DOWNLOAD Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 Service Manual ↓ Size: 7.25 MB | Pages: 127 in PDF or view online for FREE

Model
U-4LE1E5 U-4LE1E8 U-5LE1E5 U-5LE1E8 U-6LE1E5 U-6LE1E8
Pages
127
Size
7.25 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / MINI VRF SYSTEM
File
u-4le1e5-u-4le1e8-u-5le1e5-u-5le1e8-u-6le1e5-u-6le.pdf
Date

Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 Service Manual ▷ View online

Mini VRF SYSTEM
Remote Controller Functions
2
2-3
2. Simple Settings Function
• 
This allows the filter lifetime, operating mode prior-
ity change, central control address, and other set-
tings to be made for an individual or group-control 
indoor unit to which the remote controller used for 
simple settings is connected.
When simple settings mode is engaged, operation 
stops at the individual or group-control indoor unit 
to which the remote controller for simple settings is 
connected.
<Procedure of CZ-RTC2>
À  
Press and hold the 
 and 
 buttons 
simultaneously for 4 seconds or longer.
Á  
“ 
 ” unit No. “ 
 ” (or “ 
 ” in the case of 
group control), item code “ 
 ,” and settings data 
“ 
 ” are displayed blinking on the remote 
controller LCD display (Fig. 2-1). At this time, the 
indoor unit fan (or all indoor unit fans in the case of 
group control) begins operating.
Â
   If group control is in effect, press the 
 
button and select the address (unit No.) of the 
indoor unit to set. At this time, the fan at the indoor 
unit begins operating.
*  If unit No. “ 
 ” is displayed, the same setting 
will be made for all indoor units.
à  
Press the temperature setting 
 / 
 
buttons to select the item code to change.
Ä  
Press the timer time 
 / 
 buttons to select the 
desired setting data.
*  For item codes and setting data, refer to the 
following page.
Å  
Press the 
 button. (The display stops blinking 
and remains lit, and setting is completed.)
Æ  
Press the 
 button to return to normal remote 
controller display.
Fig. 2-1
3
CZ-RTC2
4
6
5
1
7
2
[Remote Controller Functions Section]
SM830196-03_Mini_VRF SYS.indb   3
SM830196-03_Mini_VRF SYS.indb   3
2014/09/08   13:08:49
2014/09/08   13:08:49
Mini VRF SYSTEM
Remote Controller Functions
2
2-4
2. Simple Settings Function
1
 Keep pressing the 
 and 
 
buttons
 simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the 
LCD display.
2
 Press the 
 or 
 button to see each 
menu.
If you wish to see the next screen instantly, press 
the 
 or 
 button.
Select “7. Simple settings” on the LCD display and 
press the 
 button.
The “Simple settings” screen appears on the LCD 
display.
Select the “Unit no.” by pressing the 
 or 
 button for changes.
Simple settings
Unit no.
Code no.
Set data
3-1
20:30 (THU)
01
0002
Sel       [
] Confirm
3
 Select the “Code no.” by pressing the 
 or 
 button.
Change the “Code no.” by pressing the 
 or 
 button.
4
 Select the “Set data” by pressing the 
 or 
 button.
Select one of the “Set data” by pressing the 
 
