Harman Kardon DMC 1000 (serv.man2) EMC - CB Certificate ▷ View online
Page 9 of 100
ST-07348
IEC/EN 60065
Clause
Requirement – Test
Result - Remark
Verdict
TRF No.: IECEN60065G
Components bridging reinforced or double
insulation complying with 14.1 a) or 14.3
insulation complying with 14.1 a) or 14.3
Evaluated in approved
building-in power supply
module
building-in power supply
module
P
Basic insulation bridged by components complying
with 14.3.4.3
with 14.3.4.3
N/A
Basic and supplementary insulation each being
bridged by a capacitor complying with 14.2.1 a)
bridged by a capacitor complying with 14.2.1 a)
No such capacitor
N/A
Reinforced or double insulation being bridged with
2 capacitors in series complying with 14.2.1 a)
2 capacitors in series complying with 14.2.1 a)
No such capacitor
N/A
Reinforced or double insulation being bridged with
a single capacitor complying with 14.2.1 b)
a single capacitor complying with 14.2.1 b)
Evaluated in approved
building-in power supply
module
building-in power supply
module
P
8.7
This clause is void
N/A
8.8
Basic or supplementary insulation > 0,4 mm (mm)
................................................................................. :
Primary lead wire: min. 0.4
mm;
mm;
Evaluated in approved
building-in power supply
module
building-in power supply
module
P
Reinforced insulation > 0,4 mm (mm) ................... : Evaluated in approved
building-in power supply
module
module
P
Thin sheet insulation (excluding non-separable thin
sheet insulation. See 8.22)
sheet insulation. See 8.22)
Evaluated in approved
building-in power supply
module
building-in power supply
module
P
Basic or supplementary insulation, at least two
layers, each meeting 10.3
layers, each meeting 10.3
N/A
Basic or supplementary insulation, three layers
any two of which meet 10.3
any two of which meet 10.3
N/A
Reinforced insulation, two layers each of which
meet 10.3
meet 10.3
N/A
Reinforced insulation, three layers any two which
meet 10.3
meet 10.3
N/A
8.9
Adequate insulation between internal hazardous
live conductors and accessible parts
live conductors and accessible parts
All internal wires with only
basic insulation are routed so
that they are not close to any
live bare components
basic insulation are routed so
that they are not close to any
live bare components
P
Adequate insulation between internal hazardous
live parts and conductors connected to accessible
parts
live parts and conductors connected to accessible
parts
All internal hazardous live parts
are separate by double or
reinforced insulation from
these conductors
are separate by double or
reinforced insulation from
these conductors
P
Page 10 of 100
ST-07348
IEC/EN 60065
Clause
Requirement – Test
Result - Remark
Verdict
TRF No.: IECEN60065G
8.10
Double insulation between conductors connected
to the mains and accessible parts.
Double insulation between internal hazardous live
parts and conductors connected to accessible
parts
to the mains and accessible parts.
Double insulation between internal hazardous live
parts and conductors connected to accessible
parts
The EUT is Class I apparatus
N/A
8.11
Detaching of wires
No undue reduction of creepages or clearance
distances if wires become detached
distances if wires become detached
All wires are fixed by double
securement
securement
P
Vibration test carried out ........................................ : See sub-clause 12.1.2
P
8.12
This clause is void
N/A
8.13
Adequate fastening of windows, lenses, lamp
covers etc. (pull test 20 N for 10 s)
covers etc. (pull test 20 N for 10 s)
No such device
N/A
8.14
Adequate fastening of covers (pull test 50 N for
10 s)
10 s)
No such cover
N/A
8.15
No risk of damage to the insulation of internal
wiring due to hot parts or sharp edges
wiring due to hot parts or sharp edges
The internal lead wires are
secured away from the hot
parts and sharp edges by the
construction
secured away from the hot
parts and sharp edges by the
construction
P
8.16
Only special supply equipment can be used
The EUT is supplied from AC
mains
mains
N/A
8.17
Insulated winding wire without additional
interleaved insulation
interleaved insulation
No such insulated winding wire
N/A
8.18
Endurance test as required by 8.17
See above
N/A
8.19
Disconnection from the mains
8.19.1
Disconnect device
The mains plug is used as the
disconnect device and see
also sub-clause 5.4.2
disconnect device and see
also sub-clause 5.4.2
P
All-pole switch or circuit breaker with > 3 mm
contact separation
contact separation
See sub-clause 8.19.1
N/A
8.19.2
Mains switch ON indication
See sub-clause 8.19.1
N/A
8.20
Switch not fitted in the mains cord
No mains switch is fitted in the
mains cord
mains cord
P
8.21
Bridging components comply with clause 14
No such component within the
EUT
EUT
N/A
8.22
Non-separable thin sheet material
No such material
N/A
Page 11 of 100
ST-07348
IEC/EN 60065
Clause
Requirement – Test
Result - Remark
Verdict
TRF No.: IECEN60065G
9
ELECTRIC SHOCK HAZARD UNDER NORMAL OPERATING CONDITIONS
9.1
Testing on the outside
9.1.1
For voltages >1000 V ac or >1500 V dc complies
with clause 13.3.1 for basic insulation
with clause 13.3.1 for basic insulation
N/A
9.1.1.1
Touch current measured from terminal devices
using the network in annex D ................................. :
using the network in annex D ................................. :
Measured open-circuit voltage
between mains and user
accessible parts: max. 388
Vpeak;
U1: max. 0.54 Vpeak;
U2: max. 0.31 Vpeak;
between mains and user
accessible parts: max. 388
Vpeak;
U1: max. 0.54 Vpeak;
U2: max. 0.31 Vpeak;
Touch current measured max.
