DOWNLOAD Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ↓ Size: 129.09 MB | Pages: 127 in PDF or view online for FREE

Model
U-50PE2E5A U-100PE1E8A U-100PEY1E8 U-125PE1E8A U-125PEY1E8 U-140PE1E8A U-140PEY1E8 S-100PU2E5B S-125PU2E5B S-140PU2E5B S-71PU2E5B S-100PF1E5B S-125PF1E5B S-140PF1E5B S-71PF1E5B
Pages
127
Size
129.09 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
u-50pe2e5a-u-100pe1e8a-u-100pey1e8-u-125pe1e8a-u-1.pdf
Date

Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ▷ View online

1-1-3-4
1
1
Simultaneous (Double-Twin) -Type
1-1.  Unit Specifications
PE1
3. Wall Mounted Type S-36PK2E5B×4 / U-125PE1E5A
INDOOR
MODEL
S-36PK2E5B×4
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-125PE1E5A
-
Branch pipe
MODEL
CZ-P155BK1×3
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
12.5 
12.5 
12.5 
-
-
-
3.3 
14.0 
BTU/h
42700
42700
42700
-
-
-
11300
47800
Current
A
0.35×4
0.34×4
0.33×4
17.3 
16.7 
16.2 
-
-
Input power
W
20×4
20×4
20×4
3.685k
3.685k
3.685k
-
-
TOTAL W
-
3.765k
3.765k
3.765k
840
4.600k
Annual consumption
TOTAL kWh *
4
-
-
-
-
1882.5
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.32 
3.32/A
3.32 
3.93
3.04
Erp
*
6
Pdesign
kW
-
-
-
-
12.5 
-
-
-
η 
s,c
%
-
-
-
-
241.1 
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
35/31/27
-
-
-
Power Level dB
51/47/43
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
H
E
A
T
I
N
G
Capacity
kW
14.0 
14.0 
14.0 
-
-
-
4.1 
16.0 
BTU/h
47800
47800
47800
-
-
-
14000
54600
Current
A
0.36×4
0.35×4
0.34×4
17.3 
16.7 
16.2 
-
-
Input power
W
20×4
20×4
20×4
3.685k
3.685k
3.685k
-
-
TOTAL W
-
3.765k
3.765k
3.765k
900
5.200k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.72 
3.72/A
3.72 
4.56
3.08
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
12.5 
-
-
-
Tbivalent
°C
-
-
-
-
-9 
-
-
-
η 
s,h
%
-
-
-
-
140.5 
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
35/31/27
-
-
-
Power Level dB
51/47/43
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.36/20×4
0.35/20×4
0.34/20×4
28.0 / 6.00k 28.0 / 6.20k 28.0 / 6.40k
-
Starting current(A) / Comp output(W)
-
-
-
17.3 / 3.0k
16.7 / 3.0k
16.2 / 3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
54
90× 2
-
Moisture removal volume
L/h(Pt/h)
3.6
(0.9×4)
(7.6)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
13.0×4/11.0×4/9.0×4 (459)×4/(388)×4/(318)×4
-
-
-
Heating
m³/min (ft³/min)
13.0×4/11.0×4/9.0×4 (459)×4/(388)×4/(318)×4
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
130.0 (4591)
-
-
Heating
m³/min (ft³/min)
-
110.0 (3885)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
302 
(11-29/32)
1416 (55-3/4)
-
Width
mm(inch)
1120 
(44-3/32)
940 (37-1/32)
-
Depth
mm(inch)
236 
(9-9/32)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
-
-
Packing dimension
Height mm(inch)
282 
(11-1/8)
1556 
-
Width
mm(inch)
1190 
(46-7/8)
1055 
-
Depth
mm(inch)
378 
(14-29/32)
485 
-
Weight
(NET)
kg(lb)
13 
(29)
98
(216)
-
(GROSS)  kg(lb)
16 
(36)
108
(238)
-
Panel (NET)  kg(lb)
-
-
-
Layers limit (actually)
11 (12)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m (16.4 ~246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas  m (ft)
20m (65.6)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  
η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   4
19/09/26   17:01:25
1-1-3-5
1
1
Simultaneous (Triple) -Type
1-1.  Unit Specifications
PE1
3. Wall Mounted Type S-45PK2E5B×3 / U-125PE1E5A
INDOOR
MODEL
S-45PK2E5B×3
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-125PE1E5A
-
Branch pipe
MODEL
CZ-P3HPC2
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
12.5 
12.5 
12.5 
-
-
-
3.3 
14.0 
BTU/h
42700
42700
42700
-
-
-
11300
47800
Current
A
0.38×3
0.37×3
0.36×3
17.2 
16.7 
16.1 
-
-
Input power
W
30×3
30×3
30×3
3.675k
3.675k
3.675k
-
-
TOTAL W
-
3.765k
3.765k
3.765k
840
4.600k
Annual consumption
TOTAL kWh *
4
-
-
-
-
1882.5
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.32 
3.32/A
3.32 
3.93
3.04
Erp
*
6
Pdesign
kW
-
-
-
-
12.5 
-
-
-
η 
s,c
%
-
-
-
-
241.1 
