Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ▷ View online
1-1-4-25
1
1
Single -Type
1-1. Unit Specifications
PE1
4. Low Silhouette Ducted Type S-100PF1E5B / U-100PE1E8A
INDOOR
MODEL
S-100PF1E5B
-
-
OUTDOOR
MODEL
-
U-100PE1E8A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253 / EN14511 / EN14825 / EN12102
Power supply
Ø, Hz
1ø 50Hz
3ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
10.0
10.0
10.0
-
-
-
3.3
12.5
BTU/h
34100
34100
34100
-
-
-
11300
42700
Current
A
1.35
1.30
1.27
3.68
3.53
3.43
-
-
Input power
W
195
195
195
2.245k
2.245k
2.245k
-
-
TOTAL W
-
2.440k
2.440k
2.440k
840
3.700k
Annual consumption
TOTAL kWh *
4
-
-
1220
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.10
4.10 / A
4.10
3.93
3.38
Erp
*
6
Pdesign
kW
-
-
-
-
10.0
-
-
-
SEER
(W/W)
-
-
-
-
5.7
-
-
-
Annual consumption
kWh
-
-
-
-
614
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
93
92
91
-
-
Noise indoor
dB-A (H/M/L)
38/34/31
-
-
-
Power Level dB
60/56/53
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
H
E
A
T
I
N
G
Capacity
kW
11.2
11.2
11.2
-
-
-
4.1
14.0
BTU/h
38200
38200
38200
-
-
-
14000
47800
Current
A
1.37
1.34
1.29
3.86
3.70
3.58
-
-
Input power
W
200
200
200
2.400k
2.400k
2.400k
-
-
TOTAL W
-
2.600k
2.600k
2.600k
900
4.400k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.31
4.31 / A
4.31
4.56
3.18
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
10.0
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
3.8
-
-
-
Annual consumption
kWh
-
-
-
-
3684
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
94
94
93
-
-
Noise indoor
dB-A (H/M/L)
38/34/31
-
-
-
Power Level dB
60/56/53
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
(Q8.8kW/W4.200kW/COP2.10)
-
Max Current(A) / Max Input power(W)
1.80/265
1.75/265
1.70/265
9.0/5.550k
9.0/5.850k
9.0/6.100k
-
Starting current(A) / Comp output(W)
-
-
-
3.86/3.0k
3.70/3.0k
3.58/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
200
90×2
-
Moisture removal volume
L/h(Pt/h)
6.0
(12.6)
-
-
External static pressure
Pa
100 (MIN10 - MAX150)
-
-
Indoor
Air flow
Cooling
m³/min (ft³/min)
32.0/26.0/21.0 (1130)/(918)/(742)
-
-
-
Heating
m³/min (ft³/min)
32.0/26.0/21.0 (1130)/(918)/(742)
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
110.0
(3885)
-
-
Heating
m³/min (ft³/min)
-
95.0
(3355)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
290 (11-13/32)
1416 (55-3/4)
-
Width
mm(inch)
1400 (55-1/8)
940 (37-1/32)
-
Depth
mm(inch)
700 (27-9/16)
340 (13-13/32)
-
Packing dimension
Height mm(inch)
355
1556
-
Width
mm(inch)
1614
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
45 (99)
98 (216)
-
(GROSS) kg(lb)
54 (119)
108 (238)
-
Layers limit (actually)
9 (10)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m
(0.538)
-
Pipe length for additional gas m (ft)
30m
(98.4)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
: If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
: SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 25
19/09/26 17:01:40
1-1-4-26
1
1
Single -Type
1-1. Unit Specifications
PE1
4. Low Silhouette Ducted Type S-125PF1E5B / U-125PE1E8A
INDOOR
MODEL
S-125PF1E5B
-
-
OUTDOOR
MODEL
-
U-125PE1E8A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz
1ø 50Hz
3ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
12.5
12.5
12.5
-
-
-
3.3
14.0
BTU/h
42700
42700
42700
-
-
-
11300
47800
Current
A
1.48
1.44
1.39
5.52
5.29
5.12
-
-
Input power
W
215
215
215
3.355k
3.355k
3.355k
-
-
TOTAL W
-
3.570k
3.570k
3.570k
840
4.600k
Annual consumption
TOTAL kWh *
4
-
-
1785
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.50
3.50 / A
3.50
3.93
3.04
Erp
*
6
Pdesign
kW
-
-
-
-
12.5
-
-
-
η
s,c
%
-
-
-
-
219.0
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
92
92
91
-
-
Noise indoor
dB-A (H/M/L)
39/35/32
-
-
-
Power Level dB
61/57/54
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
H
E
A
T
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
4.1
16.0
BTU/h
47800
47800
47800
-
-
-
14000
54600
Current
A
1.46
1.42
1.38
5.44
5.26
5.05
-
-
Input power
W
210
210
210
3.270k
3.270k
3.270k
-
-
TOTAL W
-
3.480k
3.480k
3.480k
900
5.200k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.02
4.02 / A
4.02
4.56
3.08
