DOWNLOAD Panasonic CS-Z20TKEW / CS-Z25TKEW / CS-Z35TKEW / CS-Z42TKEW / CS-Z50TKEW / CS-Z71TKEW / CS-XZ20TKEW / CS-XZ25TKEW / CS-XZ35TKEW / CS-XZ50TKEW / CU-Z20TKE / CU-Z25TKE / CU- / 35TKE / CU-Z42TKE / CU-Z50TKE / CU-Z71TKE / CU-Z20TKE / CU-Z25TKE / CU-Z35TKE / CU-Z50TKE Service Manual ↓ Size: 33.93 MB | Pages: 127 in PDF or view online for FREE

Model
CS-Z20TKEW CS-Z25TKEW CS-Z35TKEW CS-Z42TKEW CS-Z50TKEW CS-Z71TKEW CS-XZ20TKEW CS-XZ25TKEW CS-XZ35TKEW CS-XZ50TKEW CU-Z20TKE CU-Z25TKE CU- 35TKE CU-Z42TKE CU-Z50TKE CU-Z71TKE CU-Z20TKE CU-Z25TKE CU-Z35TKE CU-Z50TKE
Pages
127
Size
33.93 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-z20tkew-cs-z25tkew-cs-z35tkew-cs-z42tkew-cs-z50.pdf
Date

Panasonic CS-Z20TKEW / CS-Z25TKEW / CS-Z35TKEW / CS-Z42TKEW / CS-Z50TKEW / CS-Z71TKEW / CS-XZ20TKEW / CS-XZ25TKEW / CS-XZ35TKEW / CS-XZ50TKEW / CU-Z20TKE / CU-Z25TKE / CU- / 35TKE / CU-Z42TKE / CU-Z50TKE / CU-Z71TKE / CU-Z20TKE / CU-Z25TKE / CU-Z35TKE / CU-Z50TKE Service Manual ▷ View online

97 
14.14.2.2 Judge Sunlight Intensity 
  Based on sunlight sensor output voltage, the sunlight intensity value will be computed and logged to sunlight 
intensity database. 
  The sunlight sensor sensitivity could be adjusted: 
 
SET
Press & release
Press to choose No.2
Sensitivity Level 1: Less sensitive to sunlight intensity
Sensitivity Level 3: Default sensitive level
Sensitivity Level 5: More sensitive to sunlight intensity
Default: (Battery insert)
Set to Level. 3
Other than default
Display last set data
Transmit
solar radiation
level
&
after *30 secs
go back to
normal mode
Set to Level. 4
Press
Timer
Set to Level. 5
Set to Level. 1
Set to Level. 2
Remote control normal mode
 
 
14.14.2.3  Judge Ambient Condition 
  According to sunlight intensity over a period of time, the system will analyze the ambient condition is sunny, 
cloudy or night. 
14.14.2.4 Temperature 
Shift 
 
 
Set
temperature
HEAT
COOL/DRY
+1.0 °C
-1.0 °C
-1.0 °C
ECONAVI 
; Detecting sunlight intensity, the unit adjust temperature to save energy.
Ambient condition
Mode
Sunny
Sunny
Night/Cloudy
 
 
  In a room without window or with thick curtain, the sunlight sensor will judge as cloudy/night. 
 
 
 
 
98 
14.14.2.5 Sunlight Sensor Check Mode 
  To enable sunlight sensor check mode, during unit is OFF (power standby): 
 
SET
Transmit ECO demo code and
after 30 seconds return to normal
mode.
Press continously for 5s
Transmit check code
and after 30 seconds return to normal
mode.
Transmit sunlight sensor check code
and after 30 seconds return to normal
mode.
Remote control normal mode
 
 
 Operation 
details 
o  The sunlight sensor check mode will be operated for 5 minutes. 
o  During check mode, the ON and OFF timer will be memorized but it operation be ignored. 
o  During check mode, if the sunlight sensor check code is retransmitted, the 5 minutes counter will be reset. 
o  During check mode, if sunlight sensor detected the sunlight intensity value above minimum level, the 
ECONAVI indicator turns ON. Else if sunlight sensor detected sunlight intensity value below minimum level, 
the ECONAVI indicator is OFF. 
  To disable sunlight sensor check mode 
o  After check mode is ended (5 minutes counter elapsed), press AUTO OFF/ON button at indoor unit. 
o  If the sunlight sensor detected sunlight intensity is at abnormal range, the check mode will be ended. 
Please check for error code. 
14.14.2.6  Sunlight Sensor Abnormality 
 Abnormality 
detection: 
o  When ECONAVI is ON, if the sunlight intensity value below minimum level continuously for 24 hours, the 
sunlight sensor disconnection error counter will increase by 1 time. If the ECONAVI is OFF, the 24 hours 
timer will be reset, but the sunlight sensor disconnection error counter will not be reset. 
  Error Code judgment 
o  When sunlight sensor disconnection error counter reached 15 times. H70 occurred. 
o  No TIMER indicator or ECONAVI indicator blink. 
  When error code happened, the unit is able to operate without sunlight sensor. 
 
