DOWNLOAD Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ↓ Size: 129.09 MB | Pages: 127 in PDF or view online for FREE

Model
U-50PE2E5A U-100PE1E8A U-100PEY1E8 U-125PE1E8A U-125PEY1E8 U-140PE1E8A U-140PEY1E8 S-100PU2E5B S-125PU2E5B S-140PU2E5B S-71PU2E5B S-100PF1E5B S-125PF1E5B S-140PF1E5B S-71PF1E5B
Pages
127
Size
129.09 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
u-50pe2e5a-u-100pe1e8a-u-100pey1e8-u-125pe1e8a-u-1.pdf
Date

Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ▷ View online

1-1-1-7
1
1
Single -Type
1-1.  Unit Specifications
PE2
1. 4-Way Cassette Type S-50PU2E5B / U-50PE2E5A
INDOOR
MODEL
S-50PU2E5B
-
-
PANEL
MODEL
Standard type:CZ-KPU3 / ECONAVI type:CZ-KPU3A
-
-
OUTDOOR
MODEL
-
U-50PE2E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
5.0 
5.0 
5.0 
-
-
-
1.5 
5.6 
BTU/h
17100
17100
17100
-
-
-
5100
19100
Current
A
0.27 
0.26 
0.25 
6.25 
5.95 
5.70 
-
-
Input power
W
29
29
29
1.291k
1.291k
1.291k
-
-
TOTAL W
-
1.320k
1.320k
1.320k
240
1.620k
Annual consumption
TOTAL kWh *
4
-
-
-
-
660
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.79 
3.79/A
3.79 
6.25
3.46
Erp
*
6
Pdesign
kW
-
-
-
-
5.0 
-
-
-
SEER
(W/W)
-
-
-
-
7.1 
-
-
-
Annual consumption
kWh
-
-
-
-
246 
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
94 
94 
94 
-
-
Noise indoor
dB-A (H/M/L) *
7
32/29/27
-
-
-
Power Level dB
47/44/42
-
-
-
Noise outdoor
dB-A (H/L)
-
46/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
5.6 
5.6 
5.6 
-
-
-
1.5 
6.5 
BTU/h
19100
19100
19100
-
-
-
5100
22200
Current
A
0.26 
0.25
0.24
6.05 
5.75
5.50
-
-
Input power
W
27
27
27
1.233k
1.233k
1.233k
-
-
TOTAL W
-
1.260k
1.260k
1.260k
190
1.620k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.44 
4.44/A
4.44 
7.89
4.01
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
5.0 
-
-
-
Tbivalent
°C
-
-
-
-
-7 
-
-
-
SCOP
(W/W)
-
-
-
-
4.4 
-
-
-
Annual consumption
kWh
-
-
-
-
1591 
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
93 
93 
93 
-
-
Noise indoor
dB-A (H/M/L) *
7
32/29/27
-
-
-
Power Level dB
47/44/42
-
-
-
Noise outdoor
dB-A (H/L)
-
48/-
-
-
Power Level dB
-
68/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.27 / 29
0.26 / 29
0.25 / 29
12.0 / 2.46k 12.0 / 2.57k 12.0 / 2.68k
-
Starting current(A) / Comp output(W)
-
-
-
6.25 / 1.5k
5.95 / 1.5k
5.70 / 1.5k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
60
60
-
Moisture removal volume
L/h(Pt/h)
1.6
 
(3.4)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
16.5 / 13.5 / 11.5 (583) / (477) / (406)
-
-
-
Heating
m³/min (ft³/min)
16.5 / 13.5 / 11.5 (583) / (477) / (406)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
38.0 (1342)
-
-
Heating
m³/min (ft³/min)
-
41.0 (1448)
-
-
Refrigerant type / amount g(oz)
-
R410A
1.40k
(49.4)
-
Product dimension
Height mm(inch)
256 
(10-5/64)
619 
(24-3/8)
-
Width
mm(inch)
840 
(33-5/64)
799 
(31-29/64)
-
Depth
mm(inch)
840 
(33-5/64)
299 
(11-49/64)
-
Product dimension (Panel) H×W×D mm, inch
33.5×950×950
1-11/32 × 37-13/32 × 37-13/32
-
Packing dimension
Height mm(inch)
302 
(11-57/64)
688 
-
Width
mm(inch)
898 
(35-3/8)
931 
-
Depth
mm(inch)
898 
(35-3/8)
422 
-
Weight
(NET)
kg(lb)
19 
(42)
39
(86)
-
