547)×2
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
135.0
(4767)
-
-
Heating
m³/min (ft³/min)
-
120.0
(4238)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
235   (9-1/4)
1416   (55-3/4)
-
Width
mm(inch)
1275   (50-3/16)
940   (37-1/32)
-
Depth
mm(inch)
690   (27-5/32)
340   (13-13/32)
-
Packing dimension
Height mm(inch)
360
1556
-
Width
mm(inch)
1340
1055
-
Depth
mm(inch)
820
485
-
Weight
(NET)
kg(lb)
33   (73)
98   (216)
-
(GROSS)  kg(lb)
42   (93)
108   (238)
-
Layers limit (actually)
9 (10) 
1 (2) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   12
19/09/26   17:01:19
1-1-2-13
1
1
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, 
Other fiche data indicates in an attached sheet.
Single -Type
1-1.  Unit Specifications
PE1
2. Ceiling Type S-100PT2E5B / U-100PE1E5A
INDOOR
MODEL
S-100PT2E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-100PE1E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151  /  EN14511  /  EN14825  /  EN12102
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
10.0
10.0
10.0
-
-
-
3.3
12.5
BTU/h
34100
34100
34100
-
-
-
11300
42700
Current
A
0.69
0.67
0.65
11.5
11.1
10.6
-
-
Input power
W
80
80
80
2.450k
2.450k
2.450k
-
-
TOTAL W
-
2.530k
2.530k
2.530k
840
3.850k
Annual consumption
TOTAL kWh *
4
-
-
1265
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.95
3.95 / A
3.95
3.93
3.25
Erp
*
6
Pdesign
kW
-
-
-
-
10.0
-
-
-
SEER
(W/W)
-
-
-
-
6.7
-
-
-
Annual consumption
kWh
-
-
-
-
523
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
97
96
96
-
-
Noise indoor
dB-A (H/M/L)
42/37/35
-
-
-
-
-
Power Level dB
60/55/53
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
H
E
A
T
I
N
G
Capacity
kW
11.2
11.2
11.2
-
-
-
4.1
14.0
BTU/h
38200
38200
38200
-
-
-
14000
47800
Current
A
0.69
0.67
0.65
11.8
11.4
11.0
-
-
Input power
W
80
80
80
2.520k
2.520k
2.520k
-
-
TOTAL W
-
2.600k
2.600k
2.600k
900
4.400k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.31
4.31 / A
4.31
4.56
3.18
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
10.0
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
4.3
-
-
-
Annual consumption
kWh
-
-
-
-
3256
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L)
42/37/35
-
-
-
Power Level dB
60/55/53
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.69/80
0.67/80
0.65/80
25.0/5.34k
25.0/5.52k
25.0/5.70k
-
Starting current(A) / Comp output(W)
-
-
-
11.8/3.0k
11.4/3.0k
11.0/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
111
90×2
-
Moisture removal volume
L/h(Pt/h)
6.0
(12.6)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
30.0/25.0/23.0 (1059) / (883) / (812)
-
-
-
Heating
m³/min (ft³/min)
30.0/25.0/23.0 (1059) / (883) / (812)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
110.0
(3885)
-
-
Heating
m³/min (ft³/min)
-
95.0
(3355)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
235   (9-1/4)
1416   (55-3/4)
-
Width
mm(inch)
1590   (62-19/32)
940   (37-1/32)
-
Depth
mm(inch)
690   (27-5/32)
340   (13-13/32)
-
Packing dimension
Height mm(inch)
360
1556
-
Width
mm(inch)
1655
1055
-
Depth
mm(inch)
820
485
-
Weight
(NET)
kg(lb)
40   (88)
98   (216)
-
(GROSS)  kg(lb)
49   (108)
108   (238)
-
Layers limit (actually)
9 (10) 
1 (2) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   13
19/09/26   17:01:19
1-1-2-14
1
1
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:  η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
Single -Type
1-1.  Unit Specifications
PE1
2. Ceiling Type S-125PT2E5B / U-125PE1E5A
INDOOR
MODEL
S-125PT2E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-125PE1E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
12.5
12.5
12.5
-
-
-
3.3
14.0
BTU/h
42700
42700
42700
-
-
-
11300
47800
Current
A
0.89
0.86
0.83
17.0
16.4
15.8
-
-
Input power
W
110
110
110
3.620k
3.620k
3.620k
-
-
TOTAL W
-
3.730k
3.730k
3.730k
840
4.860k
Annual consumption
TOTAL kWh *
4
-
-
1865
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.35
3.35 / A
3.35
3.93
2.88
Erp
*
6
Pdesign
kW
-
-
-
-
12.5
-
-
-
η 
s,c
%
-
-
-
-
227.4
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97
96
96
-
-
Noise indoor
dB-A (H/M/L)
46/40/36
-
-
-
-
-
Power Level dB
64/58/54
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
H
E
A
T
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
4.1
16.0
BTU/h
47800
47800
47800
-
-
-
14000
54600
Current
A
0.89
0.86
0.83
16.0
15.4
14.9
-
-
Input power
W
110
110
110
3.400k
3.400k
3.400k
-
-
TOTAL W
-
3.510k
3.510k
3.510k
900
5.210k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.99
3.99 / A
3.99
4.56
3.07
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
12.5
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
η 
s,h
%
-
-
-
-
149.5
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L)
46/40/36
-
-
-
Power Level dB
64/58/54
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.89/110
0.86/110
0.83/110
28.0/5.98k
28.0/6.18k
28.0/6.38k
-
Starting current(A) / Comp output(W)
-
-
-
17.0/3.0k
16.4/3.0k
15.8/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
111
90×2
-
Moisture removal volume
L/h(Pt/h)
7.9
(16.6)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
34.0/28.0/24.0 (1201) / (989) / (848)
-
-
-
Heating
m³/min (ft³/min)
34.0/28.0/24.0 (1201) / (989) / (848)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
130.0
(4591)
-
-
Heating
m³/min (ft³/min)
-
110.0
(3885)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
235   (9-1/4)
1416   (55-3/4)
-
Width
mm(inch)
1590   (62-19/32)
940   (37-1/32)
-
Depth
mm(inch)
690   (27-5/32)
340   (13-13/32)
-
Packing dimension
Height mm(inch)
360
1556
-
Width
mm(inch)
1655
1055
-
Depth
mm(inch)
820
485
-
Weight
(NET)
kg(lb)
40   (88)
98   (216)
-
(GROSS)  kg(lb)
49   (108)
108   (238)
-
Layers limit (actually)
9 (10) 
1 (2) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   14
19/09/26   17:01:19
Page of 127