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
38/34/30
-
-
-
Power Level dB
54/50/46
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
H
E
A
T
I
N
G
Capacity
kW
14.0 
14.0 
14.0 
-
-
-
4.1 
16.0 
BTU/h
47800
47800
47800
-
-
-
14000
54600
Current
A
0.38×3
0.37×3
0.36×3
17.2 
16.7 
16.1 
-
-
Input power
W
30×3
30×3
30×3
3.675k
3.675k
3.675k
-
-
TOTAL W
-
3.765k
3.765k
3.765k
900
5.200k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.72 
3.72 /A
3.72 
4.56
3.08
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
12.5 
-
-
-
Tbivalent
°C
-
-
-
-
-9 
-
-
-
η 
s,h
%
-
-
-
-
140.5 
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
38/34/30
-
-
-
Power Level dB
54/50/46
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.38/30×3
0.37/30×3
0.36/30×3
28.0 / 6.00k 28.0 / 6.20k 28.0 / 6.40k
-
Starting current(A) / Comp output(W)
-
-
-
17.2 / 3.0k
16.7 / 3.0k
16.1 / 3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
54
90× 2
-
Moisture removal volume
L/h(Pt/h)
4.5
(1.5×3)
(9.5)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
14.5×3/12.5×3/10.3×3 (512)×3/(441)×3/(364)×3
-
-
-
Heating
m³/min (ft³/min)
14.5×3/12.5×3/10.3×3 (512)×3/(441)×3/(364)×3
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
130.0 (4591)
-
-
Heating
m³/min (ft³/min)
-
110.0 (3885)
-
-
Refrigerant type / amount g(oz)
-
R410A  
3.40k
(119.9)
-
Product dimension
Height mm(inch)
302 
(11-29/32)
1416 (55-3/4)
-
Width
mm(inch)
1120 
(44-3/32)
940 (37-1/32)
-
Depth
mm(inch)
236 
(9-9/32)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
-
-
Packing dimension
Height mm(inch)
282 
(11-1/8)
1556 
-
Width
mm(inch)
1190 
(46-7/8)
1055 
-
Depth
mm(inch)
378 
(14-29/32)
485 
-
Weight
(NET)
kg(lb)
13 
(29)
98
(216)
-
(GROSS)  kg(lb)
16 
(36)
108
(238)
-
Panel (NET)  kg(lb)
-
-
-
Layers limit (actually)
11 (12)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m (16.4 ~246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas  m (ft)
20m (65.6)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  
η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   5
19/09/26   17:01:25
1-1-3-6
1
1
Single -Type
1-1.  Unit Specifications
PE2
3. Wall Mounted Type S-50PK2E5B / U-50PE2E5A
INDOOR
MODEL
S-50PK2E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-50PE2E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151 / EN14511 / EN12102/ EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
5.0 
5.0 
5.0 
-
-
-
1.5 
5.6 
BTU/h
17100
17100
17100
-
-
-
5100
19100
Current
A
0.40 
0.39 
0.38 
6.60 
6.30 
6.05 
-
-
Input power
W
35
1.365k
1.365k
1.365k
-
-
TOTAL W
-
1.400k
1.400k
1.400k
240
1.720k
Annual consumption
TOTAL kWh *
4
-
-
-
-
700
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.57 
3.57/A
3.57 
6.25
3.26
Erp
*
6
Pdesign
kW
-
-
-
-
5.0 
-
-
-
SEER
(W/W)
-
-
-
-
6.2 
-
-
-
Annual consumption
kWh
-
-
-
-
282 
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
94 
94 
94 
-
-
Noise indoor
dB-A (H/M/L) *
7
40/36/32
-
-
-
Power Level dB
56/52/48
-
-
-
Noise outdoor
dB-A (H/L)
-
46/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
5.6 
5.6 
5.6 
-
-
-
1.5 
6.5 
BTU/h
19100
19100
19100
-
-
-
5100
22200
Current
A
0.40
0.39
0.38
6.75 
6.45 
6.20 
-
-
Input power
W
35
1.385k
1.385k
1.385k
-
-
TOTAL W
-
1.420k
1.420k
1.420k
190
1.920k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.94 
3.94/A
3.94 
7.89
3.39
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
5.0 
-
-
-
Tbivalent
°C
-
-
-
-
-7 
-
-
-
SCOP
(W/W)
-
-
-
-
4.1 
-
-
-
Annual consumption
kWh
-
-
-
-
1707 
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
93 
93 
93 
-
-
Noise indoor
dB-A (H/M/L) *
7
40/36/32
-
-
-
Power Level dB
56/52/48
-
-
-
Noise outdoor
dB-A (H/L)
-
48/-
-
-
Power Level dB
-
68/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.40/35
0.39/35
0.38/35
12.0/2.46k
12.0/2.57k
12.0/2.68k
-
Starting current(A) / Comp output(W)
-
-
-
6.75/1.5k
6.45/1.5k
6.20/1.5k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
54
60
-
Moisture removal volume
L/h(Pt/h)
1.8
 