(GROSS)  kg(lb)
26 
(57)
44
(97)
-
Panel (NET)  kg(lb)
(11)
-
-
Layers limit (actually)
11 (12)
5 (6)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
3 ~ 40m (9.8 ~131.2)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
20g/m (0.215)
-
Pipe length for additional gas  m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data  
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   7
19/09/26   17:01:06
1-1-1-8
1
1
Simultaneous (Twin) -Type
1-1.  Unit Specifications
PE1
1. 4-Way Cassette Type S-50PU2E5B×2 / U-100PE1E5A
INDOOR
MODEL
S-50PU2E5B×2
-
-
PANEL
MODEL
Standard type:CZ-KPU3 ×2 / ECONAVI type:CZ-KPU3A ×2
-
-
OUTDOOR
MODEL
-
U-100PE1E5A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
10.0 
10.0 
10.0 
-
-
-
3.3 
12.5 
BTU/h
34100
34100
34100
-
-
-
11300 
42700 
Current
A
0.27 ×2
0.26 ×2
0.25 ×2
10.7 
10.3 
9.9 
-
-
Input power
W
29 ×2
29 ×2
29 ×2
2.282k
2.282k
2.282k
-
-
TOTAL W
-
2.340k
2.340k
2.340k
770
3.700k
Annual consumption
TOTAL kWh *
4
-
-
-
-
1170
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.27 
4.27/A
4.27 
4.29
3.38
Erp
*
6
Pdesign
kW
-
-
-
-
10.0 
-
-
-
SEER
(W/W)
-
-
-
-
7.4 
-
-
-
Annual consumption
kWh
-
-
-
-
473
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
97 
96 
96 
-
-
Noise indoor
dB-A (H/M/L) *
7
32/29/27
-
-
-
Power Level dB
47/44/42
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
H
E
A
T
I
N
G
Capacity
kW
11.2 
11.2 
11.2 
-
-
-
4.1 
14.0 
BTU/h
38200
38200
38200
-
-
-
14000 
47800 
Current
A
0.26 ×2
0.25 ×2
0.24×2
10.2 
9.9 
9.6 
-
-
Input power
W
27 ×2
27 ×2
27 ×2
2.186k
2.186k
2.186k
-
-
TOTAL W
-
2.240k
2.240k
2.240k
790
4.400k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
5.00 
5.00/A
5.00 
5.19
3.18
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
10.0 
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
4.8 
-
-
-
Annual consumption
kWh
-
-
-
-
2917
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
32/29/27
-
-
-
Power Level dB
47/44/42
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.27×2/29×2 0.26×2/29×2 0.25×2/29×2 25.0 / 5.35k 25.0 / 5.55k 25.0 / 5.75k
-
Starting current(A) / Comp output(W)
-
-
-
10.7 / 3.0k
10.3 / 3.0k
9.9 / 3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
60
90 × 2
-
Moisture removal volume
L/h(Pt/h)
3.2
(1.6×2)
(6.7)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
16.5×2/13.5×2/11.5×2 (583)×2/(477)×2/(406)×2
-
-
-
Heating
m³/min (ft³/min)
16.5×2/13.5×2/11.5×2 (583)×2/(477)×2/(406)×2
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
110.0 (3885)
-
-
Heating
m³/min (ft³/min)
-
95.0 (3355)
-
-
Refrigerant type / amount g(oz)
-
R410A  
3.40k
(119.9)
-
Product dimension
Height mm(inch)
256 
(10-5/64)
1416 (55-3/4)
-
Width
mm(inch)
840 
(33-5/64)
940 (37-1/32)
-
Depth
mm(inch)
840 
(33-5/64)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
33.5×950×950
1-11/32 × 37-13/32 × 37-13/32
-
Packing dimension
Height mm(inch)
302 
(11-57/64)
1556 
-
Width
mm(inch)
898 
(35-3/8)
1055 
-
Depth
mm(inch)
898 
(35-3/8)
485 
-
Weight
(NET)
kg(lb)
19 
(42)
98
(216)
-
(GROSS)  kg(lb)
26 
(57)
108
(238)
-
Panel (NET)  kg(lb)
(11)
-
-
Layers limit (actually)
