DOWNLOAD Panasonic CS-Z20TKEW / CS-Z25TKEW / CS-Z35TKEW / CS-Z42TKEW / CS-Z50TKEW / CS-Z71TKEW / CS-XZ20TKEW / CS-XZ25TKEW / CS-XZ35TKEW / CS-XZ50TKEW / CU-Z20TKE / CU-Z25TKE / CU- / 35TKE / CU-Z42TKE / CU-Z50TKE / CU-Z71TKE / CU-Z20TKE / CU-Z25TKE / CU-Z35TKE / CU-Z50TKE Service Manual ↓ Size: 33.93 MB | Pages: 127 in PDF or view online for FREE

Model
CS-Z20TKEW CS-Z25TKEW CS-Z35TKEW CS-Z42TKEW CS-Z50TKEW CS-Z71TKEW CS-XZ20TKEW CS-XZ25TKEW CS-XZ35TKEW CS-XZ50TKEW CU-Z20TKE CU-Z25TKE CU- 35TKE CU-Z42TKE CU-Z50TKE CU-Z71TKE CU-Z20TKE CU-Z25TKE CU-Z35TKE CU-Z50TKE
Pages
127
Size
33.93 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-z20tkew-cs-z25tkew-cs-z35tkew-cs-z42tkew-cs-z50.pdf
Date

Panasonic CS-Z20TKEW / CS-Z25TKEW / CS-Z35TKEW / CS-Z42TKEW / CS-Z50TKEW / CS-Z71TKEW / CS-XZ20TKEW / CS-XZ25TKEW / CS-XZ35TKEW / CS-XZ50TKEW / CU-Z20TKE / CU-Z25TKE / CU- / 35TKE / CU-Z42TKE / CU-Z50TKE / CU-Z71TKE / CU-Z20TKE / CU-Z25TKE / CU-Z35TKE / CU-Z50TKE Service Manual ▷ View online

101 
16. Protection 
Control 
16.1  Protection Control for All Operations 
16.1.1 Restart 
Control 
(Time Delay Safety Control) 
  The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on 
again by pressing OFF/ON button at remote control within this period. 
  This control is not applicable if the power supply is cut off and on again. 
  This phenomenon is to balance the pressure inside the refrigerant cycle. 
 
16.1.2  Total Running Current 
1  When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor 
operation will be decreased. 
2  If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased. 
3  However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 
3 minutes.  
 
Model Z20TKE 
Z25TKE 
Z35TKE Z42TKE Z50TKE Z71TKE 
Operation Mode 
X (A) 
Y (A) 
X (A) 
Y (A) 
X (A) 
Y (A) 
X (A) 
Y (A) 
X (A) 
Y (A) 
X (A) 
Y (A) 
Cooling / Soft Dry (A) 
3.69 
14.98 
4.89 
14.66 
6.16 
14.66 
8.09 
15.02 
11.41 
14.66 
15.48 
19.01 
Cooling / Soft Dry (B) 
3.24 
4.34 
5.70 
7.57 
10.95 
14.57 
Cooling / Soft Dry (C) 
3.24 
4.34 
5.70 
7.57 
10.95 
14.57 
Heating 
3.86 5.34 7.15 8.31 10.59 
11.50 
 
4  The first 30 minutes of cooling operation, (A) will be applied. 
 
 
 
16.1.3  IPM (Power transistor) Prevention Control 
  Overheating Prevention Control 
1  When the IPM temperature rises to 120°C, compressor operation will stop immediately. 
2  Compressor operation restarts after 3 minutes the temperature decreases to 110°C. 
3  If this condition repeats continuously 4 times within 20 minutes, timer LED will be blinking (“F96” is indicated). 
 
  DC Peak Current Control 
1  When electric current to IPM exceeds set value of 16.0 ± 2.0A (Z20/25/35/42TK) and 30.0 ± 3.0A (Z50/71TK), 
the compressor will stop operate. Then, operation will restart after 3 minutes. 
2  If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will 
restart after 1 minute. 
3  If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after 
1 minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off, timer 
LED will be blinking (“F99” is indicated). 
 
16.1.4 Compressor 
Overheating Prevention Control 
  Instructed frequency for compressor operation will be regulated by compressor temperature. The changes of 
frequency are as below. 
  If compressor temperature exceeds 103°C, compressor will be stopped, occurs 4 times per 20 minutes, timer 
LED will be blinking. (“F97” is indicated.) 
 
