JBL ON BEAT MICRO (serv.man3) EMC - CB Certificate ▷ View online
Issue Date:
2012-10-23
Page 15 of 41
Report Reference #
E204594-A37-CB-1
IEC 60950-1:2005
SubClause Difference + Test
Result - Remark
Verdict
This report issued under the responsibility of UL
5) Safety extra low voltage (SELV or ELV)
6) Residual current circuit breaker (30 ma = 1delta)
7) reinforced insulation; double insulation (Class II)
6) Residual current circuit breaker (30 ma = 1delta)
7) reinforced insulation; double insulation (Class II)
2.201
Add: Prior to carrying out the tests in
accordance with the clauses of this Standard, the
compliance of the apparatus with the relevant
requirements specified in the appropriate part of
the standard series SI 961, shall be checked. The
apparatus shall meet the requirements in the
appropriate part of the standard series SI 961. If
there are components of the apparatus for the
prevention of electromagnetic interference, these
components shall not reduce the safety level of the
apparatus as required by this standard.
N/A
3.2.1.1
Add after the note: The feed plug shall
comply with the requirements of Israel Standard SI
32 Part 1.1.
N/A
3.2.1.2
Add: At the end of the first paragraph add
the following note: At the time of issue of the
standard, there is no Israel Standard for connection
accessories to d.c.
N/A
Korea - Differences to IEC 60950-1:2005 (2nd Edition); Am 1:2009
1.5.101
Plugs for the connection of the apparatus to
the mains supply shall comply with the Korean
requirement (KSC 8305)
N/A
8
EMC - The apparatus shall comply with the
relevant CISPR standards
See Enclosure 7-01
Pass
Issue Date:
2012-10-23
Page 16 of 41
Report Reference #
E204594-A37-CB-1
IEC 60950-1:2005
SubClause Difference + Test
Result - Remark
Verdict
This report issued under the responsibility of UL
Norway - Differences to IEC 60950-1:2005 (2nd Edition); Am 1:2009
1.2.13.14
Requirements according to this annex
1.7.2.1 and 7.3 apply.
N/A
1.5.7.1
Resistors bridging BASIC INSULATION in
CLASS I PLUGGABLE EQUIPMENT TYPE A must
comply with the requirements in 1.5.7.2. In
addition when a single resistor is used, the resistor
must withstand the resistor test in 1.5.7.2.
N/A
1.5.8
Due to the IT power system used (see
annex V, figure V.7), capacitors are required to be
rated for the applicable line-to-line voltage (230 V).
N/A
1.5.9.4
The third dashed sentence is applicable
only to equipment as defined in 6.1.2.2 of this
annex.
Pass
1.7.2.1
CLASS I PLUGGABLE EQUIPMENT TYPE
A intended for connection to other equipment or a
network shall, if safety relies on connection to
protective earth or if surge suppressors are
connected between the network terminals and
accessible parts, have a marking stating that the
equipment must be connected to an earthed mains
socket-outlet. The marking text shall be:
"Apparatet må tilkoples jordet stikkontakt"
N/A
1.7.2.1
In Norway, the screen of the cable
distribution system is normally not earthed at the
entrance of the building and there is normally no
equipotential bonding system within the building.
Therefore the protective earthing of the building
installation need to be isolated from the screen of a
cable distribution system. It is however accepted
to provide the insulation external to the equipment
by an adapter or an interconnection cable with
galvanic isolator, which may be provided by e.g. a
retailer.
N/A
Issue Date:
2012-10-23
Page 17 of 41
Report Reference #
E204594-A37-CB-1
IEC 60950-1:2005
SubClause Difference + Test
Result - Remark
Verdict
This report issued under the responsibility of UL
The user manual shall then have the following or
similar information in Norwegian and Swedish
language respectively, depending on in what
country the equipment is intended to be used in:
"Equipment connected to the protective earthing of
the building installation through the mains
connection or through other equipment with a
connection to protective earthing - and to a cable
distribution system using coaxial cable, may in
some circumstances create a fire hazard.
Connection to a cable distribution system has
therefore to be provided through a device providing
electrical isolation below a certain frequency range
(galvanic isolator, see EN 60728-11)."
