Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ▷ View online
1-1-3-8
1
1
Simultaneous (Triple) -Type
1-1. Unit Specifications
PE1
3. Wall Mounted Type S-50PK2E5B×3 / U-140PE1E5A
INDOOR
MODEL
S-50PK2E5B×3
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-140PE1E5A
-
Branch pipe
MODEL
CZ-P3HPC2
Performance test condition
ISO5151 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
3.3
15.5
BTU/h
47800
47800
47800
-
-
-
11300
52900
Current
A
0.40×3
0.39×3
0.38×3
21.3
20.6
20.0
-
-
Input power
W
35×3
35×3
35×3
4.545k
4.545k
4.545k
-
-
TOTAL W
-
4.650k
4.650k
4.650k
840
6.000k
Annual consumption
TOTAL kWh *
4
-
-
-
-
2325
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.01
3.01/B
3.01
3.93
2.58
Erp
*
6
Pdesign
kW
-
-
-
-
14.0
-
-
-
η
s,c
%
-
-
-
-
231.7
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L) *
7
40/36/32
-
-
-
Power Level dB
56/52/48
-
-
-
Noise outdoor
dB-A (H/L)
-
54/-
-
-
Power Level dB
-
71/-
-
-
H
E
A
T
I
N
G
Capacity
kW
16.0
16.0
16.0
-
-
-
4.1
18.0
BTU/h
54600
54600
54600
-
-
-
14000
61400
Current
A
0.40×3
0.39×3
0.38×3
21.9
21.2
20.5
-
-
Input power
W
35×3
35×3
35×3
4.665k
4.665k
4.665k
-
-
TOTAL W
-
4.770k
4.770k
4.770k
900
5.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.35
3.35/C
3.35
4.56
3.05
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
14.0
-
-
-
Tbivalent
°C
-
-
-
-
-7
-
-
-
η
s,h
%
-
-
-
-
138.4
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L) *
7
40/36/32
-
-
-
Power Level dB
56/52/48
-
-
-
Noise outdoor
dB-A (H/L)
-
55/-
-
-
Power Level dB
-
71/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.40/35×3
0.39/35×3
0.38/35×3
30.0/6.45k
30.0/6.65k
30.0/6.85k
-
Starting current(A) / Comp output(W)
-
-
-
21.9/3.0k
21.2/3.0k
20.5/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
54
90× 2
-
Moisture removal volume
L/h(Pt/h)
5.4
(1.8×3)
(11.3)
-
-
External static pressure
Pa
-
-
-
Indoor
Air flow *
7
Cooling
m³/min (ft³/min)
16.0×3/13.5×3/11.0×3 (565)×3/(477)×3/(388)×3
-
-
-
Heating
m³/min (ft³/min)
16.0×3/13.5×3/11.0×3 (565)×3/(477)×3/(388)×3
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
135.0 (4767)
-
-
Heating
m³/min (ft³/min)
-
120.0 (4238)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
302
(11-29/32)
1416 (55-3/4)
-
Width
mm(inch)
1120
(44-3/32)
940 (37-1/32)
-
Depth mm(inch)
236
(9-9/32)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
282
(11-1/8)
1556
-
Width
mm(inch)
1190
(46-7/8)
1055
-
Depth
mm(inch)
378
(14-29/32)
485
-
Weight
(NET)
kg(lb)
13
(29)
98
(216)
-
(GROSS) kg(lb)
16
(36)
108
(238)
-
Panel (NET) kg(lb)
-
-
-
Layers limit (actually)
11 (12)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 75m (16.4 ~246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas m (ft)
20m (65.6)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6
η
s,c
and
η
s,h
classification is at 230V(400V) only in accordance with EN-14825. For heating,
η
s,h
indicates the value of only Average heating season.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 8
19/09/26 17:01:26
1-1-3-9
1
1
Single -Type
1-1. Unit Specifications
PE2
3. Wall Mounted Type S-60PK2E5B / U-60PE2E5A
INDOOR
MODEL
S-60PK2E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-60PE2E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151 / EN14511 / EN12102/ EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
6.1
6.1
6.1
-
-
-
2.0
7.1
BTU/h
20800
20800
20800
-
-
-
6800
24200
Current
A
0.60
0.59
0.58
8.45
8.05
7.75
-
-
Input power
W
60
1.670k
1.670k
1.670k
-
-
TOTAL W
-
1.730k
1.730k
1.730k
300
2.350k
Annual consumption
TOTAL kWh *
4
-
-
-
-
865
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.53
3.53/A
3.53
6.67
3.02
Erp
*
6
Pdesign
kW
-
-
-
-
6.1
-
-
-
SEER
(W/W)
-
-
-
-
6.7
-
-
-
Annual consumption
kWh
-
-
-
-
319
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
90
90
90
-
-
Noise indoor
dB-A (H/M/L) *
7
47/44/40
-
-
-
Power Level dB
63/60/56
-
-
-