(3.8)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
16.0/13.5/11.0 (565)/(477)/(388)
-
-
-
Heating
m³/min (ft³/min)
16.0/13.5/11.0 (565)/(477)/(388)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
38.0 (1342)
-
-
Heating
m³/min (ft³/min)
-
41.0 (1448)
-
-
Refrigerant type / amount g(oz)
-
R410A  
1.40k
(49.4)
-
Product dimension
Height mm(inch)
302 
(11-29/32)
619 
(24-3/8)
-
Width
mm(inch)
1120 
(44-3/32)
799 
(31-29/64)
-
Depth mm(inch)
236 
(9-9/32)
299 
(11-49/64)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
282 
(11-1/8)
688 
-
Width
mm(inch)
1190 
(46-7/8)
931 
-
Depth
mm(inch)
378 
(14-29/32)
422 
-
Weight
(NET)
kg(lb)
13 
(29)
39
(86)
-
(GROSS)  kg(lb)
16 
(36)
44
(97)
-
Panel (NET)  kg(lb)
-
-
-
Layers limit (actually)
11(12)
5(6)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4)   (Gas)Ø12.7(1/2)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
3 ~ 40m (9.8 ~ 131.2)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
20g/m (0.215)
-
Pipe length for additional gas  m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data  
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   6
19/09/26   17:01:26
1-1-3-7
1
1
Simultaneous (Twin) -Type
1-1.  Unit Specifications
PE1
3. Wall Mounted Type S-50PK2E5B×2 / U-100PE1E5A
INDOOR
MODEL
S-50PK2E5B×2
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-100PE1E5A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO5151 / EN14511 / EN12102/ EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
10.0 
10.0 
10.0 
-
-
-
3.3 
12.5 
BTU/h
34100
34100
34100
-
-
-
11300
42700
Current
A
0.40×2
0.39×2
0.38×2
11.9 
11.4 
10.9 
-
-
Input power
W
35×2
35×2
35×2
2.510k
2.510k
2.510k
-
-
TOTAL W
-
2.580k
2.580k
2.580k
840
3.700k
Annual consumption
TOTAL kWh *
4
-
-
-
-
1290
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.88 
3.88/A
3.88 
3.93
3.38
Erp
*
6
Pdesign
kW
-
-
-
-
10.0 
-
-
-
SEER
(W/W)
-
-
-
-
6.2 
-
-
-
Annual consumption
kWh
-
-
-
-
564 
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
96 
96 
96 
-
-
Noise indoor
dB-A (H/M/L) *
7
40/36/32
-
-
-
Power Level dB
56/52/48
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
H
E
A
T
I
N
G
Capacity
kW
11.2 
11.2 
11.2 
-
-
-
4.1 
14.0 
BTU/h
38200
38200
38200
-
-
-
14000
47800
Current
A
0.40×2
0.39×2
0.38×2
13.0 
12.5 
11.9 
-
-
Input power
W
35×2
35×2
35×2
2.690k
2.690k
2.690k
-
-
TOTAL W
-
2.760k
2.760k
2.760k
900
4.400k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.06 
4.06/A
4.06 
4.56
3.18
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
10.0 
-
-
-
Tbivalent
°C
-
-
-
-
-10 
-
-
-
SCOP
(W/W)
-
-
-
-
4.0 
-
-
-
Annual consumption
kWh
-
-
-
-
3500 
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
94 
94 
94 
-
-
Noise indoor
dB-A (H/M/L) *
7
40/36/32
-
-
-
Power Level dB
56/52/48
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.40/35×2
0.39/35×2
0.38/35×2
25.0/5.34k
25.0/5.52k
25.0/5.70k
-
Starting current(A) / Comp output(W)
-
-
-
13.0/3.0k
12.5/3.0k
11.9/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
54
90×2
-
Moisture removal volume
L/h(Pt/h)
3.6
(1.8×2) 
(7.6)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
16.0×2/13.5×2/11.0×2 (565×2)/(477×2)/(388×2)
-
-
-
Heating
m³/min (ft³/min)
16.0×2/13.5×2/11.0×2 (565×2)/(477×2)/(388×2)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
110.0 (3885)
-
-
Heating
m³/min (ft³/min)
-
95.0 (3355)
-
-
Refrigerant type / amount g(oz)
-
R410A  
3.40k
(119.9)
-
Product dimension
Height mm(inch)
302 
(11-29/32)
1416 
(55-3/4)
-
Width
mm(inch)
1120 
(44-3/32)
940 
(37-1/32)
-
Depth mm(inch)
236 
(9-9/32)
340 
(13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
282 
(11-1/8)
1556 
-
Width
mm(inch)
1190 
(46-7/8)
1055 
-
Depth
mm(inch)
378 
(14-29/32)
485 
-
Weight
(NET)
kg(lb)
13 
(29)
98
(216)
-
(GROSS)  kg(lb)
16 
(36)
108
(238)
-
Panel (NET)  kg(lb)
-
-
-
Layers limit (actually)
11(12)
1(2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4)   (Gas)Ø12.7(1/2)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m (16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas  m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data  
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   7
19/09/26   17:01:26
Page of 127
Display

Click on the first or last page to see other U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B service manuals if exist.