or 
 button.
Then press the 
 button.
5
 Select the “Unit no.” by pressing the 
 or 
 button and press the 
 button.
The “Exit simple settings and restart?” (Simple 
setting-end) screen appears on the LCD display.
Select “YES” and press the 
 button.
<Procedure of CZ-RTC3>
Fig. 2-2
CZ-RTC3
START
[
]
20:30 (THU)
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel.
Page [
] Confirm
20:30 (THU)
7. Simple settings
Simple settings
Unit no.
Code no.
Set data
01
3-1
0001
Sel.
Next
20:30 (THU)
Simple settings
Unit no.
Code no.
Set data
3-1
0001
Sel.
Next
20:30 (THU)
01
Simple settings
Unit no.
Code no.
Set data
ALL
Sel.
Next
20:30 (THU)
01
0002
Exit simple settings
and restart?
NO
YES
SM830196-03_Mini_VRF SYS.indb   4
SM830196-03_Mini_VRF SYS.indb   4
2014/09/08   13:08:50
2014/09/08   13:08:50
Mini VRF SYSTEM
Remote Controller Functions
2
2-5
2. Simple Settings Function
List of Simple Setting Items
Item code
Item
Setting data
No.
Description
Filter sign ON time 
(fi lter life time)
0000
Not displayed
0001
150 hours
0002
2,500 hours
0003
5,000 hours
0004
10,000 hours
0005
Use the fi lter clogging sensor.
Degree of fi lter fouling
0000
Standard (setting at time of shipping)
0001
Highly fouled
(Filter sign ON time is reduced to one-half the set time.)
Central control 
address
0001
Central control address 1
0002
Central control address 2
0003
Central control address 3
0064
Central control address 64
0099
No central control address set (setting at time of shipping)
Operating mode 
priority change
0000
Normal (setting at time of shipping)
0001
Priority
Fan speed when 
heating thermostat is 
OFF
Compressor ON
Compressor OFF
0000
Lo 1 min., LL 3 min.
LL
0001
Lo
LL
0002
LL
LL
0004
Lo 1 min., LL 3 min.
Lo
0005
Lo
Lo
0006
LL
Lo
Heating intake 
temperature shift
0000
No shift
0001
Shifts intake temperature 1°C down.
0002
Shifts intake temperature 2°C down.
0003
Shifts intake temperature 3°C down.
0004
Shifts intake temperature 4°C down.
0005
Shifts intake temperature 5°C down.
0006
Shifts intake temperature 6°C down.
Electric heater 
installation
0000
No heater
0001
Heater installed
Humidifying when 
heater thermostat is 
OFF
0000
No (setting at time of shipping)
0001
Yes
Permit/prohibit 
automatic 
heating/cooling
0000
Permit
0001
Prohibit
Cool-only
0000
Normal
0001
Cool only (Set “1” for item code OD.)
NOTE
•  In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFF unless a 
vaporizing humidifier is used. 
•  Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
•  Do not change any setting data that does not appear in this list. 
SM830196-03_Mini_VRF SYS.indb   5
SM830196-03_Mini_VRF SYS.indb   5
2014/09/08   13:08:50
2014/09/08   13:08:50
Mini VRF SYSTEM
Remote Controller Functions
2
2-6
2. Simple Settings Function
Simple setting items
Item code
Item
Description
01
Filter sign ON time setting 
(fi lter lifetime)
Changes the indoor unit fi lter lifetime when a high-performance fi lter or other 
optional product is installed.
02
Degree of fi lter fouling
Reduces the fi lter sign ON time to 1/2 of the standard time (setting at the time of 
shipping) for cases when fi lter fouling is more severe than normal.
Filter sign ON times for each model
Model 
data
Model
Filter sign ON time
Standard
Long-life
Standard
High fouling
Standard
High fouling
0001
4-Way cassette (U1)
4-Way cassette 60×60 (Y1, Y2)
×
×
2500
1250
0002 2-Way cassette (L1)
×
×
2500
1250
0003 1-Way cassette (D1)
×
×
2500
1250
0005
Low Silhouette Ducted (F1, F2)
Slim Low Static Ducted (M1)
×
×
×
×
0006 High Static Pressure Ducted (E1)
×
×
×
×
0007 Ceiling (T1)
×
×
2500
750
0008 Wall Mounted (K1, K2)
150
75
×
×
0010 Floor Standing (P1)
150
75
×
×
0011 Concealed Floor Standing (R1)
150
75
×
×
Unit: hour
NOTE
• 
×
 
indicates that there is no corresponding filter.
• 
150
 indicates the filter sign ON time that is set at shipment.
•  High fouling: Set when 
 is selected for the degree of filter fouling (item code 
).
SM830196-03_Mini_VRF SYS.indb   6
SM830196-03_Mini_VRF SYS.indb   6
2014/09/08   13:08:50
2014/09/08   13:08:50
Page of 127
Display

Click on the first or last page to see other U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 service manuals if exist.