NOTE: In Norway, due to regulation for installations
of cable distribution systems, and in Sweden, a
galvanic isolator shall provide electrical insulation
below 5 MHz. The insulation shall withstand a
dielectric strength of 1,5 kV r.m.s., 50 Hz or 60 Hz,
for 1 min.
Translation to Norwegian (the Swedish text will
also be accepted in Norway): “Utstyr som er koplet
til beskyttelsesjord via nettplugg og/eller via annet
jordtilkoplet utstyr - og er tilkoplet et kabel-TV nett,
kan forårsake brannfare. For å unngå dette skal det
ved tilkopling av utstyret til kabel-TV nettet
installeres en galvanisk isolator mellom utstyret og
kabel-TV nettet."
similar information in Norwegian and Swedish
language respectively, depending on in what
country the equipment is intended to be used in:
"Equipment connected to the protective earthing of
the building installation through the mains
connection or through other equipment with a
connection to protective earthing - and to a cable
distribution system using coaxial cable, may in
some circumstances create a fire hazard.
Connection to a cable distribution system has
therefore to be provided through a device providing
electrical isolation below a certain frequency range
(galvanic isolator, see EN 60728-11)."
NOTE: In Norway, due to regulation for installations
of cable distribution systems, and in Sweden, a
galvanic isolator shall provide electrical insulation
below 5 MHz. The insulation shall withstand a
dielectric strength of 1,5 kV r.m.s., 50 Hz or 60 Hz,
for 1 min.
Translation to Norwegian (the Swedish text will
also be accepted in Norway): “Utstyr som er koplet
til beskyttelsesjord via nettplugg og/eller via annet
jordtilkoplet utstyr - og er tilkoplet et kabel-TV nett,
kan forårsake brannfare. For å unngå dette skal det
ved tilkopling av utstyret til kabel-TV nettet
installeres en galvanisk isolator mellom utstyret og
kabel-TV nettet."
2.2.4
Requirements according to this annex,
1.7.2.1, 6.1.2.1 and 6.1.2.2 apply.
Pass
2.3.2
Requirements according to this annex,
6.1.2.1 and 6.1.2.2 apply.
N/A
2.3.4
Requirements according to this annex,
1.7.2.1, 6.1.2.1 and 6.1.2.2 apply.
N/A
2.10.5.13
Requirements according to this annex,
6.1.2.1 and 6.1.2.2 apply.
N/A
Issue Date:
2012-10-23
Page 18 of 41
Report Reference #
E204594-A37-CB-1
IEC 60950-1:2005
SubClause Difference + Test
Result - Remark
Verdict
This report issued under the responsibility of UL
5.1.7.1
TOUCH CURRENT measurement results
exceeding 3,5 mA r.m.s are permitted only for the
following equipment:
- STATIONARY PLUGGABLE EQUIPMENT TYPE
A that:
(1) is intended to be used in a RESTRICTED
ACCESS LOCATION where equipotential bonding
has been applied, for example, in a
telecommunication centre; and
(2) has provision for a permanently connected
PROTECTIVE EARTHING CONDUCTOR; and
(3) is provided with instructions for the installation
of that conductor by a SERVICE PERSON;
- STATIONARY PLUGGABLE EQUIPMENT TYPE
B
- STATIONARY PERMANENTLY CONNECTED
EQUIPMENT
N/A
6.1.2.1
Add the following text between the first and
second paragraph of the compliance clause:
If this insulation is solid, including insulation
forming part of a component, it shall at least consist
of either
- two layers of thin sheet material, each of which
shall pass the electric strength test below, or
- one layer having a distance through insulation of
at least 0,4 mm, which shall pass the electric
strength test below.
Alternatively for components, there is no distance
through insulation requirement for the insulation
consisting of an insulating compound completely
filling the casing, so that CLEARANCES and
CREEPAGE DISTANCES do not exist, if the
component passes the electric strength test in
accordance with the compliance clause below and
in addition
- passes the tests and inspection criteria of 2.10.11
with an electric strength test of 1,5 kV multiplied by
1,6 (the electric strength test of 2.10.10 shall be
performed using 1,5 kV), and
- is subject to ROUTINE TESTING for electric
strength during manufacturing, using a test voltage
of 1,5 kV.
N/A
Click on the first or last page to see other ON BEAT MICRO (serv.man3) service manuals if exist.