ii. Auto Fan Speed
 1. Cooling
 2. Heating
Note:
 a. UP:
  • If move from Lo, the fan speed will be shifted to Maximum 1520 rpm (E21CK), 1480 rpm (E18CK).
  • If move from Maximum, the fan speed no change.
  • In up zone, 10 rpm is added for every 10s until Maximum 1520 rpm (E21CK), 1480 rpm (E18CK).
 b. DOWN:
  •  The fan speed will be decreased one step every 10 sec. until Minimum 1270 rpm.
 c. 
Current Output Fixed:
  • Maintain at present fan speed.
 d. Instantaneous Maximum:
  • Fan speed will be increased to maximum auto fan speed.
 e. Temperature in ( ) is for Powerful Mode operation.
21
iii. Max Capacity Condition
a) During Cooling operation, if all to the following condition is fulfilled, the indoor fan speed is set to Shi.
 1. Indoor intake temperature
24°C.
 2. Operation frequency 72 Hz (E18CK), 95 Hz (E21CK) & above.
 3. Remote Control setting temperature 16°C.
 4. Remote Control setting fan speed Hi.
 5. Outdoor temperature
30°C.
 6. Operation start
within 30 minutes.
* If any of above conditions is not valid, the condition is ended.
b) During Heating operation, if all to the following condition is fulfilled, the indoor fan speed is set to SSHi.
 1. Indoor intake temperature is 17°C or above and less than 23°C.
 2. Operation frequency 86 Hz (E18CK), 93 Hz (E21CK) & above.
 3. Remote Control setting temperature 30°C.
 4. Remote Control setting fan speed Hi.
 5. Outdoor temperature < 4°C.
 6. Operation start
2 hours.
* If any of above conditions is not valid, the condition is ended.
C. Fan Motor Control
i. Motor specification
High voltage PWM Motor
ii. Feedback Control
 1. Rotation speed feedback
Immediately after the fan started, rpm is checked and duty is added, and feedback control is performed.
iii. Abnormal Detection
1. Condition
*
*
Step out signal input
Feedback rotation speed is more than 2550 rpm or below 50 rpm.
However, 10s after fan start, rotation abnormality is not detected.
2. Control
* Fan stop
3. Return
* Restart after 5s
However, in case the fan is stopped by the above conditions within 25s after fan has started, and happened
continuously for 7 times, restart will not be performed.
→ Indoor fan motor lock abnormal (H19)
iv. Restart Prohibition Control
Prohibit to restart within 5s after fan stop.
(except when power is ON)
22
D. Deodorizing Control
i. Control condition
Control at cooling/dry operation and auto fan speed.
No Deodorizing Control is performed during ON timer standby operation and during Anti-freezing control prevention.
ii. Operation
The odor status is arranged as below and it is shifted as follow.
* When COMP is ON
1
→ 2 → 3
(Shift to 4 when COMP is OFF)
* When COMP is OFF
4
→ 5 → 4 ←→ 5
(Shift to 1 when COMP is ON)
* Start from 4 if the Thermostat is OFF during the start operation.
Odor Status
1
2
3
4
5
4
5
4.5.4...
1
Status Shift
according to COMP
ON
OFF
ON
Status Shift
according
Cooling
zone
40
50
20
90
20
90
.......
to time (s)
Dry zone
ON
Fan Speed
Cooling
zone
OFF
SLo
Auto Fan Speed
SLo
OFF
SLo
OFF
.......
Dry zone
OFF
SLo
OFF
8.1.8. Outdoor Fan Motor Operation
Outdoor fan motor is operated with 15 fan speed. It starts when compressor starts operation and it stops 30 seconds after
compressor stops operation.
23
Basic Rotation Speed
8.1.9. Airflow Direction
 1. There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).
 2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature
and intake air temperature) and manual (angles of direction can be adjusted using remote control).
Vertical Airflow
Operation Mode
Airflow Direction
Vane Angle (°)
1
2
3
4
5
Heating
Auto with Heat Exchanger
17
Temperature
58
7
Manual
7
17
33
49
67
Cooling, Soft Dry and Fan, Ion
Auto
7 ~ 37
Manual
7
17
25
33
41
Mode Judgment in Auto
Auto
7
Manual
7
17
25
33
41
24