DOWNLOAD Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ↓ Size: 129.09 MB | Pages: 127 in PDF or view online for FREE

Model
U-50PE2E5A U-100PE1E8A U-100PEY1E8 U-125PE1E8A U-125PEY1E8 U-140PE1E8A U-140PEY1E8 S-100PU2E5B S-125PU2E5B S-140PU2E5B S-71PU2E5B S-100PF1E5B S-125PF1E5B S-140PF1E5B S-71PF1E5B
Pages
127
Size
129.09 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
u-50pe2e5a-u-100pe1e8a-u-100pey1e8-u-125pe1e8a-u-1.pdf
Date

Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ▷ View online

1-1-5-6
1
1
Single -Type
1-1.  Unit Specifications
PE2
5. Ducted Type S-50PN1E5B / U-50PE2E5A
INDOOR
MODEL
S-50PN1E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-50PE2E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253  /  EN14511  /  EN14825  /  EN12102
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
5.0
5.0
5.0
-
-
-
1.5 
5.6
BTU/h
17100
17100
17100
-
-
-
5100
19100
Current
A
0.54
0.55
0.56
7.00
6.65
6.35
-
-
Input power
W
115
120
125
1.445k
1.440k
1.435k
-
-
TOTAL W
-
1.560k
1.560k
1.560k
340
1.890k
Annual consumption
TOTAL kWh *
4
-
-
780
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.21
3.21/A
3.21
4.41
2.96
Erp
*
6
Pdesign
kW
-
-
-
-
5.0
-
-
-
SEER
(W/W)
-
-
-
-
4.6
-
-
-
Annual consumption
kWh
-
-
-
-
380 
-
-
-
Class
-
-
-
-
B
-
-
-
Power factor
%
-
-
-
94 
94 
94 
-
-
Noise indoor
dB-A (H/M/L)
36/34/30
-
-
-
Power Level dB
58/56/52
-
-
-
Noise outdoor
dB-A  (H/L)
-
46/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
5.6
5.6
5.6
-
-
-
1.5
6.5
BTU/h
19100
19100
19100
-
-
-
5100
22200
Current
A
0.54
0.55
0.56
7.45
7.10
6.75
-
-
Input power
W
115
120
125
1.520k
1.515k
1.510k
-
-
TOTAL W
-
1.635k
1.635k
1.635k
290
1.860k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.43
3.43/B
3.43
5.17
3.49
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
3.8
-
-
-
Tbivalent
°C
-
-
-
-
-10 
-
-
-
SCOP
(W/W)
-
-
-
-
3.8
-
-
-
Annual consumption
kWh
-
-
-
-
1398 
-
-
-
elbu(-10°C)
kW
-
-
-
-
0.00
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
93 
93  
93  
-
-
Noise indoor
dB-A (H/M/L)
36/34/30
-
-
-
Power Level dB
58/56/52
-
-
-
Noise outdoor
dB-A (H/L)
-
48/-
-
-
Power Level dB
-
68/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A)  /  Max Input power(W)
0.76/165
0.79/180
0.80/190
12.0/2.460k
12.0/2.570k
12.0/2.680k
-
Starting current(A)/Comp output(W)
-
-
-
7.45/1.5k
7.10/1.5k
6.75/1.5k
-
Network Impedance(ΩMAX.)
-
-
Fan motor output (Indoor/Outdoor) W
85
60
-
Moisture removal volume
L/h(Pt/h)
2.8
(5.9)
-
-
External static pressure
Pa
25 (MAX80)
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
16.0/13.0/11.0 (565/459/388)
-
-
-
Heating
m³/min (ft³/min)
16.0/13.0/11.0 (565/459/388)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
38.0
(1342)
-
-
Heating
m³/min (ft³/min)
-
41.0
(1448)
-
-
Refrigerant type  /  amount g(oz)
-
R410A
1.40k
(49.4)
-
  Product dimension
Height mm(inch)
250 (9-27/32)
619 (24-3/8)
-
Width
mm(inch)
780 [+100] (30-45/64 [+3-15/16])
799 (31-29/64)
-
Depth
mm(inch)
650 (25-19/32)
299 (11-49/64)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
338 (13-5/16)
688
-
Width
mm(inch)
991 (39-1/64)
931
-
Depth
mm(inch)
761 (29-61/64)
422
-
Weight
(NET)
kg(lb)
29 (64)
39 (86)
-
(GROSS)  kg(lb)
34 (75)
44 (97)
-
Panel (NET)  kg(lb)
-
-
-
Layers limit  (actually)
5 (6) 
5 (6) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
Max Working Pressure HP/LP Mpa (bar)
4.15/2.70 (41.5/27.0)
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
3 ~ 40m
(9.8 ~ 131.2)
-
Indoor unit & Outdoor unit height difference  m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
20g/m 
(0.215)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
*1 : In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 :  If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall  
 be used.
