1-1-1-15
1
1
Single-Type
1-1.  Unit Specifications
PE1
1. 4-Way Cassette Type S-125PU2E5B / U-125PE1E5A
INDOOR
MODEL
S-125PU2E5B
-
-
PANEL
MODEL
Standard type:CZ-KPU3:ECONAVI type:CZ-KPU3A
-
-
OUTDOOR
MODEL
-
U-125PE1E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
12.5 
12.5 
12.5 
-
-
-
3.3 
14.0 
BTU/h
42700
42700
42700
-
-
-
11300 
47800 
Current
A
0.91
0.88
0.85
15.2 
14.7 
14.3 
-
-
Input power
W
110
110
110
3.260k
3.260k
3.260k
-
-
TOTAL W
-
3.370k
3.370k
3.370k
770
4.600k
Annual consumption
TOTAL kWh *
4
-
-
-
-
1685
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.70 
3.70/A
3.70 
4.29
3.04
Erp
*
6
Pdesign
kW
-
-
-
-
12.5
-
-
-
η 
s,c
%
-
-
-
-
273.4
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
46/39/33
-
-
-
Power Level dB
61/54/48
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
H
E
A
T
I
N
G
Capacity
kW
14.0 
14.0 
14.0 
-
-
-
4.1 
16.0 
BTU/h
47800
47800
47800
-
-
-
14000 
54600 
Current
A
0.90 
0.87
0.84
13.7 
13.3 
12.9 
-
-
Input power
W
105
105
105
2.935k
2.935k
2.935k
-
-
TOTAL W
-
3.040k
3.040k
3.040k
790
5.040k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.60 
4.60/A
4.60 
5.19
3.17
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
12.5
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
η 
s,h
%
-
-
-
-
160.9
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
46/39/33
-
-
-
Power Level dB
61/54/48
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.91/110
0.88/110
0.85/110
28.0 / 6.00k 28.0 / 6.20k 28.0 / 6.40k
-
Starting current(A) / Comp output(W)
-
-
-
15.2 / 3.0k
14.7 / 3.0k
14.3 / 3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
90
90 ×2
-
Moisture removal volume
L/h(Pt/h)
4.8
 
(10.1)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
37.0/27.0/19.0 (1307)/(953)/(671)
-
-
-
Heating
m³/min (ft³/min)
37.0/27.0/19.0 (1307)/(953)/(671)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
130.0 (4591)
-
-
Heating
m³/min (ft³/min)
-
110.0 (3885)
-
-
Refrigerant type / amount g(oz)
-
R410A  
3.40k
(119.9)
-
Product dimension
Height mm(inch)
319 
(12-9/16)
1416 (55-3/4)
-
Width
mm(inch)
840 
(33-5/64)
940 (37-1/32)
-
Depth
mm(inch)
840 
(33-5/64)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
33.5×950×950
1-11/32 × 37-13/32 × 37-13/32
-
Packing dimension
Height mm(inch)
365 
(14-3/8)
1556 
-
Width
mm(inch)
898 
(35-3/8)
1055 
-
Depth
mm(inch)
898 
(35-3/8)
485 
-
Weight
(NET)
kg(lb)
25 
(55)
98
(216)
-
(GROSS)  kg(lb)
32 
(71)
108
(238)
-
Panel (NET)  kg(lb)
(11)
-
-
Layers limit (actually)
11 (12)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m (16.4 ~246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas  m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  
η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   15
19/09/26   17:01:09
1-1-1-16
1
1
Single-Type
1-1.  Unit Specifications
PE1
1. 4-Way Cassette Type S-140PU2E5B / U-140PE1E5A
INDOOR
MODEL
S-140PU2E5B
-
-
PANEL
MODEL
Standard type:CZ-KPU3:ECONAVI type:CZ-KPU3A
-
-
OUTDOOR
