Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual ▷ View online
1-1-4-21
1
1
Simultaneous (Triple) -Type
1-1. Unit Specifications
PE1
4. Low Silhouette Ducted Type S-50PF1E5B×3 / U-140PE1E8A
INDOOR
MODEL
S-50PF1E5B×3
-
-
OUTDOOR
MODEL
-
U-140PE1E8A
-
Branch pipe
MODEL
CZ-P3HPC2
Performance test condition
ISO13253 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz
1ø 50Hz
3ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
3.3
15.5
BTU/h
47800
47800
47800
-
-
-
11300
52900
Current
A
0.77×3
0.74×3
0.71×3
6.69
6.42
6.18
-
-
Input power
W
100×3
100×3
100×3
4.085k
4.085k
4.085k
-
-
TOTAL W
-
4.385k
4.385k
4.385k
840
6.000k
Annual consumption
TOTAL kWh *
4
-
-
2192.5
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.19
3.19 / B
3.19
3.93
2.58
Erp
*
6
Pdesign
kW
-
-
-
-
14.0
-
-
-
η
s,c
%
-
-
-
-
225.7
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
93
92
92
-
-
Noise indoor
dB-A (H/M/L)
34/30/26
-
-
-
-
-
Power Level dB
56/52/48
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
54/-
-
-
Power Level dB
-
71/-
-
-
H
E
A
T
I
N
G
Capacity
kW
16.0
16.0
16.0
-
-
-
4.1
18.0
BTU/h
54600
54600
54600
-
-
-
14000
61400
Current
A
0.77×3
0.74×3
0.71×3
6.64
6.35
6.15
-
-
Input power
W
100×3
100×3
100×3
4.215k
4.215k
4.215k
-
-
TOTAL W
-
4.515k
4.515k
4.515k
900
5.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.54
3.54 / B
3.54
4.56
3.05
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
14.0
-
-
-
Tbivalent
°C
-
-
-
-
-7
-
-
-
η
s,h
%
-
-
-
-
143.0
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
96
96
95
-
-
Noise indoor
dB-A (H/M/L)
34/30/26
-
-
-
Power Level dB
56/52/48
-
-
-
Noise outdoor
dB-A (H/L)
-
55/-
-
-
Power Level dB
-
71/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
1.00×3/125×3 0.96×3/125×3 0.92×3/125×3 11.0/6.800k 11.0/7.150k 11.0/7.450k
-
Starting current(A) / Comp output(W)
-
-
-
6.69/3.0k
6.42/3.0k
6.18/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
120
90x2
-
Moisture removal volume
L/h(Pt/h)
9.0
(3.0×3)
(18.9)
-
-
External static pressure
Pa
70 (MIN10 - MAX150)
-
-
Indoor
Air flow
Cooling
m³/min (ft³/min)
16.0×3/15.0×3/12.0×3 (565)×3/(530)×3/(424)×3
-
-
-
Heating
m³/min (ft³/min)
16.0×3/15.0×3/12.0×3 (565)×3/(530)×3/(424)×3
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
135.0
(4767)
-
-
Heating
m³/min (ft³/min)
-
120.0
(4238)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
290 (11-13/32)
1416 (55-3/4)
-
Width
mm(inch)
800 (31-1/2)
940 (37-1/32)
-
Depth
mm(inch)
700 (27-9/16)
340 (13-13/32)
-
Packing dimension
Height mm(inch)
355
1556
-
Width
mm(inch)
1014
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
28 (62)
98 (216)
-
(GROSS) kg(lb)
35 (78)
108 (238)
-
Layers limit (actually)
9 (10)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m
(0.538)
-
Pipe length for additional gas m (ft)
20m
(65.6)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
: If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
: η
s,c
and
η
s,h
classification is at 230V(400V) only in accordance with EN-14825. For heating,
η
s,h
indicates the value of only Average heating season.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 21
19/09/26 17:01:39
1-1-4-22
1
1
Simultaneous (Twin) -Type
1-1. Unit Specifications
PE1
4. Low Silhouette Ducted Type S-60PF1E5B×2 / U-125PE1E8A
INDOOR
MODEL
S-60PF1E5B×2
-
-
OUTDOOR
MODEL
-
U-125PE1E8A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO13253 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz
1ø 50Hz
3ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
12.5
12.5
12.5
-
-
-
3.3
14.0
BTU/h
42700
42700
42700
-
-
-
11300
47800
Current
A
0.91×2
0.89×2
0.87×2
5.52
5.29
5.12
-
-
Input power
W
120×2
120×2
120×2
3.355k
3.355k
3.355k
-
-
TOTAL W
-
3.595k
3.595k
3.595k
840
4.600k
Annual consumption
TOTAL kWh *
4
-
-
1797.5
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.48
3.48 / A
3.48
3.93
3.04
Erp
*
6
Pdesign
kW
-
-
-
-
12.5
-
-
-
η
s,c
%
-
-
-
-
233.4
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
92
92
91
-
-
Noise indoor
dB-A (H/M/L)
35/32/26
-
-
-
-
-
Power Level dB
57/54/48
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
