Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ▷ View online

1-1-2-7
1
1
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, 
Other fiche data indicates in an attached sheet.
Simultaneous (Twin) -Type
1-1.  Unit Specifications
PE1
2. Ceiling Type S-50PT2E5B×2 / U-100PE1E5A
INDOOR
MODEL
S-50PT2E5B×2
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-100PE1E5A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO5151  /  EN14511  /  EN14825  /  EN12102
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
10.0
10.0
10.0
-
-
-
3.3
12.5
BTU/h
34100
34100
34100
-
-
-
11300
42700
Current
A
0.39×2
0.38×2
0.37×2
11.5
11.1
10.6
-
-
Input power
W
40×2
40×2
40×2
2.450k
2.450k
2.450k
-
-
TOTAL W
-
2.530k
2.530k
2.530k
840
3.850k
Annual consumption
TOTAL kWh *
4
-
-
1265
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.95
3.95 / A
3.95
3.93
3.25
Erp
*
6
Pdesign
kW
-
-
-
-
10.0
-
-
-
SEER
(W/W)
-
-
-
-
6.5
-
-
-
Annual consumption
kWh
-
-
-
-
539
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
97
96
96
-
-
Noise indoor
dB-A (H/M/L)
37/33/29
-
-
-
-
-
Power Level dB
55/51/47
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
H
E
A
T
I
N
G
Capacity
kW
11.2
11.2
11.2
-
-
-
4.1
14.0
BTU/h
38200
38200
38200
-
-
-
14000
47800
Current
A
0.39×2
0.38×2
0.37×2
11.8
11.4
11.0
-
-
Input power
W
40×2
40×2
40×2
2.520k
2.520k
2.520k
-
-
TOTAL W
-
2.600k
2.600k
2.600k
900
4.400k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.31
4.31 / A
4.31
4.56
3.18
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
10.0
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
4.3
-
-
-
Annual consumption
kWh
-
-
-
-
3256
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L)
37/33/29
-
-
-
Power Level dB
55/51/47
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.39×2/40×2 0.38×2/40×2 0.37×2/40×2 25.0/5.34k
25.0/5.52k
25.0/5.70k
-
Starting current(A) / Comp output(W)
-
-
-
11.8/3.0k
11.4/3.0k
11.0/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
43
90×2
-
Moisture removal volume
L/h(Pt/h)
6.0
(3.0×2)
(12.6)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
15.0×2/12.5×2/10.5×2 (530)×2/(441)×2/(371)×2
-
-
-
Heating
m³/min (ft³/min)
15.0×2/12.5×2/10.5×2 (530)×2/(441)×2/(371)×2
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
110.0
(3885)
-
-
Heating
m³/min (ft³/min)
-
95.0
(3355)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
235   (9-1/4)
1416   (55-3/4)
-
Width
mm(inch)
960   (37-25/32)
940   (37-1/32)
-
Depth
mm(inch)
690   (27-5/32)
340   (13-13/32)
-
Packing dimension
Height mm(inch)
360
1556
-
Width
mm(inch)
1025
1055
-
Depth
mm(inch)
820
485
-
Weight
(NET)
kg(lb)
27   (60)
98   (216)
-
(GROSS)  kg(lb)
34    (75)
108   (238)
-
Layers limit (actually)
9 (10) 
1 (2) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   7
19/09/26   17:01:17
1-1-2-8
1
1
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:  η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
Simultaneous (Triple) -Type
1-1.  Unit Specifications
PE1
2. Ceiling Type S-50PT2E5B×3 / U-140PE1E5A
INDOOR
MODEL
S-50PT2E5B×3
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-140PE1E5A
-
Branch pipe
MODEL
CZ-P3HPC2
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
3.3
15.5
BTU/h
47800
47800
47800
-
-
-
11300
51200
Current
A
0.39×3
0.38×3
0.37×3
21.2
20.5
19.8
-
-
Input power
W
40×3
40×3
40×3
4.530k
4.530k
4.530k
-
-
TOTAL W
-
4.650k
4.650k
4.650k
840
5.650k
Annual consumption
TOTAL kWh *
4
-
-
2325
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.01
3.01 / B
3.01
3.93
2.65
Erp
*
6
Pdesign
kW
-
-
-
-
14.0
-
-
-
η 
s,c
%
-
-
-
-
222.2
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L)
37/33/29
-
-
-
-
-
Power Level dB
55/51/47
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