MODEL
-
U-140PE1E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
14.0 
14.0 
14.0 
-
-
-
3.3 
15.5 
BTU/h
47800
47800
47800
-
-
-
11300 
52900 
Current
A
0.97
0.94
0.91
19.3 
18.6 
18.0 
-
-
Input power
W
120
120
120
4.120k
4.120k
4.120k
-
-
TOTAL W
-
4.240k
4.240k
4.240k
770
5.740k
Annual consumption
TOTAL kWh *
4
-
-
-
-
2120
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.30 
3.30/A
3.30 
4.29
2.70
Erp
*
6
Pdesign
kW
-
-
-
-
14.0
-
-
-
η 
s,c
%
-
-
-
-
257.7
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
47/40/34
-
-
-
Power Level dB
62/55/49
-
-
-
Noise outdoor
dB-A (H/L)
-
54/-
-
-
Power Level dB
-
71/-
-
-
H
E
A
T
I
N
G
Capacity
kW
16.0 
16.0 
16.0 
-
-
-
4.1 
18.0 
BTU/h
54600
54600
54600
-
-
-
14000 
61400 
Current
A
0.96
0.93
0.90 
16.9 
16.3 
15.8 
-
-
Input power
W
115
115
115
3.605k
3.605k
3.605k
-
-
TOTAL W
-
3.720k
3.720k
3.720k
790
5.720k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.30 
4.30/A
4.30 
5.19
3.15
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
14.0
-
-
-
Tbivalent
°C
-
-
-
-
-7
-
-
-
η 
s,h
%
-
-
-
-
152.9
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
47/40/34
-
-
-
Power Level dB
62/55/49
-
-
-
Noise outdoor
dB-A (H/L)
-
55/-
-
-
Power Level dB
-
71/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.97/120
0.94/120
0.91/120
30.0 / 6.45k 30.0 / 6.65k 30.0 / 6.85k
-
Starting current(A) / Comp output(W)
-
-
-
19.3 / 3.0k
18.6 / 3.0k
18.0 / 3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
90
90 ×2
-
Moisture removal volume
L/h(Pt/h)
6.0
 
(12.6)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
38.0/29.0/20.0 (1342)/(1024)/(706)
-
-
-
Heating
m³/min (ft³/min)
38.0/29.0/20.0 (1342)/(1024)/(706)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
135.0 (4767)
-
-
Heating
m³/min (ft³/min)
-
120.0 (4238)
-
-
Refrigerant type / amount g(oz)
-
R410A  
3.40k
(119.9)
-
Product dimension
Height mm(inch)
319 
(12-9/16)
1416 (55-3/4)
-
Width
mm(inch)
840 
(33-5/64)
940 (37-1/32)
-
Depth
mm(inch)
840 
(33-5/64)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
33.5×950×950
1-11/32 × 37-13/32 × 37-13/32
-
Packing dimension
Height mm(inch)
365 
(14-3/8)
1556 
-
Width
mm(inch)
898 
(35-3/8)
1055 
-
Depth
mm(inch)
898 
(35-3/8)
485 
-
Weight
(NET)
kg(lb)
25 
(55)
98
(216)
-
(GROSS)  kg(lb)
32 
(71)
108
(238)
-
Panel (NET)  kg(lb)
(11)
-
-
Layers limit (actually)
11 (12)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m (16.4 ~246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas  m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  
η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   16
19/09/26   17:01:10
1-1-1-17
1
1
Simultaneous (Twin) -Type
1-1.  Unit Specifications
PE1
1. 4-Way Cassette Type S-36PU2E5B×2 / U-71PE1E8A
INDOOR
MODEL
S-36PU2E5B×2
-
-
PANEL
MODEL
Standard type:CZ-KPU3 ×2 / ECONAVI type:CZ-KPU3A ×2
-
-
OUTDOOR
MODEL
-
U-71PE1E8A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1Ø 50Hz
3Ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