H
E
A
T
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
4.1
16.0
BTU/h
47800
47800
47800
-
-
-
14000
54600
Current
A
0.91×2
0.89×2
0.87×2
5.44
5.26
5.05
-
-
Input power
W
120×2
120×2
120×2
3.270k
3.270k
3.270k
-
-
TOTAL W
-
3.510k
3.510k
3.510k
900
5.200k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.99
3.99 / A
3.99
4.56
3.08
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
12.5
-
-
-
Tbivalent
°C
-
-
-
-
-9
-
-
-
η
s,h
%
-
-
-
-
146.6
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
91
90
90
-
-
Noise indoor
dB-A (H/M/L)
35/32/26
-
-
-
Power Level dB
57/54/48
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
1.26×2/160×2 1.20×2/160×2 1.15×2/160×2 10.0/6.200k 10.0/6.500k 10.0/6.750k
-
Starting current(A) / Comp output(W)
-
-
-
5.52/3.0k
5.29/3.0k
5.12/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
120
90x2
-
Moisture removal volume
L/h(Pt/h)
7.9
(3.9×2)
(16.6)
-
-
External static pressure
Pa
70 (MIN10 - MAX150)
-
-
Indoor
Air flow
Cooling
m³/min (ft³/min)
21.0×2/19.0×2/15.0×2 (742)×2/(671)×2/(530)×2
-
-
-
Heating
m³/min (ft³/min)
21.0×2/19.0×2/15.0×2 (742)×2/(671)×2/(530)×2
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
130.0
(4591)
-
-
Heating
m³/min (ft³/min)
-
110.0
(3885)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
290 (11-13/32)
1416 (55-3/4)
-
Width
mm(inch)
1000 (39-3/8)
940 (37-1/32)
-
Depth
mm(inch)
700 (27-9/16)
340 (13-13/32)
-
Packing dimension
Height mm(inch)
355
1556
-
Width
mm(inch)
1214
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
33 (73)
98 (216)
-
(GROSS) kg(lb)
41 (91)
108 (238)
-
Layers limit (actually)
9 (10)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m
(0.538)
-
Pipe length for additional gas m (ft)
30m
(98.4)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
: If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
: η
s,c
and
η
s,h
classification is at 230V(400V) only in accordance with EN-14825. For heating,
η
s,h
indicates the value of only Average heating season.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 22
19/09/26 17:01:39
1-1-4-23
1
1
Single -Type
1-1. Unit Specifications
PE1
4. Low Silhouette Ducted Type S-71PF1E5B / U-71PE1E8A
INDOOR
MODEL
S-71PF1E5B
-
-
OUTDOOR
MODEL
-
U-71PE1E8A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253 / EN14511 / EN14825 / EN12102
Power supply
Ø, Hz
1ø 50Hz
3ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
7.10
7.10
7.10
-
-
-
3.2
8.0
BTU/h
24200
24200
24200
-
-
-
10900
27300
Current
A
0.91
0.89
0.87
2.75
2.65
2.60
-
-
Input power
W
120
120
120
1.730k
1.730k
1.730k
-
-
TOTAL W
-
1.850k
1.850k
1.850k
640
2.650k
Annual consumption
TOTAL kWh *
4
-
-
925
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.84 / A
3.84 / A
3.84 / A
5.00
3.02
Erp
*
6
Pdesign
kW
-
-
-
-
7.1
-
-
-
SEER
(W/W)
-
-
-
-
6.0
-
-
-
Annual consumption
kWh
-
-
-
-
414
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
96
94
93
-
-
Noise indoor
dB-A (H/M/L)
35/32/26
-
-
-
Power Level dB
57/54/48
-
-
-
Noise outdoor
dB-A (H/L)
-
48/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
8.00
8.00
8.00
-
-
-
2.8
9.0
BTU/h
27300
27300
27300
-
-
-
9600
30700
Current
A
0.91
0.89
0.87
3.10
3.00
2.90
-
-
Input power
W
120
120
120
1.960k
1.960k
1.960k
-
-
TOTAL W
-
2.080k
2.080k
2.080k
580
2.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.85 / A
3.85 / A
3.85 / A
4.83
3.10
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
7.1
-
-
-
Tbivalent
°C
-
-
-
-
-9
-
-
-
SCOP
(W/W)
-
-
-
-
3.9
-
-
-
Annual consumption
kWh
-
-
-
-
2548
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
96
94
94
-
-
Noise indoor
dB-A (H/M/L)
35/32/26
-
-
-
Power Level dB
57/54/48
-
-
-
Noise outdoor
dB-A (H/L)
-
50/-
-
-
Power Level dB
-
67/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
1.26/160
1.20/160
1.15/160
7.0/4.150k
7.0/4.360k
7.0/4.530k
-
Starting current(A) / Comp output(W)
-
-
-
3.10/2.0k
3.00/2.0k
2.90/2.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
120
90
-
Moisture removal volume
L/h(Pt/h)
4.2
(8.8)
-
-
External static pressure
Pa
70 (MIN10 - MAX150)
-
-
Indoor
Air flow
Cooling
