14.11 Indication Panel
LED POWER TIMER nanoe
ECONAVI
Color White White White White
Light ON
Operation ON Timer Setting ON nanoe ON
ECONAVI ON
Light OFF
Operation OFF Timer Setting OFF nanoe OFF ECONAVI OFF
Note:
If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation
mode judgment, or ON timer sampling.
If Timer LED is blinking, there is an abnormality operation occurs.
14.12 nanoe Operation
This operation provides clean air by producing great amount of negative ions and distribute through the
discharge airflow to capture or deactivate molds, bacteria or viruses.
Generate nanoe (water wrapped ion particle) to moisturize skin.
nanoe operation start condition
o During unit running at any operation mode, if nanoe operation is activated, combination operation (operation
mode + nanoe operation) starts.
o During unit is OFF, if nanoe operation is activated, nanoe individual operation starts.
nanoe operation stop condition
o When OFF/ON button is pressed to stop the operation.
o When nanoe button is pressed.
o When OFF Timer activates.
o When nanoe button is pressed.
o When OFF Timer activates.
nanoe operation pause condition
o When indoor fan stop (during deice, odor cut control, thermostat off, etc.). nanoe operation resume after
indoor fan restarts.
o When indoor intake temperature ≥ 35°C and < 5°C. nanoe operation resume after indoor intake temperature
< 35°C or ≥ 5°C continuously for 6 minutes.
Indoor
fan
control
o During any operation mode combines with nanoe operation, fan speed follows respective operation mode.
However, nanoe system enabled when fan speed ≥ 470 rpm to ensure proper negative ion distribution,
nanoe system disabled when fan speed < 470 rpm.
nanoe system disabled when fan speed < 470 rpm.
o During nanoe individual operation, only Auto Fan Speed and no Powerful operation is allowed. Even if Fan
Speed button is pressed, no signal is sent to the unit and no change on remote control display. Auto Fan
Speed for nanoe individual operation is cooling medium fan.
Speed for nanoe individual operation is cooling medium fan.
Airflow direction control
o During any operation mode combines with nanoe operation, airflow direction follows respective operation
mode.
o During nanoe individual operation, only Auto Air Swing is allowed. Even if Air Swing button is pressed, no
signal is sent to the unit and no change on remote control display.
Timer
control
o When ON Timer activates when unit stops, previous operation resumes and restored last saved nanoe
operation status.
o When ON Timer activates during any operation, no change on current operation.
o When OFF Timer activates during any operation, all operation stops and the latest nanoe operation status is
o When OFF Timer activates during any operation, all operation stops and the latest nanoe operation status is
saved.
Indicator
o When nanoe starts, nanoe indicator ON.
90
Remote Control Receiving Sound
o Normal
Operation
nanoe Operation
: Beep
o nanoe
Operation
Normal Operation
: Beep
o
Stop
nanoe individual Operation : Beep
o nanoe individual Operation
Stop
: Long Beep
Power
failure
o During nanoe individual operation, if power failure occurs, after power resumes, nanoe individual operation
resumes immediately.
o During combination operation, if power failure occurs, after power resumes, combination operation resume
immediately.
nanoe
check
mode
o To enable nanoe check mode, during nanoe operation ON:
Normal display mode
Transmit
“NANOE CHECK” code
“NANOE CHECK” code
Press SW
(t
≥ 0 secs)
When
SW pressed continuously for t
≥ 5 secs to enter service zone
and press
SW’s to choose function 57
o During nanoe check mode, H67 is judged when disconnection detected. Timer LED blinks.
nanoe Abnormal Detection
o Disconnection
Abnormality
Abnormal
detection
condition
Start from 1 sec after nanoe power ON, 6 secs has passed and in this 6 secs period, abnormal signal
is detected continuously for 5.9 secs.
Action after abnormal detection condition fulfilled
Disconnection counters +1, nanoe power OFF for 5 minutes and then restart. However, according to
action mode and disconnection counter, below will be implemented:
o During nanoe Check Mode: Disconnection abnormality will judged when disconnection counter
o During nanoe Check Mode: Disconnection abnormality will judged when disconnection counter
≥ 1. Abnormal code: H67 will memorized in EEPROM, Timer LED blinking and nanoe LED Off.
o Other Than Above: Disconnection abnormality will judged when disconnection counter ≥ 3.