7.1 
7.1 
7.1 
-
-
-
3.2 
8.0 
BTU/h
24200
24200
24200
-
-
-
10900 
27300 
Current
A
0.23 ×2
0.23 ×2
0.22 ×2
2.85 
2.70 
2.60 
-
-
Input power
W
24 ×2
24 ×2
24 ×2
1.762k
1.762k
1.762k
-
-
TOTAL W
-
1.810k
1.810k
1.810k
560
2.650k
Annual consumption
TOTAL kWh *
4
-
-
-
-
905
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.92 
3.92/A
3.92 
5.71
3.02
Erp
*
6
Pdesign
kW
-
-
-
-
7.1 
-
-
-
SEER
(W/W)
-
-
-
-
7.1 
-
-
-
Annual consumption
kWh
-
-
-
-
350
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
94 
94 
94 
-
-
Noise indoor
dB-A (H/M/L) *
7
30/28/27
-
-
-
Power Level dB
45/43/42
-
-
-
Noise outdoor
dB-A (H/L)
-
48/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
8.0 
8.0 
8.0 
-
-
-
2.8 
9.0 
BTU/h
27300
27300
27300
-
-
-
9600 
30700 
Current
A
0.22 ×2
0.22 ×2
0.21 ×2
2.95 
2.80 
2.70 
-
-
Input power
W
22 ×2
22 ×2
22 ×2
1.826k
1.826k
1.826k
-
-
TOTAL W
-
1.870k
1.870k
1.870k
500
2.850k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.28 
4.28/A
4.28 
5.60
3.16
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
7.1 
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
4.3 
-
-
-
Annual consumption
kWh
-
-
-
-
2312
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
94 
94 
94 
-
-
Noise indoor
dB-A (H/M/L) *
7
30/28/27
-
-
-
Power Level dB
45/43/42
-
-
-
Noise outdoor
dB-A (H/L)
-
50/-
-
-
Power Level dB
-
67/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.23×2/24×2 0.23×2/24×2
0.22×2/24×2 7.00 / 4.15k 7.00 / 4.36k 7.00 / 4.53k
-
Starting current(A) / Comp output(W)
-
-
-
2.95 / 2.0k
2.80 / 2.0k
2.70 / 2.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
60
90
-
Moisture removal volume
L/h(Pt/h)
1.4
 (0.7×2)
(2.9)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
14.5×2/13.0×2/11.5×2 (512)×2/(459)×2/(406)×2
-
-
-
Heating
m³/min (ft³/min)
14.5×2/13.0×2/11.5×2 (512)×2/(459)×2/(406)×2
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
60.0 (2119)
-
-
Heating
m³/min (ft³/min)
-
60.0 (2119)
-
-
Refrigerant type / amount g(oz)
-
R410A  
2.35k
(82.9)
-
Product dimension
Height mm(inch)
256
(10-5/64)
996 (39-7/32)
-
Width
mm(inch)
840 
(33-5/64)
940 (37-1/32)
-
Depth
mm(inch)
840 
(33-5/64)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
33.5×950×950
1-11/32 × 37-13/32 × 37-13/32
-
Packing dimension
Height mm(inch)
302 
(11-57/64)
1136 
-
Width
mm(inch)
898 
(35-3/8)
1055 
-
Depth
mm(inch)
898 
(35-3/8)
485 
-
Weight
(NET)
kg(lb)
19 
(42)
71
(157)
-
(GROSS)  kg(lb)
26 
(57)
79
(174)
-
Panel (NET)  kg(lb)
(11)
-
-
Layers limit (actually)
11 (12)
2 (3)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 50m (16.4 ~164)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas  m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data  
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   17
19/09/26   17:01:10
1-1-1-18
1
1
Simultaneous (Triple) -Type
1-1.  Unit Specifications
PE1
1. 4-Way Cassette Type S-36PU2E5B×3 / U-100PE1E8A
INDOOR
MODEL
S-36PU2E5B×3
-
-