m³/min (ft³/min)
21.0/19.0/15.0 (742)/(671)/(530)
-
-
-
Heating
m³/min (ft³/min)
21.0/19.0/15.0 (742)/(671)/(530)
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
60.0
(2119)
-
-
Heating
m³/min (ft³/min)
-
60.0
(2119)
-
-
Refrigerant type / amount g(oz)
-
R410A
2.35k
(82.9)
-
Product dimension
Height mm(inch)
290 (11-13/32)
996 (39-7/32)
-
Width
mm(inch)
1000 (39-3/8)
940 (37-1/32)
-
Depth
mm(inch)
700 (27-9/16)
340 (13-13/32)
-
Packing dimension
Height mm(inch)
355
1136
-
Width
mm(inch)
1214
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
33 (73)
71 (157)
-
(GROSS) kg(lb)
41 (91)
79 (174)
-
Layers limit (actually)
9 (10)
2 (3)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 50m
(16.4 ~ 164.0)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m
(0.538)
-
Pipe length for additional gas m (ft)
30m
(98.4)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
: If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
: SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 23
19/09/26 17:01:39
1-1-4-24
1
1
Simultaneous (Twin) -Type
1-1. Unit Specifications
PE1
4. Low Silhouette Ducted Type S-71PF1E5B×2 / U-140PE1E8A
INDOOR
MODEL
S-71PF1E5B×2
-
-
OUTDOOR
MODEL
-
U-140PE1E8A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO13253 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz
1ø 50Hz
3ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
3.3
15.5
BTU/h
47800
47800
47800
-
-
-
11300
52900
Current
A
0.91×2
0.89×2
0.87×2
6.69
6.42
6.18
-
-
Input power
W
120×2
120×2
120×2
4.085k
4.085k
4.085k
-
-
TOTAL W
-
4.325k
4.325k
4.325k
840
6.000k
Annual consumption
TOTAL kWh *
4
-
-
2162.5
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.24
3.24 / A
3.24
3.93
2.58
Erp
*
6
Pdesign
kW
-
-
-
-
14.0
-
-
-
η
s,c
%
-
-
-
-
225.7
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
93
92
92
-
-
Noise indoor
dB-A (H/M/L)
35/32/26
-
-
-
-
-
Power Level dB
57/54/48
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
54/-
-
-
Power Level dB
-
71/-
-
-
H
E
A
T
I
N
G
Capacity
kW
16.0
16.0
16.0
-
-
-
4.1
18.0
BTU/h
54600
54600
54600
-
-
-
14000
61400
Current
A
0.91×2
0.89×2
0.87×2
6.64
6.35
6.15
-
-
Input power
W
120×2
120×2
120×2
4.215k
4.215k
4.215k
-
-
TOTAL W
-
4.455k
4.455k
4.455k
900
5.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.59
3.59 / A
3.59
4.56
3.05
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
14.0
-
-
-
Tbivalent
°C
-
-
-
-
-7
-
-
-
η
s,h
%
-
-
-
-
143.0
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
96
96
95
-
-
Noise indoor
dB-A (H/M/L)
35/32/26
-
-
-
Power Level dB
57/54/48
-
-
-
Noise outdoor
dB-A (H/L)
-
55/-
-
-
Power Level dB
-
71/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
1.26×2/160×2 1.20×2/160×2 1.15×2/160×2 11.0/6.800k 11.0/7.150k 11.0/7.450k
-
Starting current(A) / Comp output(W)
-
-
-
6.69/3.0k
6.42/3.0k
6.18/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
120
90x2
-
Moisture removal volume
L/h(Pt/h)
9.0
(4.5×2)
(18.9)
-
-
External static pressure
Pa
70 (MIN10 - MAX150)
-
-
Indoor
Air flow
Cooling
m³/min (ft³/min)
21.0×2/19.0×2/15.0×2 (742)×2/(671)×2/(530)×2
-
-
-
Heating
m³/min (ft³/min)
21.0×2/19.0×2/15.0×2 (742)×2/(671)×2/(530)×2
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
135.0
(4767)
-
-
Heating
m³/min (ft³/min)
-
120.0
(4238)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
290 (11-13/32)
1416 (55-3/4)
-
Width
mm(inch)
1000 (39-3/8)
940 (37-1/32)
-
Depth
mm(inch)
700 (27-9/16)
340 (13-13/32)
-
Packing dimension
Height mm(inch)
355
1556
-
Width
mm(inch)
1214
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
33 (73)
98 (216)
-
(GROSS) kg(lb)
41 (91)
108 (238)
-
Layers limit (actually)
9 (10)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m
(0.538)
-
Pipe length for additional gas m (ft)
30m
(98.4)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
: If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
: η
s,c
and
η
s,h
classification is at 230V(400V) only in accordance with EN-14825. For heating,
η
s,h
indicates the value of only Average heating season.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 24
19/09/26 17:01:40