*3 : Network Impedance shall be applicable for EUROPE and CHINA models. 
*4 : The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 : EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 :  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data   
 indicates in an attached sheet.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   6
19/09/26   17:01:43
1-1-5-7
1
1
Simultaneous (Twin) -Type
1-1.  Unit Specifications
PE1
5. Ducted Type S-50PN1E5B×2 / U-100PE1E5A
INDOOR
MODEL
S-50PN1E5B×2
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-100PE1E5A  
-
Branch pipe
MODEL
-
Performance test condition
ISO13253  /  EN14511  /  EN14825  /  EN12102
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
10.0
10.0
10.0
-
-
-
3.3
12.5
BTU/h
34100
34100
34100
-
-
-
11300
42700
Current
A
0.54×2
0.55×2
0.56×2
11.5
11.0
10.8
-
-
Input power
W
115×2
120×2
125×2
2.440k
2.430k
2.420k
-
-
TOTAL W
-
2.670k
2.670k
2.670k
790
4.040k
Annual consumption
TOTAL kWh *
4
-
-
1335
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.75
3.75/A
3.75
4.18
3.09
Erp
*
6
Pdesign
kW
-
-
-
-
10.0
-
-
-
SEER
(W/W)
-
-
-
-
5.8
-
-
-
Annual consumption
kWh
-
-
-
-
595 
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
97 
96 
94 
-
-
Noise indoor
dB-A (H/M/L)
36/34/30
-
-
-
Power Level dB
58/56/52
-
-
-
Noise outdoor
dB-A  (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
H
E
A
T
I
N
G
Capacity
kW
11.2
11.2
11.2
-
-
-
4.1
14.0
BTU/h
38200
38200
38200
-
-
-
14000
47800
Current
A
0.54×2
0.55×2
0.56×2
12.7
12.5
12.0
-
-
Input power
W
115×2
120×2
125×2
2.720k
2.710k
2.700k
-
-
TOTAL W
-
2.950k
2.950k
2.950k
940
4.240k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.80
3.80/A
3.80
4.36
3.30
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
10.0
-
-
-
Tbivalent
°C
-
-
-
-
-10 
-
-
-
SCOP
(W/W)
-
-
-
-
3.9
-
-
-
Annual consumption
kWh
-
-
-
-
3588 
-
-
-
elbu(-10°C)
kW
-
-
-
-
0.00
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
97 
95  
94 
-
-
Noise indoor
dB-A (H/M/L)
36/34/30
-
-
-
Power Level dB
58/56/52
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A)  /  Max Input power(W)
0.76×2/165×2 0.79×2/180×2 0.80×2/190×2 25.0/5.350k
25.0/5.550k
25.0/5.750k
-
Starting current(A)/Comp output(W)
-
-
-
12.7/3.0k
12.5/3.0k
12.0/3.0k
-
Network Impedance(ΩMAX.)
-
-
Fan motor output (Indoor/Outdoor) W
85×2
90×2
-
Moisture removal volume
L/h(Pt/h)
6.0
(3.0×2)
(12.6)
-
-
External static pressure
Pa
25 (MAX80)
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
16.0×2/13.0×2/11.0×2 (565)×2/(459)×2/(388)×2
-
-
-
Heating
m³/min (ft³/min)
16.0×2/13.0×2/11.0×2 (565)×2/(459)×2/(388)×2
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
110.0
(3885)
-
-
Heating
m³/min (ft³/min)
-
95.0
(3355)
-
-
Refrigerant type  /  amount g(oz)
-
R410A
3.40k
(119.9)
-
  Product dimension
Height mm(inch)
250 (9-27/32)
1416 (55-3/4)
-
Width
mm(inch)
780 [+100] (30-45/64 [+3-15/16])
940 (37-1/32)
-
Depth
mm(inch)
650 (25-19/32)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
338 (13-5/16)
1556 
-
Width
mm(inch)
991 (39-1/64)
1055 
-
Depth
mm(inch)
761 (29-61/64)
485 
-
Weight
(NET)
kg(lb)
29 (64)
98 (216)
-
(GROSS)  kg(lb)
34 (75)
108 (238)
-
Panel (NET)  kg(lb)
-
-
-
Layers limit  (actually)
5 (6) 
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
Max Working Pressure HP/LP Mpa (bar)
4.15/2.70 (41.5/27.0)
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference  m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
*1 : In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 :  If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall  
 be used.