Noise outdoor
dB-A (H/L)
-
46/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
7.0
7.0
7.0
-
-
-
1.8
8.0
BTU/h
23900
23900
23900
-
-
-
6100
27300
Current
A
0.60
0.59
0.58
8.10
7.75
7.40
-
-
Input power
W
60
1.600k
1.600k
1.600k
-
-
TOTAL W
-
1.660k
1.660k
1.660k
200
2.050k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.22
4.22/A
4.22
9.00
3.90
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
6.0
-
-
-
Tbivalent
°C
-
-
-
-
-8
-
-
-
SCOP
(W/W)
-
-
-
-
4.2
-
-
-
Annual consumption
kWh
-
-
-
-
2000
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
90
90
90
-
-
Noise indoor
dB-A (H/M/L) *
7
47/44/40
-
-
-
Power Level dB
63/60/56
-
-
-
Noise outdoor
dB-A (H/L)
-
49/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.60/60
0.59/60
0.58/60
16.5/3.27k
16.5/3.42k
16.5/3.57k
-
Starting current(A) / Comp output(W)
-
-
-
8.45/1.7k
8.05/1.7k
7.75/1.7k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
54
60
-
Moisture removal volume
L/h(Pt/h)
2.0
(4.2)
-
-
External static pressure
Pa
-
-
-
Indoor
Air flow *
7
Cooling
m³/min (ft³/min)
20.0/17.5/14.5 (706)/(618)/(512)
-
-
-
Heating
m³/min (ft³/min)
20.0/17.5/14.5 (706)/(618)/(512)
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
38.0 (1342)
-
-
Heating
m³/min (ft³/min)
-
41.0 (1448)
-
-
Refrigerant type / amount g(oz)
-
R410A
1.95k
(68.8)
-
Product dimension
Height mm(inch)
302
(11-29/32)
619
(24-3/8)
-
Width
mm(inch)
1120
(44-3/32)
799
(31-29/64)
-
Depth mm(inch)
236
(9-9/32)
299
(11-49/64)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
282
(11-1/8)
688
-
Width
mm(inch)
1190
(46-7/8)
931
-
Depth
mm(inch)
378
(14-29/32)
422
-
Weight
(NET)
kg(lb)
14
(31)
40
(88)
-
(GROSS) kg(lb)
17
(38)
45
(99)
-
Panel (NET) kg(lb)
-
-
-
Layers limit (actually)
11(12)
5(6)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
3 ~ 40m (9.8 ~ 131.2)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
40g/m (0.430)
-
Pipe length for additional gas m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 9
19/09/26 17:01:27
1-1-3-10
1
1
Simultaneous (Twin) -Type
1-1. Unit Specifications
PE1
3. Wall Mounted Type S-60PK2E5B×2 / U-125PE1E5A
INDOOR
MODEL
S-60PK2E5B×2
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-125PE1E5A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO5151 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
12.5
12.5
12.5
-
-
-
3.3
14.0
BTU/h
42700
42700
42700
-
-
-
11300
47800
Current
A
0.60×2
0.59×2
0.58×2
17.1
16.5
16.0
-
-
Input power
W
60×2
60×2
60×2
3.645k
3.645k
3.645k
-
-
TOTAL W
-
3.765k
3.765k
3.765k
840
4.600k
Annual consumption
TOTAL kWh *
4
-
-
-
-
1882.5
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.32
3.32/A
3.32
3.93
3.04
Erp
*
6
Pdesign
kW
-
-
-
-
12.5
-
-
-
η
s,c
%
-
-
-
-
241.1
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L) *
7
47/44/40
-
-
-
Power Level dB
63/60/56
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
H
E
A
T
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
4.1
16.0
BTU/h
47800
47800
47800
-
-
-
14000
54600
Current
A
0.60×2
0.59×2
0.58×2
17.1
16.5
16.0
-
-
Input power
W
60×2
60×2
60×2
3.645k
3.645k
3.645k
-
-
TOTAL W
-
3.765k
3.765k
3.765k
900
5.200k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.72
3.72/A
3.72
4.56
3.08
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
12.5
-
-
-
Tbivalent
°C
-
-
-
-
-9
-
-
-
η
s,h
%
-
-
-
-
140.5
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97
96
95
-
-
Noise indoor
dB-A (H/M/L) *
7
47/44/40
-
-
-
Power Level dB
63/60/56
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.60/60×2
0.59/60×2
0.58/60×2
28.0/6.00k
28.0/6.20k
28.0/6.40k
-
Starting current(A) / Comp output(W)
-
-
-
17.1/3.0k
16.5/3.0k
16.0/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
54
90× 2
-
Moisture removal volume
L/h(Pt/h)
4.0
(2.0×2)
(8.4)
-
-
External static pressure
Pa
-
-
-
Indoor
Air flow *
7
Cooling
m³/min (ft³/min)
20.0×2/17.5×2/14.5×2 (706)×2/(618)×2/(512)×2
