DOWNLOAD Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ↓ Size: 129.09 MB | Pages: 127 in PDF or view online for FREE

Model
U-50PE2E5A U-100PE1E8A U-100PEY1E8 U-125PE1E8A U-125PEY1E8 U-140PE1E8A U-140PEY1E8 S-100PU2E5B S-125PU2E5B S-140PU2E5B S-71PU2E5B S-100PF1E5B S-125PF1E5B S-140PF1E5B S-71PF1E5B
Pages
127
Size
129.09 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
u-50pe2e5a-u-100pe1e8a-u-100pey1e8-u-125pe1e8a-u-1.pdf
Date

Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ▷ View online

1-1-4-13
1
1
Single -Type
1-1.  Unit Specifications
PE1
4. Low Silhouette Ducted Type S-100PF1E5B / U-100PE1E5A
INDOOR
MODEL
S-100PF1E5B
-
-
OUTDOOR
MODEL
-
U-100PE1E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253  /  EN14511  /  EN14825  /   EN12102
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
10.0
10.0
10.0
-
-
-
3.3
12.5
BTU/h
34100
34100
34100
-
-
-
11300
42700
Current
A
1.35
1.30
1.27
11.0
10.6
10.3
-
-
Input power
W
195
195
195
2.245k
2.245k
2.245k
-
-
TOTAL W
-
2.440k
2.440k
2.440k
840
3.700k
Annual consumption
TOTAL kWh *
4
-
-
1220
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.10
4.10 / A
4.10
3.93
3.38
Erp
*
6
Pdesign
kW
-
-
-
-
10.0
-
-
-
SEER
(W/W)
-
-
-
-
5.8
-
-
-
Annual consumption
kWh
-
-
-
-
603
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
93
92
91
-
-
Noise indoor
dB-A (H/M/L)
38/34/31
-
-
-
Power Level dB
60/56/53
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
H
E
A
T
I
N
G
Capacity
kW
11.2
11.2
11.2
-
-
-
4.1
14.0
BTU/h
38200
38200
38200
-
-
-
14000
47800
Current
A
1.37
1.34
1.29
11.6
11.2
10.7
-
-
Input power
W
200
200
200
2.400k
2.400k
2.400k
-
-
TOTAL W
-
2.600k
2.600k
2.600k
900
4.400k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.31
4.31 / A
4.31
4.56
3.18
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
10.0
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
3.8
-
-
-
Annual consumption
kWh
-
-
-
-
3684
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
94
94
93
-
-
Noise indoor
dB-A (H/M/L)
38/34/31
-
-
-
Power Level dB
60/56/53
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
1.80/265
1.75/265
1.70/265
25.0/5.350k 25.0/5.550k 25.0/5.750k
-
Starting current(A) / Comp output(W)
-
-
-
11.6/3.0k
11.2/3.0k
10.7/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
200
90×2
-
Moisture removal volume
L/h(Pt/h)
6.0
(12.6)
-
-
External static pressure
Pa
100 (MIN10 - MAX150)
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
32.0/26.0/21.0 (1130)/(918)/(742)
-
-
-
Heating
m³/min (ft³/min)
32.0/26.0/21.0 (1130)/(918)/(742)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
110.0
(3885)
-
-
Heating
m³/min (ft³/min)
-
95.0
(3355)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
290  (11-13/32)
1416  (55-3/4)
-
Width
mm(inch)
1400  (55-1/8)
940  (37-1/32)
-
Depth
mm(inch)
700  (27-9/16)
340  (13-13/32)
-
Packing dimension
Height mm(inch)
355
1556
-
Width
mm(inch)
1614
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
45   (99)
98   (216)
-
(GROSS)  kg(lb)
54   (119)
108   (238)
-
Layers limit (actually)
9 (10) 
1 (2) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, 
Other fiche data indicates in an attached sheet.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   13
19/09/26   17:01:36
1-1-4-14
1
1
Single -Type
1-1.  Unit Specifications
PE1
4. Low Silhouette Ducted Type S-125PF1E5B / U-125PE1E5A
INDOOR
MODEL
S-125PF1E5B
-
-
OUTDOOR
MODEL
-
U-125PE1E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
12.5
12.5
12.5
-
-
-
3.3
14.0
BTU/h
42700
42700
42700
-
-
-
11300
47800
Current
A
1.48
1.44
1.39
16.6
15.9
15.3
-
-
Input power
W
215
215
215
3.355k
3.355k
3.355k
-
-
TOTAL W
-
3.570k
3.570k
3.570k
840
4.600k
Annual consumption
TOTAL kWh *
4
-
-
1785
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.50
3.50 / A
3.50
3.93
3.04
Erp
*
6
Pdesign
kW
-
-
-
-
12.5
-
-
-
η 
