Applicable piping kit
CZ-4F5, 7, 10AN (E18CK, E21CK)
SELECT THE BEST LOCATION
INDOOR UNIT
  • There should not be any heat source or steam near the
unit.
  • There should not be any obstacles blocking the air
circulation.
  • A place where air circulation in the room is good.
  • A place where drainage can be easily done.
  • A place where noise prevention is taken into
consideration.
  • Do not install the unit near the door way.
  • Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
  • Recommended installation height for indoor unit shall be
at least 2.3 m.
OUTDOOR UNIT
  • If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
  • There should not be any animal or plant which could be
affected by hot air discharged.
  • Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
  • Do not place any obstacles which may cause a short
circuit of the discharged air.
  • If piping length is over 10m, additional refrigerant should
be added as shown in the table.
Indoor/Outdoor Unit Installation Diagram
  • This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
Attached accessories
65
11.2.1. SELECT THE BEST LOCATION
(Refer to “Select the best location”
section)
11.2.2. HOW TO FIX INSTALLATION
PLATE
The mounting wall is strong and solid enough to prevent it from
the vibration.
The centre of installation plate should be at more than 550 mm
at right and left of the wall.
The distance from installation plate edge to ceiling should more
than 67 mm.
From installation plate left edge to unit’s left side is 47 mm.
From installation plate right edge to unit’s right is 73 mm.
:
:
:
For left side piping, piping connection for liquid should be
about 126 mm from this line.
For left side piping, piping connection for gas should be
about 174 mm from this line.
For left side piping, piping connecting cable should be
about 984 mm from this line.
 1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall consider using
anchor bolts.)
  • Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge.
 2. Drill the piping plate hole with ø70 mm hole-core drill.
  • Line according to the arrows marked on the lower left
and right side of the installation plate. The meeting point
of the extended line is the centre of the hole. Another
method is by putting measuring tape at position as
shown in the diagram above. The hole centre is
obtained by measuring the distance namely 150 mm
and 125 mm for left and right hole respectively.
  • Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
11.2.3. TO DRILL A HOLE IN THE WALL
AND INSTALL A SLEEVE OF
PIPING
 1. Insert the piping sleeve to the hole.
 2. Fix the bushing to the sleeve.
 3. Cut the sleeve until it extrudes about 15 mm from the wall.
Caution
When the wall is hollow, please be sure to use the
sleeve for tube ass’y to prevent dangers caused by
mice biting the connecting cable.
 4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
11.2.4. INDOOR UNIT INSTALLATION
 1. For the right rear piping
 2. For the right and right bottom piping
11.2. INDOOR UNIT
66
 3. For the embedded piping
(This can be used for left rear piping & left bottom piping also.)
67
 1. The inside and outside connecting cable can be connected
without removing the front grille.
 2. Connecting cable between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 4 × 2.5 mm
2
(E18CK, E21CK) flexible cord, type designation 245 IEC 57
or heavier cord.
  • Ensure the color of wires of outdoor unit and the
terminal Nos. are the same to the indoor’s respectively.
  • Earth lead wire shall be longer than the other lead wires
as shown in the figure for the electrical safety in case of
the slipping out of the cord from the anchorage.
  • Secure the cable onto the control board with the holder
(clamper).
INSTALLATION OF AIR PURIFYING FILTERS
 a. Open the front panel.
 b. Remove the air filters.
 c. 
Put air purifying filters (left) and triple deodorizing filter
(right) into place as shown in illustration below.
HOW TO TAKE OUT FRONT GRILLE
Please follow the steps below to take out front grille if
necessary such as when servicing.
 a. Open the intake grille and remove the screw at the front
of the front grille.
 b. Set the vertical airflow direction louver to the horizontal
position.
 c. 
Slide down the 3 caps on the front grille as shown in the
illustration below, and then remove the 3 mounting
screws.
 d. Pull the lower section of the front grille towards you to
remove the front grille.
When reinstalling the front grille, first set the vertical
airflow direction louver to the horizontal position and
then carry out above steps 2 - 3 in the reverse order.
11.2.5. CONNECT THE CABLE TO THE INDOOR UNIT