11 (12)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m (16.4 ~246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas  m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data  
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   8
19/09/26   17:01:07
1-1-1-9
1
1
Simultaneous (Triple) -Type
1-1.  Unit Specifications
PE1
1. 4-Way Cassette Type S-50PU2E5B×3 / U-140PE1E5A
INDOOR
MODEL
S-50PU2E5B×3
-
-
PANEL
MODEL
Standard type:CZ-KPU3 ×3 / ECONAVI type:CZ-KPU3A ×3
-
-
OUTDOOR
MODEL
-
U-140PE1E5A
-
Branch pipe
MODEL
CZ-P3HPC2
Performance test condition
ISO5151  /  EN14511  /  EN12102   /  EN14825 
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
14.0 
14.0 
14.0 
-
-
-
3.3 
15.5 
BTU/h
47800
47800
47800
-
-
-
11300 
52900 
Current
A
0.27 ×3
0.26 ×3
0.25 ×3
19.4 
18.8 
18.2 
-
-
Input power
W
29 ×3
29 ×3
29 ×3
4.153k
4.153k
4.153k
-
-
TOTAL W
-
4.240k
4.240k
4.240k
770
5.740k
Annual consumption
TOTAL kWh *
4
-
-
-
-
2120
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.30 
3.30/A
3.30 
4.29
2.70
Erp
*
6
Pdesign
kW
-
-
-
-
14.0
-
-
-
η 
s,c
%
-
-
-
-
260.9
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
32/29/27
-
-
-
Power Level dB
47/44/42
-
-
-
Noise outdoor
dB-A (H/L)
-
54/-
-
-
Power Level dB
-
71/-
-
-
H
E
A
T
I
N
G
Capacity
kW
16.0 
16.0 
16.0 
-
-
-
4.1 
18.0 
BTU/h
54600
54600
54600
-
-
-
14000 
61400 
Current
A
0.26 ×3
0.25 ×3
0.24×3
17.0 
16.4 
15.9 
-
-
Input power
W
27 ×3
27 ×3
27 ×3
3.639k
3.639k
3.639k
-
-
TOTAL W
-
3.720k
3.720k
3.720k
790
5.720k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.30 
4.30/A
4.30 
5.19
3.15
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
14.0
-
-
-
Tbivalent
°C
-
-
-
-
-7
-
-
-
η 
s,h
%
-
-
-
-
152.9
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
32/29/27
-
-
-
Power Level dB
47/44/42
-
-
-
Noise outdoor
dB-A (H/L)
-
55/-
-
-
Power Level dB
-
71/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.27×3/29×3 0.26×3/29×3 0.25×3/29×3 30.0 / 6.45k 30.0 / 6.65k 30.0 / 6.85k
-
Starting current(A) / Comp output(W)
-
-
-
19.4 / 3.0k
18.8 / 3.0k
18.2 / 3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
60
90 × 2
-
Moisture removal volume
L/h(Pt/h)
4.8
(1.6×3)
(10.1)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
16.5×3/13.5×3/11.5×3 (583)×3/(477)×3/(406)×3
-
-
-
Heating
m³/min (ft³/min)
16.5×3/13.5×3/11.5×3 (583)×3/(477)×3/(406)×3
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
135.0 (4767)
-
-
Heating
m³/min (ft³/min)
-
120.0 (4238)
-
-
Refrigerant type / amount g(oz)
-
R410A  
3.40k
(119.9)
-
Product dimension
Height mm(inch)
256 
(10-5/64)
1416 (55-3/4)
-
Width
mm(inch)
840 
(33-5/64)
940 (37-1/32)
-
Depth
mm(inch)
840 
(33-5/64)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
33.5×950×950
1-11/32 × 37-13/32 × 37-13/32
-
Packing dimension
Height mm(inch)
302 
(11-57/64)
1556 
-
Width
mm(inch)
898 
(35-3/8)
1055 
-
Depth
mm(inch)
898 
(35-3/8)
485 
-
Weight
(NET)
kg(lb)
19 
(42)
98
(216)
-
(GROSS)  kg(lb)
26 
(57)
108
(238)
-
Panel (NET)  kg(lb)
(11)
-
-
Layers limit (actually)
11 (12)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m (16.4 ~246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas  m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  