 
 
 
 
 
 
 
 
 
99 
15.  Operation Control (For Multi Split Connection) 
During multi split connection, indoor unit’s operation controls are same with single split connection unless specified in 
this chapter. 
15.1 Cooling 
operation 
15.1.1 Thermostat 
control 
  Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting 
temperature < -2.0°C. 
  Capability resume supply to indoor unit after waiting for 3 minutes, if the Intake Air temperature — Internal setting 
temperature > Capability supply OFF point. 
 
15.2  Soft Dry Operation 
15.2.1 Thermostat 
control 
  Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting 
temperature < -3.0°C. 
  Capability resume to indoor unit after waiting for 3 minutes, if the Intake Air temperature — Internal setting 
temperature > Capability supply OFF point. 
 
15.3 Heating 
Operation 
15.3.1 Thermostat 
control 
  Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting 
temperature > +1.0°C. 
  During this condition, the indoor fan is stopped if compressor is ON. 
  Capability resume supply to indoor unit after waiting for 3 minutes, if the Intake Air Temperature — Internal 
setting temperature < Capability supply OFF point. 
 
15.3.2  Temperature Sampling Control 
  Temperature sampling is controlled by outdoor unit where room temperature for all power supply ON indoor unit 
could be obtained. 
  When capability supply to the indoor unit is OFF and the compressor is ON, the indoor fan motor is stopped. 
During this condition, 15 seconds after sampling signal from outdoor unit is received, the indoor fan start 
operation at low fan speed. 
  However, within first 4 minutes of capability stopped supply to the indoor unit, even sampling signal is received, 
the sampling control is cancelled. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
100 
15.4 Automatic 
Operation 
  This mode can be set using remote control and the operation is decided by remote control setting temperature, 
remote control operation mode, indoor intake and outdoor air temperature. 
  During operation mode judgment, indoor fan motor (with speed of -Lo) and outdoor fan motor are running for 
30 seconds to detect the indoor intake and outdoor air temperature. The operation mode is decided based on 
below chart. 
 
 
  Every 180 minutes, the indoor and outdoor temperature is judge. Based on remote control setting temperature, 
the value of T1 will increase up to 10°C, T2 will decrease by 3°C and T3 will decrease up to 8°C. 
15.5  Indoor Fan Motor Operation 
15.5.1  Residual Heat Removal Control 
  To prevent high pressure at indoor unit, when heating mode thermostat-off condition or power supply OFF, 
indoor fan continue to operate at controlled fan speed for maximum 30 seconds then stop. 
15.6 Powerful 
Mode 
Operation 
  When the power mode is selected, the internal setting temperature will shift lower up to 4.0°C for Cooling/Soft 
Dry or higher up to 6.0°C for heating than remote control setting temperature, the powerful operation continue 
until user cancel the Powerful operation by pressing powerful button again. 
15.7 Auto 
Restart 
Control 
  When the power supply is cut off during the operation of air conditioner, the compressor will re-operate between 
three to four minutes (10 patterns to be selected randomly) after power resume. 
  During multi split connection, Indoor unit will resume previous mode, include unit standby mode. 
15.8 Indication 
Panel 
 
LED POWER  TIMER  nanoe 
ECONAVI 
Color White 
White  White White 
Light ON 
Operation ON 
Timer Setting ON
nanoe ON 
ECONAVI ON 
Light OFF 
Operation OFF  Timer Setting OFF
nanoe OFF  ECONAVI OFF 
 
Note: 
  If POWER LED is blinking (0.5 seconds ON, 0.5 second OFF), the possible operation of the unit are during 
Indoor Residual Heat Removal, Hot Start, during Deice operation, operation mode judgment, or ON timer 
sampling. 
  If POWER LED is blinking (2.5 seconds ON, 0.5 second OFF), the unit is in standby mode. 
  If TIMER LED is blinking, there is an abnormality operation occurs. 
15.9  Mild Dry Cooling Operation 
  During multi split connection, Mild Dry Cooling Operation is disabled. 
Page of 127
Display

Click on the first or last page to see other CS-Z20TKEW / CS-Z25TKEW / CS-Z35TKEW / CS-Z42TKEW / CS-Z50TKEW / CS-Z71TKEW / CS-XZ20TKEW / CS-XZ25TKEW / CS-XZ35TKEW / CS-XZ50TKEW / CU-Z20TKE / CU-Z25TKE / CU- / 35TKE / CU-Z42TKE / CU-Z50TKE / CU-Z71TKE / CU-Z20TKE / CU-Z25TKE / CU-Z35TKE / CU-Z50TKE service manuals if exist.