DOWNLOAD Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 Service Manual ↓ Size: 7.25 MB | Pages: 127 in PDF or view online for FREE

Model
U-4LE1E5 U-4LE1E8 U-5LE1E5 U-5LE1E8 U-6LE1E5 U-6LE1E8
Pages
127
Size
7.25 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / MINI VRF SYSTEM
File
u-4le1e5-u-4le1e8-u-5le1e5-u-5le1e8-u-6le1e5-u-6le.pdf
Date

Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 Service Manual ▷ View online

Mini VRF SYSTEM
Remote Controller Functions
2
2-15
3. Detailed Settings Function
Item code
Item
Setting data
No.
Description
Fan tap setting 
(Fan tap change in order 
to prevent drop in air 
discharge caused by 
fi lter installation)
DC fan tap operating 
mode
Purpose
0000
Standard
Standard (setting at shipment)
0001
High ceiling use
High ceiling setting 1 (with standard panel)
For low
static-pressure fi lter
Ultra long-life fi lter, oil guard panel, ammonia deodorizing 
fi lter, optical regenerative deodorizing fi lter
0003
High ceiling use
High ceiling setting 2 (with standard panel)
For low 
static-pressure fi lter
(Antibacterial) high-performance fi lter (90%) 
(Antibacterial) high-performance fi lter (65%) 
Air-cleaning unit, air-cleaning unit + optical regenerative 
deodorizing fi lter, deodorant (activated charcoal) fi lter
For air-blocking 
material
For 3-way discharge, when discharge duct is connected
0006
For air-blocking 
material
For 2-way discharge
Humidifi er ON time 
(ON time per 60 
seconds)
0000
No humidifi er output
0001
1 second
0002
2 seconds
0058
58 seconds
0059
59 seconds
0060
Continuously ON
Timer function change 
prohibit
0000
Function disabled
0001
Function enabled
Smudging control
0000
No smudging control
Setting the Flap 
Separately
*Only for 4-way
Cassette type
0000
0001
0002
0003
0004
0005
0006
Setting the Flap 
Separately
*Only for 4-way
Cassette type
Setting the Flap 
Separately
*Only for 4-way
Cassette type
Setting the Flap 
Separately
*Only for 4-way
Cassette type
=91
=90
Flap 1
(Motor No. 4)
(Motor No. 1)
(Motor No. 2)
(Motor No. 3)
Flap 3
Flap 2
Flap 4
=92
=93
Electrical 
component 
box
Flap position
1
2
3
4
5
Flap position during operation
Setting data
Move to position  1  and stay
Without separate setting
Swing
Move to position  2  and stay
Move to position  3  and stay
Move to position  4  and stay
Move to position  5  and stay
When the flap position is set to 
 4  or  5  and the unit is in the 
cooling or dry mode, the flap 
position is moved to  3  and the 
operation is started.
The flap swings during the 
operation under "Setting the 
Flap Separately".
At this time, the unselected flaps 
are moved to the position  1 . 
NOTE
Air discharge 
port
Flap 
(adjustment for 
up-down 
airflow direction)
SM830196-03_Mini_VRF SYS.indb   15
SM830196-03_Mini_VRF SYS.indb   15
2014/09/08   13:08:53
2014/09/08   13:08:53
Mini VRF SYSTEM
Remote Controller Functions
2
2-16
3. Detailed Settings Function
Item code
Item
Description
10
Unit type
Set when the indoor unit EEPROM memory is replaced during servicing.
11
Indoor unit capacity
12
System (outdoor unit) 
address
These are not set at the time of shipping from the factory.
These must be set after installation if automatic address setting is not 
performed.
13
Indoor unit address
14
Group address
17
Cooling intake temperature 
shift
Shifts the intake temperature during cooling and dry operation.
(Enabled only when the body thermostat is used.) 
Increase this value when it is diffi cult to turn the thermostat ON.
18
Automatic stop time after 
operation start
The time at which an indoor unit is automatically stopped after operation starts 
can be set in increments of 5 minutes.
1E
Temperature shift for 
cooling/heating change in 
“auto heat/cool” mode
“Auto heat/cool” selects the operating mode automatically based on the 
difference between the room temperature and the temperature set on the 
remote controller. This setting establishes a shift temperature for the heating/
cooling temperature setting relative to the remote controller temperature 
setting.
Cooling temperature setting
Remote controller temperature setting
Heating temperature setting
Shift temperature
(+)
Shift temperature
(–)
SM830196-03_Mini_VRF SYS.indb   16
SM830196-03_Mini_VRF SYS.indb   16
2014/09/08   13:08:53
2014/09/08   13:08:53
Mini VRF SYSTEM
Remote Controller Functions
2
2-17
3. Detailed Settings Function