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
12.5
-
-
-
Tbivalent
°C
-
-
-
-
-9
-
-
-
η
s,h
%
-
-
-
-
145.9
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
91
90
90
-
-
Noise indoor
dB-A (H/M/L)
39/35/32
-
-
-
Power Level dB
61/57/54
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
(Q10.5kW/W5.200kW/COP2.02)
-
Max Current(A) / Max Input power(W)
1.80/265
1.75/265
1.70/265
10.0/6.200k 10.0/6.500k 10.0/6.750k
-
Starting current(A) / Comp output(W)
-
-
-
5.52/3.0k
5.29/3.0k
5.12/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
200
90×2
-
Moisture removal volume
L/h(Pt/h)
7.9
(16.6)
-
-
External static pressure
Pa
100 (MIN10 - MAX150)
-
-
Indoor
Air flow
Cooling
m³/min (ft³/min)
34.0/29.0/23.0 (1201)/(1024)/(812)
-
-
-
Heating
m³/min (ft³/min)
34.0/29.0/23.0 (1201)/(1024)/(812)
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
130.0
(4591)
-
-
Heating
m³/min (ft³/min)
-
110.0
(3885)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
290 (11-13/32)
1416 (55-3/4)
-
Width
mm(inch)
1400 (55-1/8)
940 (37-1/32)
-
Depth
mm(inch)
700 (27-9/16)
340 (13-13/32)
-
Packing dimension
Height mm(inch)
355
1556
-
Width
mm(inch)
1614
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
45 (99)
98 (216)
-
(GROSS) kg(lb)
54 (119)
108 (238)
-
Layers limit (actually)
9 (10)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m
(0.538)
-
Pipe length for additional gas m (ft)
30m
(98.4)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
: If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
: η
s,c
and
η
s,h
classification is at 230V(400V) only in accordance with EN-14825. For heating,
η
s,h
indicates the value of only Average heating season.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 26
19/09/26 17:01:40
1-1-4-27
1
1
Single -Type
1-1. Unit Specifications
PE1
4. Low Silhouette Ducted Type S-140PF1E5B / U-140PE1E8A
INDOOR
MODEL
S-140PF1E5B
-
-
OUTDOOR
MODEL
-
U-140PE1E8A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz
1ø 50Hz
3ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
3.3
15.5
BTU/h
47800
47800
47800
-
-
-
11300
52900
Current
A
1.55
1.50
1.47
6.69
6.42
6.18
-
-
Input power
W
225
225
225
4.085k
4.085k
4.085k
-
-
TOTAL W
-
4.310k
4.310k
4.310k
840
6.000k
Annual consumption
TOTAL kWh *
4
-
-
2155
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.25
3.25 / A
3.25
3.93
2.58
Erp
*
6
Pdesign
kW
-
-
-
-
14.0
-
-
-
η
s,c
%
-
-
-
-
212.8
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
93
92
92
-
-
Noise indoor
dB-A (H/M/L)
40/36/33
-
-
-
Power Level dB
62/58/55
-
-
-
Noise outdoor
dB-A (H/L)
-
54/-
-
-
Power Level dB
-
71/-
-
-
H
E
A
T
I
N
G
Capacity
kW
16.0
16.0
16.0
-
-
-
4.1
18.0
BTU/h
54600
54600
54600
-
-
-
14000
61400
Current
A
1.55
1.50
1.46
6.64
6.35
6.15
-
-
Input power
W
225
225
225
4.215k
4.215k
4.215k
-
-
TOTAL W
-
4.440k
4.440k
4.440k
900
5.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.60
3.60 / A
3.60
4.56
3.05
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
14.0
-
-
-
Tbivalent
°C
-
-
-
-
-7
-
-
-
η
s,h
%
-
-
-
-
142.3
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
96
96
95
-
-
Noise indoor
dB-A (H/M/L)
40/36/33
-
-
-
Power Level dB
62/58/55
-
-
-
Noise outdoor
dB-A (H/L)
-
55/-
-
-
Power Level dB
-
71/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
(Q11.5kW/W5.800kW/COP1.98)
-
Max Current(A) / Max Input power(W)
1.91/285
1.86/285
1.81/285
11.0/6.800k 11.0/7.150k 11.0/7.450k
-
Starting current(A) / Comp output(W)
-
-
-
6.69/3.0k
6.42/3.0k
6.18/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
200
90×2
-
Moisture removal volume
L/h(Pt/h)
9.0
(18.9)
-
-
External static pressure
Pa
100 (MIN10 - MAX150)
-
-
Indoor
Air flow
Cooling
m³/min (ft³/min)
36.0/32.0/25.0 (1271)/(1130)/(883)
-
-
-
Heating
m³/min (ft³/min)
36.0/32.0/25.0 (1271)/(1130)/(883)
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
135.0
(4767)
-
-
Heating
m³/min (ft³/min)
-
120.0
(4238)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
290 (11-13/32)
1416 (55-3/4)
-
Width
mm(inch)
1400 (55-1/8)
940 (37-1/32)
-
Depth
mm(inch)
700 (27-9/16)
340 (13-13/32)
-
Packing dimension
Height mm(inch)
355
1556
-
Width
mm(inch)
1614
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
45 (99)