*3 : Network Impedance shall be applicable for EUROPE and CHINA models. 
*4 : The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 : EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 :  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data   
 indicates in an attached sheet.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   7
19/09/26   17:01:43
1-1-5-8
1
1
Simultaneous (Triple) -Type
1-1.  Unit Specifications
PE1
5. Ducted Type S-50PN1E5B×3 / U-140PE1E5A
INDOOR
MODEL
S-50PN1E5B×3
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-140PE1E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253  /  EN14511  /  EN14825  /  EN12102
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
3.3
15.5 
BTU/h
47800
47800
47800
-
-
-
11300
52900
Current
A
0.54×3
0.55×3
0.56×3
20.0
19.6
19.0
-
-
Input power
W
115×3
120×3
125×3
4.305k
4.290k
4.275k
-
-
TOTAL W
-
4.650k
4.650k
4.650k
910
6.010k
Annual consumption
TOTAL kWh *
4
-
-
2325
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.01
3.01/B
3.01
3.63
2.58
Erp
*
6
Pdesign
kW
-
-
-
-
14.0
-
-
-
η 
s,c
%
-
-
-
-
241.8
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
98 
95 
94 
-
-
Noise indoor
dB-A (H/M/L)
36/34/30
-
-
-
Power Level dB
58/56/52
-
-
-
Noise outdoor
dB-A  (H/L)
-
54/-
-
-
Power Level dB
-
71/-
-
-
H
E
A
T
I
N
G
Capacity
kW
16.0
16.0
16.0
-
-
-
4.1 
18.0 
BTU/h
54600
54600
54600
-
-
-
14000
61400
Current
A
0.54×3
0.55×3
0.56×3
20.1
19.7
19.2
-
-
Input power
W
115×3
120×3
125×3
4.345k
4.330k
4.315k
-
-
TOTAL W
-
4.690k
4.690k
4.690k
1.110k
6.110k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.41
3.41/B
3.41
3.69
2.95
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
14.0 
-
-
-
Tbivalent
°C
-
-
-
-
-7 
-
-
-
η 
s,h
%
-
-
-
-
142.4
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
elbu(-10°C)
kW
-
-
-
-
2.74
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
98 
96 
94 
-
-
Noise indoor
dB-A (H/M/L)
36/34/30
-
-
-
Power Level dB
58/56/52
-
-
-
Noise outdoor
dB-A (H/L)
-
55/-
-
-
Power Level dB
-
71/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A)  /  Max Input power(W)
0.76×3/165×3 0.79×3/180×3 0.80×3/190×3 30.0/6.450k
30.0/6.650k
30.0/6.850k
-
Starting current(A)/Comp output(W)
-
-
-
20.1/3.0k
19.7/3.0k
19.2/3.0k
-
Network Impedance(ΩMAX.)
-
-
Fan motor output (Indoor/Outdoor) W
85×3
90×2
-
Moisture removal volume
L/h(Pt/h)
9.0
 (3.0×3)
(18.9)
-
-
External static pressure
Pa
25 (MAX80)
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
16.0×3/13.0×3/11.0×3 (565)×3/(459)×3/(388)×3
-
-
-
Heating
m³/min (ft³/min)
16.0×3/13.0×3/11.0×3 (565)×3/(459)×3/(388)×3
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
135.0
(4767)
-
-
Heating
m³/min (ft³/min)
-
120.0
(4238)
-
-
Refrigerant type  /  amount g(oz)
-
R410A
3.40k
(119.9)
-
  Product dimension
Height mm(inch)
250 (9-27/32)
1416 (55-3/4)
-
Width
mm(inch)
780 [+100] (30-45/64 [+3-15/16])
940 (37-1/32)
-
Depth
mm(inch)
650 (25-19/32)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
338 (13-5/16)
1556 
-
Width
mm(inch)
991 (39-1/64)
1055 
-
Depth
mm(inch)
761 (29-61/64)
485 
-
Weight
(NET)
kg(lb)
29 (64)
98 (216)
-
(GROSS)  kg(lb)
34 (75)
108 (238)
-
Panel (NET)  kg(lb)
-
-
-
Layers limit  (actually)
5 (6) 
1 (2) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
Max Working Pressure HP/LP Mpa (bar)
4.15/2.70 (41.5/27.0)
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference  m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
*1 : In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 :  If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall  
 be used.
