 d. R410A refrigerating machine oil
Conventionally, mineral oil or a synthetic oil such as alkylbenzene has been used for R22 refrigerating machine oil. Because
of the poor compatibility between R410A and conventional oils like mineral oil, however, there is a tendency for the
refrigerating machine oil to collect in the refrigerating cycle. For this reason, polyester and other synthetic oils which have
a high compatibility with R410A are used as refrigerating machine oil.
Because of the high hygroscopic property of synthetic oil, more care must be taken in its handling than was necessary with
conventional refrigerating machine oils. Also, these synthetic oils will degrade if mixed with mineral oil or alkylbenzene,
causing clogging in capillary tubes or compressor malfunction. Do not mix them under any circumstances.
10.1.2. Safety Measure When Installing / Receiving Refrigerant Piping
Cause the gas pressure of R410A is approximately 1.6 times as high as that of R22, a mistake in installation or servicing could
result in a major accident. It is essential that you use R410a tools and materials, and that you observe the following precautions
to ensure safety.
 1. Do not use any refrigerant other than R410A in ACs that have been used with R410A.
 2. If any refrigerant gas leaks while you are working, ventilate the room. Toxic gas may be generated if refrigerant gas is exposed
to a direct flame.
 3. When installing or transferring an AC, do not allow any air or substance other than R410A to mix into the refrigeration cycle. If
it does, the pressure in the refrigeration cycle can become abnormally high, possibly causing an explosion and/or injury.
 4. After finishing the installation, check to make sure there is no refrigerant gas leaking.
 5. When installing or transferring an AC, follow the instructions in the installation instructions carefully. Incorrect installation can
result in an abnormal refrigeration cycle or water leakage, electric shock, fire, etc.
 6. Do not perform any alterations on the AC unit under any circumstances. Have all repair work done by a specialist. Incorrect
repairs can result in an water leakage, electric shock, fire, etc.
10.2. TOOL FOR INSTALLING / SERVICING REFRIGERANT PIPING
10.2.1. Necessary Tools
In order to prevent an R410A AC from mistakenly being charged with any other refrigerant, the diameter of the 3-way valve service
port on the outdoor unit has been changed. Also, to increase its ability to withstand pressure, the opposing dimensions have been
changed for the refrigerant pipe flaring size and flare nut. Accordingly, when installing or servicing refrigerant piping, you must have
both the R410A and ordinary tools listed below.
Table 3 Tools for installation, transferring or replacement
Type of work
Ordinary tools
R410A tools
Flaring
Flaring tool (clutch type), pipe cutter,
reamer
Copper pipe gauge for clearance
Adjustment, flaring tool (clutch type)*1)
Bending, connecting pipes
Torque wrench (nominal diameter 1/4,
3/8,1/2) Fixed spanner (opposing sides 12
mm, 17 mm, 19 mm)Adjustable wrench,
Spring bender
Air purging
Vacuum pump Hexagonal wrench
(opposing sides 4 mm)
Manifold gauge, charging hose, vacuum
pump adaptor
Gas leak inspection
Gas leak inspection fluid or soapy water
Electric gas leak detector for HFC
refrigerant*2)
*1) You can use the conventional (R22) flaring tool. If you need to buy a new tool, buy the R410A type.
*2) Use when it is necessary to detect small gas leaks.
For other installation work, you should have the usual tools, such as screwdrivers (+,-), a metal-cutting saw, an electrical drill, a hole
core drill (65 or 70 dia.), a tape measure, a level, a thermometer, a clamp meter, an insulation tester, a voltmeter, etc.
Table 4 Tools for serving
Type of work
Ordinary tools
R410A tools
Refrigerant charging
Electronic scale for refrigerant charging
Refrigerant cylinder Charging orifice and
packing for refrigerant cylinder
Brazing
(Replacing
refrigerating
cycle
part*1)
Nitrogen blow set (be sure to use nitrogen
blowing for all brazing), and brazing), and
brazing machine
*1) Always replace the dryer of the outdoor unit at the same time. The replacement dryer is wrapped in a vacuum pack. Replace
it last among the refrigerating cycle parts. Start brazing as soon as you have opened the vacuum pack, and begin the vacuuming
operation within 2 hours.
53
10.2.2.  R410A Tools
 1. Cooper tube gauge for clearance adjustment
(used when flaring with the conventional flaring tool (clutch
type))
  • This gauge makes it easy to set the clearance for the
copper tube to 1.0-1.5 mm from the clamp bar of the
flaring tool.
 2. Flaring tool (clutch type)
  • In the R410A flaring tool, the receiving hole for the
clamp bar is enlarged so the clearance from the clamp
bar can be set to 0-0.5 mm, and the spring inside the
tool is strengthened to increase the strength of the pipe-
expanding torque. This flaring tools can also be used
with R22 piping, so we recommend that you select it if
you are buying a new flaring tool.