54/-
-
-
Power Level dB
-
71/-
-
-
H
E
A
T
I
N
G
Capacity
kW
16.0
16.0
16.0
-
-
-
4.1
18.0
BTU/h
54600
54600
54600
-
-
-
14000
61400
Current
A
0.39×3
0.38×3
0.37×3
19.8
19.2
18.5
-
-
Input power
W
40×3
40×3
40×3
4.240k
4.240k
4.240k
-
-
TOTAL W
-
4.360k
4.360k
4.360k
900
5.930k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.67
3.67 / A
3.67
4.56
3.04
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
14.0
-
-
-
Tbivalent
°C
-
-
-
-
-7
-
-
-
η 
s,h
%
-
-
-
-
145.5
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L)
37/33/29
-
-
-
Power Level dB
55/51/47
-
-
-
Noise outdoor
dB-A (H/L)
-
55/-
-
-
Power Level dB
-
71/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.39×3/40×3 0.38×3/40×3 0.37×3/40×3 30.0/6.40k
30.0/6.62k
30.0/6.84k
-
Starting current(A) / Comp output(W)
-
-
-
21.2/3.0k
20.5/3.0k
19.8/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
43
90×2
-
Moisture removal volume
L/h(Pt/h)
9.0
(3.0×3)
(18.9)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
15.0×3/12.5×3/10.5×3 (530)×3/(441)×3/(371)×3
-
-
-
Heating
m³/min (ft³/min)
15.0×3/12.5×3/10.5×3 (530)×3/(441)×3/(371)×3
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
135.0
(4767)
-
-
Heating
m³/min (ft³/min)
-
120.0
(4238)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
235   (9-1/4)
1416   (55-3/4)
-
Width
mm(inch)
960   (37-25/32)
940   (37-1/32)
-
Depth
mm(inch)
690   (27-5/32)
340   (13-13/32)
-
Packing dimension
Height mm(inch)
360
1556
-
Width
mm(inch)
1025
1055
-
Depth
mm(inch)
820
485
-
Weight
(NET)
kg(lb)
27   (60)
98   (216)
-
(GROSS)  kg(lb)
34   (75)
108   (238)
-
Layers limit (actually)
9  (10) 
1 (2) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
20m
(65.6)
-
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   8
19/09/26   17:01:17
1-1-2-9
1
1
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230V (400V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230V (400V) only in accordance with EU directive 2002/31/EC.
*6
:  SEER and SCOP classification is at 230V (400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data 
indicates in an attached sheet.
Single -Type
1-1.  Unit Specifications
PE2
2. Ceiling Type S-60PT2E5B / U-60PE2E5A
INDOOR
MODEL
S-60PT2E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-60PE2E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
6.0
6.0
6.0
-
-
-
2.0 
7.1 
BTU/h
20500
20500
20500
-
-
-
6800 
24200 
Current
A
0.42
0.41
0.40
7.90 
7.50 
7.20 
-
-
Input power
W
50
50
50
1.560k
1.560k
1.560k
-
-
TOTAL W
-
1.610k
1.610k
1.610k
250
2.250k
Annual consumption
TOTAL kWh *
4
-
-
805
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.73 
3.73/A
3.73 
8.00
3.16
Erp
*
6
Pdesign
kW
-
-
-
-
6.0 
-
-
-
SEER
(W/W)
-
-
-
-
6.8 
-
-
-
Annual consumption
kWh
-
-
-
-
309 
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
90 
90 
90 
-
-
Noise indoor
dB-A (H/M/L)
38/34/30
-
-
-
-
-
Power Level dB
56/52/48
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
46/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
7.0
7.0
7.0
-
-
-
1.8 
8.0 
BTU/h
23900
23900
23900
-
-
-
6100 
27300 
Current
A
0.42
0.41
0.40
8.15 
7.80
7.45
-
-
Input power
W
50
50
50
1.610k
1.610k
1.610k
-
-
TOTAL W
-
1.660k
1.660k
1.660k
200
1.950k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.22 
4.22/A
4.22 
9.00
4.10
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
6.0 
-
-
-
Tbivalent
°C
-
-
-
-
-8 
-
-
-
SCOP
(W/W)
-
-
-
-
4.1 
-
-
-
Annual consumption
kWh
-
-
-
-
2050 
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
90 
90 
90 
-
-
Noise indoor
dB-A (H/M/L)
38/34/30
-
-
-
Power Level dB
56/52/48
-
-
-
Noise outdoor
dB-A (H/L)
-
49/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.42/50
0.41/50
0.40/50
16.5/3.27k
16.5/3.42k
16.5/3.57k