*3 : Network Impedance shall be applicable for EUROPE and CHINA models. 
*4 : The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 : EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 :  
η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   8
19/09/26   17:01:44
1-1-5-9
1
1
Single -Type
1-1.  Unit Specifications
PE2
5. Ducted Type S-60PN1E5B / U-60PE2E5A
INDOOR
MODEL
S-60PN1E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-60PE2E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253  /  EN14511  /  EN14825  /  EN12102
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
6.0
6.0
6.0
-
-
-
2.0
7.1
BTU/h
20500
20500
20500
-
-
-
6800
24200
Current
A
1.12
1.08
1.04
8.60
8.30
7.90
-
-
Input power
W
140
140
140
1.710k
1.710k
1.710k
-
-
TOTAL W
-
1.850k
1.850k
1.850k
400
2.550k
Annual consumption
TOTAL kWh *
4
-
-
925
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.24
3.24/A
3.24
5.00
2.78
Erp
*
6
Pdesign
kW
-
-
-
-
6.0
-
-
-
SEER
(W/W)
-
-
-
-
5.3
-
-
-
Annual consumption
kWh
-
-
-
-
392 
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
90
90
90 
-
-
Noise indoor
dB-A (H/M/L)
38/36/31
-
-
-
Power Level dB
60/58/53
-
-
-
Noise outdoor
dB-A  (H/L)
-
46/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
7.0
7.0
7.0
-
-
-
1.8
8.0
BTU/h
23900
23900
23900
-
-
-
6100
27300
Current
A
1.12
1.08
1.04
8.70
8.35
8.00
-
-
Input power
W
140
140
140
1.745k
1.745k
1.745k
-
-
TOTAL W
-
1.885k
1.885k
1.885k
350
2.200k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.71
3.71/A
3.71
5.14
3.64
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
5.6
-
-
-
Tbivalent
°C
-
-
-
-
-9
-
-
-
SCOP
(W/W)
-
-
-
-
3.8
-
-
-
Annual consumption
kWh
-
-
-
-
2063 
-
-
-
elbu(-10°C)
kW
-
-
-
-
0.16
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
91 
91   
91   
-
-
Noise indoor
dB-A (H/M/L)
38/36/31
-
-
-
Power Level dB
60/58/53
-
-
-
Noise outdoor
dB-A (H/L)
-
49/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A)  /  Max Input power(W)
1.28/160
1.24/160
1.20/160
16.5/3.27k
16.5/3.42k
16.5/3.57k
-
Starting current(A)/Comp output(W)
-
-
-
8.70/1.7k
8.35/1.7k
8.00/1.7k
-
Network Impedance(ΩMAX.)
-
-
Fan motor output (Indoor/Outdoor) W
120
60
-
Moisture removal volume
L/h(Pt/h)
3.4
(7.1)
-
-
External static pressure
Pa
25 (MIN10 - MAX80)
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
22.0/20.0/16.0 (777/706/565)
-
-
-
Heating
m³/min (ft³/min)
22.0/20.0/16.0 (777/706/565)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
38.0
(1342)
-
-
Heating
m³/min (ft³/min)
-
41.0
(1448)
-
-
Refrigerant type  /  amount g(oz)
-
R410A
1.95k
(68.8)
-
  Product dimension
Height mm(inch)
250 (9-27/32)
619 (24-3/8)
-
Width
mm(inch)
1000 [+100] (39-3/8 [+3-15/16])
799 (31-29/64)
-
Depth
mm(inch)
650 (25-19/32)
299 (11-49/64)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
338 (13-5/16)
688
-
Width
mm(inch)
1211 (47-43/64)
931 
-
Depth
mm(inch)
761 (29-61/64)
422
-
Weight
(NET)
kg(lb)
32 (71)
40 (88)
-
(GROSS)  kg(lb)
38 (84)
45 (99)
-
Panel (NET)  kg(lb)
-
-
-
Layers limit  (actually)
5 (6) 
5 (6) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
Max Working Pressure HP/LP Mpa (bar)
4.15/2.70 (41.5/27.0)
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
3 ~ 40m
(9.8 ~ 131.2)
-
Indoor unit & Outdoor unit height difference  m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
40g/m 
(0.430)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
*1 : In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 :  If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall  
 be used.
*3 : Network Impedance shall be applicable for EUROPE and CHINA models. 
*4 : The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 : EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 :  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data   
 indicates in an attached sheet.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   9
19/09/26   17:01:44
Page of 127
Display

Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ▷ Download