Abnormal code: H67 will memorized in EEPROM and nanoe LED OFF, Timer LED not blinking.
Disconnection counters clear condition >
Disconnection counter will be cleared when operation stop. (Not nanoe Check Mode)
91
o nanoe Discharge Abnormality
Abnormal
detection
condition
After 30 minutes nanoe power ON, abnormal signal is being detected continuously for 5s.
Action after abnormal detection condition fulfilled
Abnormal discharge counter +1, nanoe power OFF for 30 minutes and then restart. When abnormal
discharge counter ≥ 12, abnormal code: H67 in analyze area (Area where abnormal code not
displayed) will be memorized.
displayed) will be memorized.
Abnormal discharge counters clear condition
Discharge counter will be cleared when operation become normal for 50 mins above or when
operations stop.
14.13 Mild Dry Cooling Operation
This operation helps to prevent decreases in room humidity while maintaining the setting temperature.
During unit running at Cooling operation mode, if “Mild Dry Cooling” button is pressed, Mild Dry Cooling operation
starts and Mild Dry Cooling indicators turns ON at remote control display.
Mild dry cooling operation is unavailable when the unit is operating Auto mode and Soft Dry model operation.
Mild dry cooling operation is cancelled when the unit turned OFF, Mild Dry Cooling button is pressed again or
when the operation mode changed from Cooling to other mode.
ECONAVI, Powerful, Quiet and Mild Dry Cooling mode cannot function at the same time, the unit will follows the
operation according to the last signal received.
During this operation, the compressor frequency changes according to operating condition to prevent room
humidity decreases and when AUTO AIR SWING is set, the vertical airflow direction fixed at lower limit position.
14.14 ECONAVI Operation
Area of human availability, activity level and absent is judged based on pulses by using 2 infrared sensors. The
internal setting temperature shift, fan speed and horizontal airflow direction are adjusted in order to provide
comfort environment while maintain the energy saving level.
comfort environment while maintain the energy saving level.
ECONAVI start condition:
o When ECONAVI button is pressed.
ECONAVI stop conditions:
o When ECONAVI button is pressed again.
o When unit is OFF by OFF/ON button.
o When unit is OFF when OFF TIMER activates.
o When unit is OFF by AUTO OFF/ON button at indoor unit.
o When QUIET operation activates.
o When button is pressed.
o When POWERFUL operation is selected.
o When unit is OFF by OFF/ON button.
o When unit is OFF when OFF TIMER activates.
o When unit is OFF by AUTO OFF/ON button at indoor unit.
o When QUIET operation activates.
o When button is pressed.
o When POWERFUL operation is selected.
92
14.14.1 Human Activity Sensor
Area of human availability, activity level and absent is judged based on pulses by using 2 infrared sensors. The
internal setting temperature shift, fan speed and horizontal airflow direction are adjusted in order to provide
comfort environment while maintain the energy saving level.
comfort environment while maintain the energy saving level.
Human activity judgment is as following
Signal Detection
Information Log
Area of Living Classification Judgment
Human Position Analysis
Target Area & Position Judgment
Human Activity Level Judgment
Setting Position Judgment
14.14.1.1 Signal Detection
C
B
A
7m
120°
7m
2m
Human Activity sensor will turns on according to infrared sensors signal detection.
Signal detection
Possible detected human
position area
Sensor 1
Sensor 2
1
0
C
0
1
A
1 1
B
A & C
B & C
A & C
B & C
A & C
A, B & C
0 0
–
14.14.1.2 Information Log
The signal from Infrared sensors will be log to human activity database for further analysis.
14.14.1.3 Area of Living Classification Judgment
The system is able to judge area of living according to human activity database, classified as following:
o Living
Area
–
In front of television, dining table, etc.
o Walkway
–
Human detection is relatively less.
o Non-Living
Area
–
near windows, wall, etc.
Click on the first or last page to see other CS-Z20TKEW / CS-Z25TKEW / CS-Z35TKEW / CS-Z42TKEW / CS-Z50TKEW / CS-Z71TKEW / CS-XZ20TKEW / CS-XZ25TKEW / CS-XZ35TKEW / CS-XZ50TKEW / CU-Z20TKE / CU-Z25TKE / CU- / 35TKE / CU-Z42TKE / CU-Z50TKE / CU-Z71TKE / CU-Z20TKE / CU-Z25TKE / CU-Z35TKE / CU-Z50TKE service manuals if exist.