-
Starting current(A) / Comp output(W)
-
-
-
8.15/1.7k
7.80/1.7k
7.45/1.7k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
74
60
-
Moisture removal volume
L/h(Pt/h)
3.4
(7.1)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
20.0 / 17.0 / 14.5 (706) / (600) / (512)
-
-
-
Heating
m³/min (ft³/min)
20.0 / 17.0 / 14.5 (706) / (600) / (512)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
38.0
(1342)
-
-
Heating
m³/min (ft³/min)
-
41.0
(1448)
-
-
Refrigerant type / amount g(oz)
-
R410A
1.95k
(68.8)
-
Product dimension
Height mm(inch)
235   
(9-1/4)
619   
(24-3/8)
-
Width
mm(inch)
1275   
(50-3/16)
799   
(31-29/64)
-
Depth
mm(inch)
690   
(27-5/32)
299   
(11-49/64)
-
  Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
360
688 
-
Width
mm(inch)
1340
931 
-
Depth
mm(inch)
820
422 
-
Weight
(NET)
kg(lb)
33   
(73)
40   
(88)
-
(GROSS)  kg(lb)
42   
(93)
45   
(99)
-
Panel (NET)  kg(lb)
-
-
-
Layers limit (actually)
9 (10) 
5 (6) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
3 ~ 40m
(9.8 ~ 131.2)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
40g/m 
(0.430)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   9
19/09/26   17:01:17
1-1-2-10
1
1
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:  η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
Simultaneous (Twin) -Type
1-1.  Unit Specifications
PE1
2. Ceiling Type S-60PT2E5B×2 / U-125PE1E5A
INDOOR
MODEL
S-60PT2E5B×2
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-125PE1E5A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
12.5
12.5
12.5
-
-
-
3.3
14.0
BTU/h
42700
42700
42700
-
-
-
11300
47800
Current
A
0.42×2
0.41×2
0.40×2
17.0
16.4
15.9
-
-
Input power
W
50×2
50×2
50×2
3.630k
3.630k
3.630k
-
-
TOTAL W
-
3.730k
3.730k
3.730k
840
4.860k
Annual consumption
TOTAL kWh *
4
-
-
1865
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.35
3.35 / A
3.35
3.93
2.88
Erp
*
6
Pdesign
kW
-
-
-
-
12.5
-
-
-
η 
s,c
%
-
-
-
-
240.8
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L)
38/34/30
-
-
-
-
-
Power Level dB
56/52/48
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
H
E
A
T
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
4.1
16.0
BTU/h
47800
47800
47800
-
-
-
14000
54600
Current
A
0.42×2
0.41×2
0.40×2
16.0
15.4
14.9
-
-
Input power
W
50×2
50×2
50×2
3.410k
3.410k
3.410k
-
-
TOTAL W
-
3.510k
3.510k
3.510k
900
5.210k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.99
3.99 / A
3.99
4.56
3.07
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
12.5
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
η 
s,h
%
-
-
-
-
150.1
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L)
38/34/30
-
-
-
Power Level dB
56/52/48
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.42×2/50×2 0.41×2/50×2 0.40×2/50×2 28.0/5.98k
28.0/6.18k
28.0/6.38k
-
Starting current(A) / Comp output(W)
-
-
-
17.0/3.0k
16.4/3.0k
15.8/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
74
90×2
-
Moisture removal volume
L/h(Pt/h)
7.9
(3.9×2)
(16.6)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
20.0×2/17.0×2/14.5×2 (706)×2/(600)×2/(512)×2
-
-
-
Heating
m³/min (ft³/min)
20.0×2/17.0×2/14.5×2 (706)×2/(600)×2/(512)×2
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
130.0
(4591)
-
-
Heating
m³/min (ft³/min)
-
110.0
(3885)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
235   (9-1/4)
1416   (55-3/4)
-
Width
mm(inch)
1275   (50-3/16)
940   (37-1/32)
-
Depth
mm(inch)
690   (27-5/32)
340   (13-13/32)
-
Packing dimension
Height mm(inch)
360
1556
-
Width
mm(inch)
1340
1055
-
Depth
mm(inch)
820
485
-
Weight
(NET)
kg(lb)
33   (73)
98   (216)
-
(GROSS)  kg(lb)
42   (93)
108   (238)
-
Layers limit (actually)
9 (10) 
1 (2) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   10
19/09/26   17:01:18