98 (216)
-
(GROSS) kg(lb)
54 (119)
108 (238)
-
Layers limit (actually)
9 (10)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m
(0.538)
-
Pipe length for additional gas m (ft)
30m
(98.4)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
: If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
: η
s,c
and
η
s,h
classification is at 230V(400V) only in accordance with EN-14825. For heating,
η
s,h
indicates the value of only Average heating season.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 27
19/09/26 17:01:41
1-1-5-1
1
1
Single -Type
1-1. Unit Specifications
PE2
5. Ducted Type S-36PN1E5B / U-36PE2E5A
INDOOR
MODEL
S-36PN1E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-36PE2E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253 / EN14511 / EN14825 / EN12102
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
3.6
3.6
3.6
-
-
-
1.5
4.0
BTU/h
12300
12300
12300
-
-
-
5100
13600
Current
A
0.42
0.43
0.44
4.35
4.15
3.95
-
-
Input power
W
90
95
100
0.870k
0.865k
0.860k
-
-
TOTAL W
-
0.960k
0.960k
0.960k
340
1.120k
Annual consumption
TOTAL kWh *
4
-
-
480
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.75
3.75/A
3.75
4.41
3.57
Erp
*
6
Pdesign
kW
-
-
-
-
3.6
-
-
-
SEER
(W/W)
-
-
-
-
4.6
-
-
-
Annual consumption
kWh
-
-
-
-
269
-
-
-
Class
-
-
-
-
B
-
-
-
Power factor
%
-
-
-
91
91
91
-
-
Noise indoor
dB-A (H/M/L)
35/33/30
-
-
-
Power Level dB
57/55/52
-
-
-
Noise outdoor
dB-A (H/L)
-
45/-
-
-
Power Level dB
-
64/-
-
-
H
E
A
T
I
N
G
Capacity
kW
4.0
4.0
4.0
-
-
-
1.5
5.0
BTU/h
13600
13600
13600
-
-
-
5100
17100
Current
A
0.42
0.43
0.44
4.20
4.00
3.80
-
-
Input power
W
90
95
100
0.840k
0.835k
0.830k
-
-
TOTAL W
-
0.930k
0.930k
0.930k
290
1.250k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.30
4.30/A
4.30
5.17
4.00
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
3.6
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
3.8
-
-
-
Annual consumption
kWh
-
-
-
-
1324
-
-
-
elbu(-10°C)
kW
-
-
-
-
0.00
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
91
91
91
-
-
Noise indoor
dB-A (H/M/L)
35/33/30
-
-
-
Power Level dB
57/55/52
-
-
-
Noise outdoor
dB-A (H/L)
-
46/-
-
-
Power Level dB
-
66/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.60/130
0.62/140
0.63/150
11.0/2.20k
11.0/2.30k
11.0/2.40k
-
Starting current(A)/Comp output(W)
-
-
-
4.35/1.1k
4.15/1.1k
3.95/1.1k
-
Network Impedance(ΩMAX.)
-
-
Fan motor output (Indoor/Outdoor) W
60
60
-
Moisture removal volume
L/h(Pt/h)
2.1
(4.4)
-
-
External static pressure
Pa
25 (MAX80)
-
-
Indoor
Air flow
Cooling
m³/min (ft³/min)
14.0/12.0/10.0 (494)/(424)/(353)
-
-
-
Heating
m³/min (ft³/min)
14.0/12.0/10.0 (494)/(424)/(353)
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
38.0
(1342)
-
-
Heating
m³/min (ft³/min)
-
38.0
(1342)
-
-
Refrigerant type / amount g(oz)
-
R410A
1.40k
(49.4)
-
Product dimension
Height mm(inch)
250 (9-27/32)
619 (24-3/8)
-
Width
mm(inch)
780 [+100] 30-45/64 [+3-15/16])
799 (31-29/64)
-
Depth
mm(inch)
650 (25-19/32)
299 (11-49/64)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
338 (13-5/16)
688
-
Width
mm(inch)
991 (39-1/64)
931
-
Depth
mm(inch)
761 (29-61/64)
422
-
Weight
(NET)
kg(lb)
29 (64)
39 (86)
-
(GROSS) kg(lb)
34 (75)
44 (97)
-
Panel (NET) kg(lb)
-
-
-
Layers limit (actually)
5 (6)
5 (6)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
Max Working Pressure HP/LP Mpa (bar)
4.15/2.70 (41.5/27.0)
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
3 ~ 40m
(9.8 ~ 131.2)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
20g/m
(0.215)
-
Pipe length for additional gas m (ft)
30m
(98.4)
-
*1 : In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 : If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall
be used.
*3 : Network Impedance shall be applicable for EUROPE and CHINA models.
*4 : The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 : EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 : SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data
indicates in an attached sheet.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 1
19/09/26 17:01:41
Click on the first or last page to see other U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B service manuals if exist.