8.2.3. Protection Control For Heating Operation
8.2.3.1. 
Anti Cold Draft Control
Indoor fan speed varies in accordance to indoor heat exchanger temperature, based on type of air volume and direction, as shown
below.
 1. Manual Fan Speed
 2. Auto Fan Speed
37
Note:
 a. UP:
  • If move from Lo, the fan speed will be shifted to Maximum 1520 rpm (E21CK), 1480 rpm (E18CK).
  • If move from Maximum, the fan speed no change.
  • In up zone, 10 rpm is added for every 10s until Maximum 1520 rpm (E21CK), 1480 rpm (E18CK).
 b. DOWN:
  •  The fan speed will be decreased one step every 10 sec. until Minimum 1270 rpm.
 c. 
Current Output Fixed:
  • Maintain at present fan speed.
 d. Instantaneous Maximum:
  • Fan speed will be increased to maximum auto fan speed.
 e. Temperature in ( ) is for Powerful Mode operation.
8.2.3.2. Intake Air Temperature Control
Compressor will operate at maximum of 128 Hz respectively if either one of the below conditions occur:
 1. When the indoor intake air temperature is above 10°C and remote control setting fan speed is lower Me-.
 2. When the indoor intake air temperature is 30°C or above.
8.2.3.3. Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the below figures. This
control will begin one minute after the compressor starts.
38
8.2.3.4. Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.
8.2.3.5. Outdoor Temperature Control
  • Outdoor temperature is detected and the following control is perform.
  • Control operates after more than 1 minute the compressor has started.
39
8.2.3.6. Deice Control
A. Deice operation (Normal Deice Operation)
 1. Detection methods
Outdoor heat exchanger temperature sensor, timer.
 2. Deice operation time chart
Notes
 a. During deice operation, the relationship between outdoor pipe temperature and time T1 is such operation will
proceed to next stage.
 b. The deice will be performed only after 1 hour from when the operation has started.
 c. 
When Comp. OFF by the sequence No. 1, 6, 7 compressor can restart back without 3 minutes waits (immediate
restart).
Outdoor heat exchanger temperature
a
15°C
b
18°C
c
25°C
40