PANEL
MODEL
Standard type:CZ-KPU3 ×3 / ECONAVI type:CZ-KPU3A ×3
-
-
OUTDOOR
MODEL
-
U-100PE1E8A
-
Branch pipe
MODEL
CZ-P3HPC2
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1Ø 50Hz
3Ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
10.0 
10.0 
10.0 
-
-
-
3.3 
12.5 
BTU/h
34100
34100
34100
-
-
-
11300 
42700 
Current
A
0.23 ×3
0.23 ×3
0.22 ×3
3.65 
3.50 
3.40 
-
-
Input power
W
24 ×3
24 ×3
24 ×3
2.268k
2.268k
2.268k
-
-
TOTAL W
-
2.340k
2.340k
2.340k
770
3.700k
Annual consumption
TOTAL kWh *
4
-
-
-
-
1170
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.27 
4.27/A
4.27 
4.29
3.38
Erp
*
6
Pdesign
kW
-
-
-
-
10.0 
-
-
-
SEER
(W/W)
-
-
-
-
7.1 
-
-
-
Annual consumption
kWh
-
-
-
-
493
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
94 
94 
93 
-
-
Noise indoor
dB-A (H/M/L) *
7
30/28/27
-
-
-
Power Level dB
45/43/42
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
H
E
A
T
I
N
G
Capacity
kW
11.2 
11.2 
11.2 
-
-
-
4.1 
14.0 
BTU/h
38200
38200
38200
-
-
-
14000 
47800 
Current
A
0.22 ×3
0.22 ×3
0.21×3
3.50 
3.35 
3.25 
-
-
Input power
W
22 ×3
22 ×3
22 ×3
2.174k
2.174k
2.174k
-
-
TOTAL W
-
2.240k
2.240k
2.240k
790
4.400k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
5.00 
5.00/A
5.00 
5.19
3.18
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
10.0 
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
4.8 
-
-
-
Annual consumption
kWh
-
-
-
-
2917
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
94 
94 
93 
-
-
Noise indoor
dB-A (H/M/L) *
7
30/28/27
-
-
-
Power Level dB
45/43/42
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.23×3/24×3 0.23×3/24×3
0.22×3/24×3 9.00 / 5.55k 9.00 / 5.85k 9.00 / 6.10k
-
Starting current(A) / Comp output(W)
-
-
-
3.65 / 3.0k
3.50 / 3.0k
3.40 / 3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
60
90 ×2
-
Moisture removal volume
L/h(Pt/h)
2.1
 (0.7×3)
(4.4)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
14.5×3/13.0×3/11.5×3 (512)×3/(459)×3/(406)×3
-
-
-
Heating
m³/min (ft³/min)
14.5×3/13.0×3/11.5×3 (512)×3/(459)×3/(406)×3
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
110.0 (3885)
-
-
Heating
m³/min (ft³/min)
-
95.0 (3355)
-
-
Refrigerant type / amount g(oz)
-
R410A  
3.40k
(119.9)
-
Product dimension
Height mm(inch)
256
(10-5/64)
1416 (55-3/4)
-
Width
mm(inch)
840 
(33-5/64)
940 (37-1/32)
-
Depth
mm(inch)
840 
(33-5/64)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
33.5×950×950
1-11/32 × 37-13/32 × 37-13/32
-
Packing dimension
Height mm(inch)
302 
(11-57/64)
1556 
-
Width
mm(inch)
898 
(35-3/8)
1055 
-
Depth
mm(inch)
898 
(35-3/8)
485 
-
Weight
(NET)
kg(lb)
19 
(42)
98
(216)
-
(GROSS)  kg(lb)
26 
(57)
108
(238)
-
Panel (NET)  kg(lb)
(11)
-
-
Layers limit (actually)
11 (12)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m (16.4 ~246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas  m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data  
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   18
19/09/26   17:01:11