η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   9
19/09/26   17:01:07
1-1-1-10
1
1
Single -Type
1-1.  Unit Specifications
PE2
1. 4-Way Cassette Type S-60PU2E5B / U-60PE2E5A
INDOOR
MODEL
S-60PU2E5B
-
-
PANEL
MODEL
Standard type:CZ-KPU3 / ECONAVI type:CZ-KPU3A
-
-
OUTDOOR
MODEL
-
U-60PE2E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
6.0 
6.0 
6.0 
-
-
-
2.0 
7.1 
BTU/h
20500
20500
20500
-
-
-
6800 
24200 
Current
A
0.36 
0.35 
0.34 
7.90 
7.50 
7.25 
-
-
Input power
W
38
38
38
1.562k
1.562k
1.562k
-
-
TOTAL W
-
1.600k
1.600k
1.600k
250
2.200k
Annual consumption
TOTAL kWh *
4
-
-
-
-
800
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.75 
3.75/A
3.75 
8.00
3.23
Erp
*
6
Pdesign
kW
-
-
-
-
6.0 
-
-
-
SEER
(W/W)
-
-
-
-
7.4 
-
-
-
Annual consumption
kWh
-
-
-
-
284 
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
90 
90 
90 
-
-
Noise indoor
dB-A (H/M/L) *
7
36/31/28
-
-
-
Power Level dB
51/46/43
-
-
-
Noise outdoor
dB-A (H/L)
-
46/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
7.0 
7.0 
7.0 
-
-
-
1.8 
8.0 
BTU/h
23900
23900
23900
-
-
-
6100 
27300 
Current
A
0.35 
0.34
0.33
8.50
8.15
7.80
-
-
Input power
W
36
36
36
1.684k
1.684k
1.684k
-
-
TOTAL W
-
1.720k
1.720k
1.720k
200
2.050k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.07 
4.07/A
4.07 
9.00
3.90
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
6.0 
-
-
-
Tbivalent
°C
-
-
-
-
-8 
-
-
-
SCOP
(W/W)
-
-
-
-
4.2 
-
-
-
Annual consumption
kWh
-
-
-
-
1999 
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
90 
90 
90 
-
-
Noise indoor
dB-A (H/M/L) *
7
36/31/28
-
-
-
Power Level dB
51/46/43
-
-
-
Noise outdoor
dB-A (H/L)
-
49/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.36 / 38
0.35 / 38
0.34 / 38
16.5 / 3.27k 16.5 / 3.42k 16.5 / 3.57k
-
Starting current(A) / Comp output(W)
-
-
-
8.50 / 1.7k
8.15 / 1.7k
7.80 / 1.7k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
60
60
-
Moisture removal volume
L/h(Pt/h)
1.7
 
(3.6)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
21.0 / 16.0 / 13.0 (742) / (565) / (459)
-
-
-
Heating
m³/min (ft³/min)
21.0 / 16.0 / 13.0 (742) / (565) / (459)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
38.0 (1342)
-
-
Heating
m³/min (ft³/min)
-
41.0 (1448)
-
-
Refrigerant type / amount g(oz)
-
R410A  
1.95k
(68.8)
-
Product dimension
Height mm(inch)
256 
(10-5/64)
619 
(24-3/8)
-
Width
mm(inch)
840 
(33-5/64)
799 
(31-29/64)
-
Depth
mm(inch)
840 
(33-5/64)
299 
(11-49/64)
-
Product dimension (Panel) H×W×D mm, inch
33.5×950×950
1-11/32 × 37-13/32 × 37-13/32
-
Packing dimension
Height mm(inch)
302 
(11-57/64)
688 
-
Width
mm(inch)
898 
(35-3/8)
931 
-
Depth
mm(inch)
898 
(35-3/8)
422 
-
Weight
(NET)
kg(lb)
20 
(44)
40
(88)
-
(GROSS)  kg(lb)
27 
(60)
45
(99)
-
Panel (NET)  kg(lb)
(11)
-
-
Layers limit (actually)
11 (12)
5 (6)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
3 ~ 40m (9.8 ~131.2)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
40g/m (0.430)
-
Pipe length for additional gas  m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data  
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   10
19/09/26   17:01:08
Page of 127