-
-
-
Heating
m³/min (ft³/min)
20.0×2/17.5×2/14.5×2 (706)×2/(618)×2/(512)×2
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
130.0 (4591)
-
-
Heating
m³/min (ft³/min)
-
110.0 (3885)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
302
(11-29/32)
1416 (55-3/4)
-
Width
mm(inch)
1120
(44-3/32)
940 (37-1/32)
-
Depth mm(inch)
236
(9-9/32)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
282
(11-1/8)
1556
-
Width
mm(inch)
1190
(46-7/8)
1055
-
Depth
mm(inch)
378
(14-29/32)
485
-
Weight
(NET)
kg(lb)
14
(31)
98
(216)
-
(GROSS) kg(lb)
17
(38)
108
(238)
-
Panel (NET) kg(lb)
-
-
-
Layers limit (actually)
11 (12)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 75m (16.4 ~246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6
η
s,c
and
η
s,h
classification is at 230V(400V) only in accordance with EN-14825. For heating,
η
s,h
indicates the value of only Average heating season.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 10
19/09/26 17:01:27
1-1-3-11
1
1
Single -Type
1-1. Unit Specifications
PE1
3. Wall Mounted Type S-71PK2E5B / U-71PE1E5A
INDOOR
MODEL
S-71PK2E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-71PE1E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151 / EN14511 / EN12102/ EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
7.1
7.1
7.1
-
-
-
2.5
8.0
BTU/h
24200
24200
24200
-
-
-
8500
27300
Current
A
0.60
0.59
0.58
9.70
9.40
9.10
-
-
Input power
W
60
2.030k
2.030k
2.030k
-
-
TOTAL W
-
2.090k
2.090k
2.090k
450
2.650k
Annual consumption
TOTAL kWh *
4
-
-
-
-
1045
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.40
3.40/A
3.40
5.56
3.02
Erp
*
6
Pdesign
kW
-
-
-
-
7.1
-
-
-
SEER
(W/W)
-
-
-
-
6.7
-
-
-
Annual consumption
kWh
-
-
-
-
371
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
95
94
93
-
-
Noise indoor
dB-A (H/M/L) *
7
47/44/40
-
-
-
Power Level dB
63/60/56
-
-
-
Noise outdoor
dB-A (H/L)
-
48/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
8.0
8.0
8.0
-
-
-
2.0
9.0
BTU/h
27300
27300
27300
-
-
-
6800
30700
Current
A
0.60
0.59
0.58
9.20
8.90
8.60
-
-
Input power
W
60
1.940k
1.940k
1.940k
-
-
TOTAL W
-
2.000k
2.000k
2.000k
400
2.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.00
4.00/A
4.00
5.00
3.10
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
7.1
-
-
-
Tbivalent
°C
-
-
-
-
-9
-
-
-
SCOP
(W/W)
-
-
-
-
4.1
-
-
-
Annual consumption
kWh
-
-
-
-
2424
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
96
95
94
-
-
Noise indoor
dB-A (H/M/L) *
7
47/44/40
-
-
-
Power Level dB
63/60/56
-
-
-
Noise outdoor
dB-A (H/L)
-
50/-
-
-
Power Level dB
-
67/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.60/60
0.59/60
0.58/60
18.0/3.80k
18.0/3.93k
18.0/4.06k
-
Starting current(A) / Comp output(W)
-
-
-
9.70/2.0k
9.40/2.0k
9.10/2.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
54
90
-
Moisture removal volume
L/h(Pt/h)
3.0
(6.3)
-
-
External static pressure
Pa
-
-
-
Indoor
Air flow *
7
Cooling
m³/min (ft³/min)
20.0/17.5/14.5 (706)/(618)/(512)
-
-
-
Heating
m³/min (ft³/min)
20.0/17.5/14.5 (706)/(618)/(512)
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
60.0 (2119)
-
-
Heating
m³/min (ft³/min)
-
60.0 (2119)
-
-
Refrigerant type / amount g(oz)
-
R410A
2.35k
(82.9)
-
Product dimension
Height mm(inch)
302
(11-29/32)
996
(39-7/32)
-
Width
mm(inch)
1120
(44-3/32)
940
(37-1/32)
-
Depth mm(inch)
236
(9-9/32)
340
(13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
282
(11-1/8)
1136
-
Width
mm(inch)
1190
(46-7/8)
1055
-
Depth
mm(inch)
378
(14-29/32)
485
-
Weight
(NET)
kg(lb)
14
(31)
69
(153)
-
(GROSS) kg(lb)
17
(38)
77
(170)
-
Panel (NET) kg(lb)
-
-
-
Layers limit (actually)
11(12)
2(3)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 50m (16.4 ~ 164.0)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 11
19/09/26 17:01:27
Click on the first or last page to see other U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B service manuals if exist.