0.38 mA (limit: 3.5 mA, Class I
construction)
0.38 mA (limit: 3.5 mA, Class I
construction)
P
Discharge not exceeding 45
µ
C
< 45
µ
C
P
Energy of discharge not exceeding 350 mJ
N/A
9.1.1.2
Test with test finger and test probe
No hazardous live parts are
accessible by the test finger
accessible by the test finger
P
9.1.2
No hazardous live shafts of knobs, handles or
levers
levers
No hazardous live shafts of
operating knobs, handles,
levers or the likes are used
operating knobs, handles,
levers or the likes are used
N/A
9.1.3
Ventilation holes tested by means of
4 mm x 100 mm test pin
4 mm x 100 mm test pin
The test pin was not became
hazardous live
hazardous live
P
9.1.4
Terminal devices tested with 1 mm x 20 mm test
pin (10 N); test probe D of IEC 61032
pin (10 N); test probe D of IEC 61032
The test probe was not
became hazardous live
became hazardous live
P
Terminal devices tested with 1 mm x 100 mm
straight wire (1 N); test probe D of IEC 61032
straight wire (1 N); test probe D of IEC 61032
The test probe was not
became hazardous live
became hazardous live
P
9.1.5
Pre-set controls tested with 2,5 mm x 100 mm test
pin (10 N); test probe C of IEC 61032
pin (10 N); test probe C of IEC 61032
No pre-set control
N/A
9.1.6
No shock hazard due to stored charge on
withdrawal of the mains plug; voltage (V) after 2 s :
withdrawal of the mains plug; voltage (V) after 2 s :
Measured max. 4 Vpeak after
2 s
2 s
P
If C is not greater than 0,1
µ
F no test needed
N/A
9.1.7
Enclosure sufficiently resistant to external force
After the tests as below, the
EUT shown no damage and
hazardous live parts are not
accessible
EUT shown no damage and
hazardous live parts are not
accessible
P
Test probe 11 of IEC 61032 for 10 s (50 N)
P
Test hook of fig. 4 for 10 s (20 N)
P
30 mm diameter test tool for 5 s (100 or 250 N) ... : 100 N
P
9.2
No hazard after removing a cover by hand
No such cover provided
N/A
Page 12 of 100
ST-07348
IEC/EN 60065
Clause
Requirement – Test
Result - Remark
Verdict
TRF No.: IECEN60065G
10
INSULATION REQUIREMENTS
10.1
Insulation resistance (M
Ω
) at least 2 M
Ω
min. after
surge test for basic and 4 M
Ω
min. for reinforced
insulation ................................................................. :
N/A
10.2
Humidity treatment 48 h or 120 h .......................... : R.H. 95 %, 42
°
C, 120 h
P
10.3
Insulation resistance and dielectric strength
(see appended table 10.3)
P
Insulation resistance and dielectric strength
across BASIC or SUPPLEMENTARY insulation
(Class I)
across BASIC or SUPPLEMENTARY insulation
(Class I)
(see appended table 10.3)
P
Insulation resistance and dielectric strength
across REINFORCED insulation (Class II)
across REINFORCED insulation (Class II)
(see appended table 10.3)
P
11
FAULT CONDITIONS
11.1
No shock hazard under fault condition
P
11.2
Heating under fault condition
See below
P
No hazard from softening solder
No softening solder and
becoming fluid
becoming fluid
N/A
Flames extinguish within 10 seconds
No such condition occurred
N/A
Soldered terminations not used as protective
mechanism
mechanism
No such termination
N/A
11.2.1
Measurement of temperature rises
(see appended table 11.2)
P
11.2.2
Temperature rise of accessible parts
(see appended table 11.2)
P
11.2.3
Temperature rise of parts, other than windings,
providing electrical insulation
providing electrical insulation
(see appended table 11.2)
P
Temperature rise of printed circuit boards (PCB)
exceeding the limits of table 3 by max. 100 K for
max. 5 min
exceeding the limits of table 3 by max. 100 K for
max. 5 min
No temperature exceeded
N/A
a) Temperature rise of printed circuit boards (PCB)
to 20.1.3, exceeding the limits of table 3 by not
more than 100 K for an area not greater than
2 cm²
to 20.1.3, exceeding the limits of table 3 by not
more than 100 K for an area not greater than
2 cm²
No temperature exceeded
N/A
b) Temperature rise of printed circuit boards (PCB)
to 20.1.3 up to 300 K for an area not greater than
2 cm² for a maximum of 5 min
to 20.1.3 up to 300 K for an area not greater than
2 cm² for a maximum of 5 min
No temperature exceeded
N/A
Meets all the special conditions if conductors on
printed circuit boards are interrupted
printed circuit boards are interrupted
Traces on the PCB were not
interrupted
interrupted
N/A
Class I protective earthing maintained
It is still complying with
relevant requirements of this
standard
relevant requirements of this
standard
P
Click on the first or last page to see other DMC 1000 (serv.man2) service manuals if exist.