s,c
%
-
-
-
-
219.6
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
92
92
91
-
-
Noise indoor
dB-A (H/M/L)
39/35/32
-
-
-
Power Level dB
61/57/54
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
H
E
A
T
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
4.1
16.0
BTU/h
47800
47800
47800
-
-
-
14000
54600
Current
A
1.46
1.42
1.38
16.3
15.8
15.1
-
-
Input power
W
210
210
210
3.270k
3.270k
3.270k
-
-
TOTAL W
-
3.480k
3.480k
3.480k
900
5.200k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.02
4.02 / A
4.02
4.56
3.08
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
12.5
-
-
-
Tbivalent
°C
-
-
-
-
-9
-
-
-
η 
s,h
%
-
-
-
-
145.9
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
91
90
90
-
-
Noise indoor
dB-A (H/M/L)
39/35/32
-
-
-
Power Level dB
61/57/54
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
1.80/265
1.75/265
1.70/265
28.0/6.000k 28.0/6.200k 28.0/6.400k
-
Starting current(A) / Comp output(W)
-
-
-
16.6/3.0k
15.9/3.0k
15.3/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
200
90×2
-
Moisture removal volume
L/h(Pt/h)
7.9
(16.6)
-
-
External static pressure
Pa
100 (MIN10 - MAX150)
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
34.0/29.0/23.0 (1201)/(1024)/(812)
-
-
-
Heating
m³/min (ft³/min)
34.0/29.0/23.0 (1201)/(1024)/(812)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
130.0
(4591)
-
-
Heating
m³/min (ft³/min)
-
110.0
(3885)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
290  (11-13/32)
1416  (55-3/4)
-
Width
mm(inch)
1400  (55-1/8)
940  (37-1/32)
-
Depth
mm(inch)
700  (27-9/16)
340  (13-13/32)
-
Packing dimension
Height mm(inch)
355
1556
-
Width
mm(inch)
1614
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
45   (99)
98   (216)
-
(GROSS)  kg(lb)
54   (119)
108   (238)
-
Layers limit (actually)
9 (10) 
1 (2) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:  η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   14
19/09/26   17:01:36
1-1-4-15
1
1
Single -Type
1-1.  Unit Specifications
PE1
4. Low Silhouette Ducted Type S-140PF1E5B / U-140PE1E5A
INDOOR
MODEL
S-140PF1E5B
-
-
OUTDOOR
MODEL
-
U-140PE1E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
3.3
15.5
BTU/h
47800
47800
47800
-
-
-
11300
52900
Current
A
1.55
1.50
1.47
20.1
19.3
18.6
-
-
Input power
W
225
225
225
4.085k
4.085k
4.085k
-
-
TOTAL W
-
4.310k
4.310k
4.310k
840
6.000k
Annual consumption
TOTAL kWh *
4
-
-
2155
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.25
3.25 / A
3.25
3.93
2.58
Erp
*
6
Pdesign
kW
-
-
-
-
14.0
-
-
-
η 
s,c
%
-
-
-
-
213.4
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
93
92
92
-
-
Noise indoor
dB-A (H/M/L)
40/36/33
-
-
-
Power Level dB
62/58/55
-
-
-
Noise outdoor
dB-A (H/L)
-
54/-
-
-
Power Level dB
-
71/-
-
-
H
E
A
T
I
N
G
Capacity
kW
16.0
16.0
16.0
-
-
-
4.1
18.0
BTU/h
54600
54600
54600
-
-
-
14000
61400
Current
A
1.55
1.50
1.46
19.9
19.1
18.4
-
-
Input power
W
225
225
225
4.215k
4.215k
4.215k
-
-
TOTAL W
-
4.440k
4.440k
4.440k
900
5.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.60
3.60 / A
3.60
4.56
3.05
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
14.0
-
-
-
Tbivalent
°C
-
-
-
-
-7
-
-
-
η 
s,h
%
-
-
-
-
142.3
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
96
96
95
-
-
Noise indoor
dB-A (H/M/L)
40/36/33
-
-
-
Power Level dB
62/58/55
-
-
-
Noise outdoor
dB-A (H/L)
-
55/-
-
-
Power Level dB
-
71/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
1.91/285
1.86/285
1.81/285
30.0/6.450k 30.0/6.650k 30.0/6.850k
-
Starting current(A) / Comp output(W)
-
-
-
20.1/3.0k
19.3/3.0k
18.6/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
200
90×2
-
Moisture removal volume
L/h(Pt/h)
9.0
(18.9)
-
-
External static pressure
Pa
100 (MIN10 - MAX150)
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
36.0/32.0/25.0 (1271)/(1130)/(883)
-
-
-
Heating
m³/min (ft³/min)