Description
Item
Item code
1F (Upper limit)
20 (Lower limit)
Change to the remote 
control temperature 
setting range
Cooling
This setting changes the temperature range (upper limit and lower 
limit) which is set from the remote controller or central control device. 
The set upper limit must be greater than or equal to the lower limit. 
If the temperature setting is to be a single point, set the upper limit 
and lower limit to the same temperature.
21 (Upper limit)
22 (Lower limit)
Heating
23 (Upper limit)
24 (Lower limit)
Drying
25 (Upper limit)
26 (Lower limit)
Auto
heat/cool
29
Humidifier operation which ignores 
the heat exchanger temperature
During heating operation, the humidifier operates when the heat 
exchanger temperature is suitable for humidifying. This setting is 
used to ignore this condition for humidifier operation and operate the 
humidifier more.
2A
Filter input switching
This setting switches the filter input according to the purpose of use.
2C
Indoor unit electronic control valve
This setting indicates whether or not an indoor unit electronic control 
valve is present.
At the time of shipping, this setting is set according to the conditions 
of the indoor unit.
2E
T10 terminal input switching
Ordinarily, the T10 terminal is used as the HA terminal at the time of 
shipping. However, this setting is used when the T10 terminal is used 
for OFF reminder or for fire prevention input.
31
Ventilation fan operation from 
remote controller
It is possible to install a total heat exchanger and ventilation fan in 
the system, which can be started and stopped by the wired remote 
controller. The ventilation fan can operate linked with the start and 
stop of the indoor unit, or can be operated even when the indoor 
unit is stopped.
Use a ventilation fan that can accept the no-voltage A contact as 
the external input signal.
In the case of group control, the fans are operated together. They 
cannot be operated individually.
32
Switching to remote controller
sensor
This setting is used to switch from the body sensor to the remote 
controller sensor.
Check that “remote controller sensor” is displayed.
Do not use this setting with models that do not include a remote 
controller sensor.
Do not use this setting if both the body sensor and remote sensor 
are used.
34
ON/OFF of “Operation change 
control in progress” display
In a MULTI system with multiple remote controllers, switching 
between heating and cooling is restricted, and “Operation change 
control in progress” is displayed.
This setting is used to prevent this display from appearing.
Refer to the item concerned with operating mode priorities.
(Continued)
28
Auto restart setting
When indoor unit is shutdown due to power failure, auto restart 
setting can restore the previous operating system.
SM830196-03_Mini_VRF SYS.indb   17
SM830196-03_Mini_VRF SYS.indb   17
2014/09/08   13:08:53
2014/09/08   13:08:53
Mini VRF SYSTEM
Remote Controller Functions
2
2-18
3. Detailed Settings Function
(Continued from previous page)
Item code
Item
Description
3C
Heat exchanger temperature for 
cold air discharge
The heat exchanger temperature control point for prevention of cold air 
discharge during heating operation can be changed.
3d
Fan output switching
The indoor unit PCB optional output for the fan can be switched 
according to the purpose of use.
3E
Drain pump delayed start time
The drain pump starts after the set time delay after cooling operation 
stops.
40
Humidifi er drain pump setting
This specifi es the humidifi er and drain pump setting.
45
DC fl ap operation mode
Changes fl ap operation to draft reduction mode.
46
DC fl ap swing mode
Selects the swing operation mode for the fl ap.
5d
DC fan tap setting
Sets the DC fan tap according to the purpose of use.
Change the settings data at the same time.
5E
Humidifi er ON time
Sets the humidifi er output ON time for when the humidifi er is operating.
ON/OFF control is performed during humidifi er operation.
This setting therefore sets the ON time per 60-second interval.
60
Timer function change prohibit
This function prohibits changes from being made to the remote 
controller time setting.
62
Smudging control
Smudging control is disabled when 0000 is set.
SM830196-03_Mini_VRF SYS.indb   18
SM830196-03_Mini_VRF SYS.indb   18
2014/09/08   13:08:53
2014/09/08   13:08:53
Page of 127
Display