102 
Compressor = OFF
Compressor Frequency
Reduce
Compressor Frequency
Maintain
Free
Comp. temperature
103°C
99°C
96°C
88°C
87°C
86°C
 
 
16.1.5  Low Pressure Prevention Control (Gas Leakage Detection) 
  Control start conditions 
o  For 5 minutes, the compressor continuously operates and outdoor total current is between 0.75A and 0.95A 
(Z20/25/35/42TK), 1.38A and 1.65A (Z50/71TK). 
o  During Cooling and Soft Dry operations: 
Indoor suction temperature - indoor piping temperature is below 4°C. 
o  During Heating operations : 
Indoor piping temperature - indoor suction is under 5°C. 
 Control 
contents 
o  Compressor stops (and restart after 3 minutes). 
o  If the conditions above happen 2 times within 20 minutes, the unit will: 
 Stop 
operation 
  Timer LED blinks and “F91” indicated. 
 
16.1.6 Low 
Frequency 
Protection Control 1 
  When the compressor operate at frequency lower than 24 Hz continued for 20 minutes, the operation frequency 
will be changed to 23 Hz for 2 minutes. 
 
16.1.7 Low 
Frequency 
Protection Control 2 
  When all the below conditions comply, the compressor frequency will change to lower frequency. 
 
Temperature, T, for: 
Cooling/Soft Dry 
Heating 
 Indoor intake air (°C) 
T < 14 or T ≥ 30 
T < 14 or T ≥ 28 
 Outdoor air (°C) 
T < 13 or T ≥ 38 
T < 4 or T ≥ 24 
 Indoor heat exchanger (°C) 
T < 30 
T ≥ 0 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
103 
16.2 
Protection Control for Cooling & Soft Dry Operation 
16.2.1  Outdoor Air Temperature Control 
  The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the 
diagram below. 
  This control will begin 1 minute after the compressor starts. 
 Compressor 
frequency will adjust base on outdoor air temperature. 
 
 
 
  The compressor will be stopped to avoid compressor overloading. 
 
-10°C
-12°C
COMP. ON
COMP. OFF
Outdoor
Air
Temperature
 
 
16.2.2  Cooling Overload Control 
  Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation 
frequency). 
  The compressor stop if outdoor pipe temperature exceeds 60°C. 
  If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95 indicated: outdoor high pressure rise 
protection). 
16.2.3  Freeze Prevention Control 1 
  When indoor heat exchanger temperature is lower than 0°C continuously for 6 minutes, compressor will stop 
operating. 
  Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 5°C. 
  At the same time, indoor fan speed will be higher than during its normal operation. 
  If indoor heat exchanger temperature is higher than 5°C for 5 minutes, the fan speed will return to its normal 
operation. 
16.2.4  Freeze Prevention Control 2 
  Control start conditions 
o  During Cooling operation and soft dry operation 
  During thermo OFF condition, indoor intake temperature is less than 10°C or  
  Compressor stops for freeze prevention control 
o  Either one of the conditions above occurs 5 times in 60 minutes. 
 Control 
contents 
o Operation 
stops 
o  Timer LED blinks and “H99” indicated 
 
 
 
104 
16.2.5  Dew Prevention Control 1 
  To prevent dew formation at indoor unit discharge area. 
  This control will be activated if: 
o  Outdoor air temperature and Indoor pipe temperature judgment by microcontroller is fulfilled. 
o  When Cooling or Dry mode is operated more than 20 minutes or more. 
  This control stopped if: 
o Compressor 
stopped. 
o  Remote control setting changed (fan speed / temperature). 
o  Outdoor air temperature and indoor intake temperature changed. 
  Fan speed will be adjusted accordingly in this control. 
16.2.6 Odor 
Cut 
Control 
  To reduce the odor released from the unit.  
o Start 
Condition 
  AUTO FAN Speed is selected during COOL or DRY operation. 
  During freeze prevention control and timer preliminary operation, this control is not applicable. 
o Control 
content 
  Depends on compressor conditions: 
1. Compressor 
OFF 
 Compressor ON. 
The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds. 
2. Compressor 
ON 
 Compressor OFF. 
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds. 
16.3  Protection Control for Heating Operation 
16.3.1  Intake Air Temperature Control 
Compressor will operate at limited freq., if indoor intake air temperature is 30°C or above. 
 
16.3.2  Outdoor Air Temperature Control 
  The Max current value is regulated when the outdoor air temperature rise above 14°C in order to avoid 
compressor overloading. 
 
 
 
16.3.3  Overload Protection Control 
  The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown 
below. 
  If the heat exchanger temperature exceeds 60°C, compressor will stop. 
 
 
 
 
Page of 127
Display

Click on the first or last page to see other CS-Z20TKEW / CS-Z25TKEW / CS-Z35TKEW / CS-Z42TKEW / CS-Z50TKEW / CS-Z71TKEW / CS-XZ20TKEW / CS-XZ25TKEW / CS-XZ35TKEW / CS-XZ50TKEW / CU-Z20TKE / CU-Z25TKE / CU- / 35TKE / CU-Z42TKE / CU-Z50TKE / CU-Z71TKE / CU-Z20TKE / CU-Z25TKE / CU-Z35TKE / CU-Z50TKE service manuals if exist.