36.0/32.0/25.0 (1271)/(1130)/(883)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
135.0
(4767)
-
-
Heating
m³/min (ft³/min)
-
120.0
(4238)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
290  (11-13/32)
1416  (55-3/4)
-
Width
mm(inch)
1400  (55-1/8)
940  (37-1/32)
-
Depth
mm(inch)
700  (27-9/16)
340  (13-13/32)
-
Packing dimension
Height mm(inch)
355
1556
-
Width
mm(inch)
1614
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
45   (99)
98   (216)
-
(GROSS)  kg(lb)
54   (119)
108   (238)
-
Layers limit (actually)
9 (10) 
1 (2) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:  η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   15
19/09/26   17:01:37
1-1-4-16
1
1
Simultaneous (Twin) -Type
1-1.  Unit Specifications
PE1
4. Low Silhouette Ducted Type S-36PF1E5B×2 / U-71PE1E8A
INDOOR
MODEL
S-36PF1E5B×2
-
-
OUTDOOR
MODEL
-
U-71PE1E8A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO13253  /  EN14511  /  EN14825  /   EN12102
Power supply
Ø, Hz
1ø 50Hz
3ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
7.10
7.10
7.10
-
-
-
3.2
8.0
BTU/h
24200
24200
24200
-
-
-
10900
27300
Current
A
0.60×2
0.57×2
0.56×2
2.75
2.65
2.60
-
-
Input power
W
70×2
70×2
70×2
1.730k
1.730k
1.730k
-
-
TOTAL W
-
1.870k
1.870k
1.870k
640
2.650k
Annual consumption
TOTAL kWh *
4
-
-
935
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.80
3.80 / A
3.80
5.00
3.02
Erp
*
6
Pdesign
kW
-
-
-
-
7.1
-
-
-
SEER
(W/W)
-
-
-
-
5.8
-
-
-
Annual consumption
kWh
-
-
-
-
428
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
96
94
93
-
-
Noise indoor
dB-A (H/M/L)
33/29/25
-
-
-
-
-
Power Level dB
55/51/47
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
48/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
8.0
8.0
8.0
-
-
-
2.8
9.0
BTU/h
27300
27300
27300
-
-
-
9600
30700
Current
A
0.60×2
0.57×2
0.56×2
3.10
3.00
2.90
-
-
Input power
W
70×2
70×2
70×2
1.960k
1.960k
1.960k
-
-
TOTAL W
-
2.100k
2.100k
2.100k
580
2.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.81
3.81 / A
3.81
4.83
3.10
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
7.1
-
-
-
Tbivalent
°C
-
-
-
-
-9
-
-
-
SCOP
(W/W)
-
-
-
-
3.9
-
-
-
Annual consumption
kWh
-
-
-
-
2548
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
96
94
94
-
-
Noise indoor
dB-A (H/M/L)
33/29/25
-
-
-
Power Level dB
55/51/47
-
-
-
Noise outdoor
dB-A (H/L)
-
50/-
-
-
Power Level dB
-
67/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.86×2/105×2 0.82×2/105×2 0.79×2/105×2 7.0/4.150k
7.0/4.360k
7.0/4.530k
-
Starting current(A) / Comp output(W)
-
-
-
3.10/2.0k
3.00/2.0k
2.90/2.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
120
90
-
Moisture removal volume
L/h(Pt/h)
4.2
(2.1×2)
(8.8)
-
-
External static pressure
Pa
70 (MIN10 - MAX150)
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
14.0×2/13.0×2/10.0×2 (494)×2/(459)×2/(353)×2
-
-
-
Heating
m³/min (ft³/min)
14.0×2/13.0×2/10.0×2 (494)×2/(459)×2/(353)×2
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
60.0
(2119)
-
-
Heating
m³/min (ft³/min)
-
60.0
(2119)
-
-
Refrigerant type / amount g(oz)
-
R410A
2.35k
(82.9)
-
Product dimension
Height mm(inch)
290  (11-13/32)
996  (39-7/32)
-
Width
mm(inch)
800  (31-1/2)
940  (37-1/32)
-
Depth
mm(inch)
700  (27-9/16)
340  (13-13/32)
-
Packing dimension
Height mm(inch)
355
1136
-
Width
mm(inch)
1014
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
28   (62)
71   (157)
-
(GROSS)  kg(lb)
35   (78)
79   (174)
-
Layers limit (actually)
9 (10) 
2 (3) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 50m
(16.4 ~ 164.0)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, 
Other fiche data indicates in an attached sheet.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   16
19/09/26   17:01:37
Page of 127
Display

Click on the first or last page to see other U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B service manuals if exist.