 3. Torque wrenches
 4. Manifold gauge
Fig. 1 Copper tube gauge for clearance adjustment
Fig. 2 Flaring tool (clutch type)
Fig. 3 Torque wrenches
Table 5
Conventional wrenches
R410A wrenches
For 1/4 (opposite side x torque)
17 mm x 18 N.m (180 kgf.cm)
17 mm x 18 N.m (180 kgf.cm)
For 3/3 (opposite side x torque)
22 mm x 42 N.m (180 kgf.cm)
22 mm x 42 N.m (180 kgf.cm)
For 1/2 (opposite side x torque)
24 mm x 55 N.m (180 kgf.cm)
26 mm x 55 N.m (180 kgf.cm)
  • Because the pressure is higher for the R410A type, the conventional type cannot be used.
Table 6 Difference between R410A and conventional high / low-pressure gauges
Conventional wrenches
R410A wrenches
High-pressure gauge (red)
-76 cmHg - 35 kgf/cm
3
-0.1 - 5.3 Mpa -76 cmHg - 53 kgf/cm
3
High-pressure gauge (blue)
-76 cmHg - 17 kgf/cm
3
-0.1 - 3.8 Mpa -76 cmHg - 38 kgf/cm
3
  • The shape of the manifold ports has been changed to prevent the possibility of mistakenly charging with another type of
refrigerant.
Table 7 Difference between R410A and conventional manifold port size
Conventional gauges
R410A gauges
Port size
7/6 UNF 20 threads
1/2 UNF 20 threads
54
 5. Charging hose
  • The pressure resistance of the charging hose has been
raised to match the higher pressure of R410A. The hose
material has also been changed to suit HFC use, and
the size of the fitting has been changed to match the
manifold ports.
 6. Vacuum pump adaptor
  • When using a vacuum pump for R410A, it is necessary
to install an electromagnetic valve to prevent the
vacuum pump oil from flowing back into the charging
hose. The vacuum pump adaptor is installed for that
purpose. if the vacuum pump oil (mineral oil) becomes
mixed with R410A, it will damage the unit.
 7. Electric gas leak detector for HFC refrigerant
  • The leak detector and halide torch that were used with
CFC and HCFC cannot be used with R410A (because
there is no chlorine in the refrigerant).
  • The present R134a leak detector can be used, but the
detection sensitivity will be lower (setting the sensitivity
for R134a at 1, the level for R410A will drop to 0.6).
  • For detecting small amounts of gas leakage, use the
electric gas leak detector for HFC refrigerant. (Detection
sensitivity with R410A is about 23 g/year).
Fig. 4 Manifold gauge charging hose
Fig. 5 Vacuum pump adaptor
Fig. 6 Electric gas leak detector for HFC refrigerant
Table 8 Difference between R410A and conventional charging hoses
Conventional hoses
R410A hoses
Pressure
resistance
Working pressure
3.4 MPa (35 kgf/cm
3
)
5.1 MPa (52 kgf/cm
3
)
Bursting pressure
17.2 MPa (175 kgf/cm
3
)
27.4 MPa (280 kgf/cm
3
)
Material
NBR rubber
HNBR rubber Nylon coating inside
55
 8. Electronic scale for refrigerant charging
  • Because of the high pressure and fast vaporizing speed
of R410A, the refrigerant cannot be held in a liquid
phase inside the charging cylinder when charging is
done using the charging cylinder method, causing
bubbles to form in the measurement scale glass and
making it difficult to see the reading. (Naturally, the
conventional R22 charging cylinder cannot be used
because of the differences in the pressure resistance,
scale gradation, connecting port size, etc.)
  • The electronic scale has been strengthened by using a
structure in which the weight detector for the refrigerant
cylinder is held by four supports. It is also equipped with
two connection ports, one for R22 *7/16 UNF, 20
threads) and one for R410A (1/2 UNF, 20 threads), so
it can also be used for conventional refrigerant charging.
  • There are two types of electronic scales, one for 10-kg
cylinders and one for 20-kg cylinders. (The 10-kg
cylinder is recommended.)
Refrigerant charging is done manually by opening and
closing the valve.
 9. Refrigerant cylinders
  • The R410A cylinders are labeled with the refrigerant
name, and the coating color of the cylinder protector is
pink, which is the color stipulated by ARI of the U.S.
  • Cylinder equipped with a siphon tube are available to
allow the cylinder to stand upright for liquid refrigerant
charging.
 10. Charging orifice and packing for refrigerant cylinders
  • The charging orifice must match the size of the charging
hose fitting (1/2 UNF, 20 threads).
  • The packing must also be made of an HFC-resistant
material.
Fig. 7 Electronic scale for refrigerant charging
Fig. 8 Refrigerant cylinders
Fig. 9 Charging orifice and packing
10.2.3.  R410A Tools Which Are Usable for R22 Models
Table 9 R410A tools which are usable for R22 models
R410A tools
Usable for R22 models
(1)
Copper tube gauge for clearance adjustment
OK
(2)
Flaring tool (clutch type)
OK
(3)
Manifold gauge
NG
(4)
Charging hose
NG
(5)
Vacuum pump adaptor
OK
(6)
Electric gas leak detector for HFC refrigerant
NG
(7)
Electronic scale for refrigerant charging
OK
(8)
Refrigerant cylinder
NG
(9)
Charging orifice and packing for refrigerant cylinder
NG
56