41 
12.5 Quiet Operation 
 Purpose 
o  To provide quiet operation compare to normal operation. 
 
 Control 
condition 
o  Quiet operation start condition 
  When “QUIET” button at remote control is pressed. 
 “ 
 ” shown in LCD of remote control. 
o  Quiet operation stop condition 
  When one of the following conditions is satisfied, quiet operation stops: 
  QUIET button is pressed again. 
  Stop by OFF/ON button. 
  FAN SPEED button is pressed. 
  AUTO COMFORT button is pressed. 
  ECONAVI button is pressed. 
  When fan speed is changed, fan speed follows the setting change. 
  When operation mode is changed, resume previous operation setting. 
  During quiet operation, if timer “on” activates, quiet operation maintains. 
12.6 Powerful Mode Operation 
  When the powerful mode is selected, the internal setting temperature will shift lower up to 1°C (for Cooling) or 
higher up to 1.7°C (for Heating) than remote control setting temperature to achieve the setting temperature 
quickly. 
12.7 Timer Control 
  There are 2 sets of ON and OFF timer available to turn the unit ON or OFF at different preset time. 
  If more than one timer had been set, the upcoming timer will be displayed and will activate in sequence. 
12.7.1 ON 
Timer 
Control 
  ON timer 1 and ON timer 2 can be set using remote control, the unit with timer set will start operate earlier than 
the setting time. 
This is to provide a comfortable environment when reaching the set ON time. 
  70 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to 
determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting 
time. 
  From the above judgment, the decided operation will start operate earlier than the set time as shown below. 
 
 
 
12.7.2  OFF Timer Control 
OFF timer 1 and OFF timer 2 can be set using remote control, the unit with timer set will stop operate at set time. 
42 
12.7.3 Sleep 
Timer 
  Sleep operation is performed according to the delay OFF time (0.5, 1, 2, 3, 5, 7 or 9 hr) and provide comfortable 
environment by shifting set temperature. 
 
 
 
 Heating Cooling, 
Dry 
A 2hr 
3hr 
B *5am 
*4am 
 
* According to remote control clock 
 
Temperature Shift 
 
 
 
Status 1 
Status 2 
Status 3 
Status 4 
Cooling/Dry 0 
+1 
+1 
+1 
Set temperature (°C) 
Heating 0 -1 -1 -1 
 
Stop condition 
- Reached delay time. 
- Pressed sleep button to cancel. 
- Unit is OFF. 
12.8 Auto Restart Control 
  When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within 
three to four minutes (various period of protection control is programmed) after power supply resumes. 
  This type of control is not applicable during ON/OFF Timer setting. 
12.9 Indication Panel 
 
LED POWER  TIMER  +8/10°C 
HEAT 
nanoe-G
ECONAVI 
Color Green  Orange 
Green  Blue Green 
Light ON 
Operation ON  Timer Setting ON
+8/10°C HEAT 
Mode ON 
nanoe-G 
ON 
ECONAVI ON 
Light OFF 
Operation OFF  Timer Setting OFF
+8/10°C HEAT 
Mode OFF 
nanoe-G 
OFF 
ECONAVI OFF 
 
Note: 
  If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation 
mode judgment, or ON timer sampling. 
  If Timer LED is blinking, there is an abnormality operation occurs. 
43 
12.10 nanoe-G 
Operation 
  This operation provides clean air by producing great amount of negative ions and distribute through the 
discharge airflow to capture or deactivate molds, bacteria or viruses. 
 
  nanoe-G ON/OFF condition 
 
Priority Item 
Output 
During Demo mode 
Two-way communications on remote control 
NANOE-G connector open 
NANOE-G error (circuit error & abnormal discharge detection) 
OFF 
Inspection mode  NANOE-G ON command 
ON 
Inspection mode  NANOE-G OFF command 
OFF 
No “NANOE-G” setting on the remote control 
Operation status: OFF 
During NANOE-G restart prohibiting time 
(Prohibiting time is set in the case of abnormal discharge and room temperature of 40°C 
and above. Details will be provided later.) 
During FM OFF; or FM rotation speed is less than 490 rpm 
OFF 
Less than 60 minutes have elapsed 
since the start of Powerful 
individual fan operation. 
ON 
Airflow direction is not set to ceiling airflow or 
DOWN   
 
Other than above 
Airflow direction is ceiling airflow or DOWN   
 
ON/OFF 
intermittent output 
as mentioned 
below 
 
 ON/OFF intermittent output 
 
  nanoe-G operation pause condition 
o  When indoor fan stop (during deice, odor cut control, thermostat off, etc.). nanoe-G operation resume after 
indoor fan restarts. 
o  When indoor intake temperature ≥ 40°C. nanoe-G operation resume after indoor intake temperature ≤ 40°C 
continuously for 30 minutes. 
 
 Indoor 
fan 
control 
o  During any operation mode combines with nanoe-G operation, fan speed follows respective operation mode. 
However, nanoe-G system enabled when fan speed ≥ 490 rpm to ensure proper negative ion distribution, 
nanoe-G system disabled when fan speed < 490 rpm. 
 
  Airflow direction control 
o  During any operation mode combines with nanoe-G operation, airflow direction follows respective operation 
mode. 
o  During nanoe-G individual operation, any airflow direction can be combined. 
 
 Timer 
control 
o  When ON Timer activates during any operation, no change on current operation. 
o  When OFF Timer activates during any operation, all operation stops and the latest nanoe-G operation status 
is saved. 
 
 Indicator 
o  When nanoe-G starts, nanoe-G indicator ON (at Indoor Unit and Remote Control). 
 
  Remote Control Receiving Sound 
o Normal 
Operation 
 
 nanoe-G Operation   
     : Beep 
o Nanoe-G 
Operation   
 Normal Operation 
 
     : Beep 
 
Stop 
    nanoe-G individual Operation      : Beep 
o  Nanoe-G individual Operation   Stop  
 
 
     : Long Beep 
 
 
 
44 
 Power 
failure 
o  During nanoe-G individual operation, if power failure occurs, after power resumes, nanoe-G individual 
operation resumes immediately. 
o  During combination operation, if power failure occurs, after power resumes, combination operation resume 
immediately. 
 
  Error detection control 
When nanoe-G indicator blinks, it indicates error listed below: 
o  nanoe-G connector at main PCB open 
 Judgment 
method 
  During nanoe-G operation, nanoe-G connector at main PCB is opened. 
 Troubleshooting 
method 
  Connect the connector or stop operation to cancel the blinking. 
o  Abnormal discharge error 
 Judgment 
method 
  During nanoe-G operation, the nanoe-G system has abnormal discharge due to short-circuit caused 
by water or dust adhesion and so forth, with Lo-feedback voltage (at microcontroller). 
  When abnormal discharge occurred, every 30 minutes the unit supplies power to the nanoe-G 
system. 
  When abnormal discharge occurs for 24 times continuously, nanoe-G indicator blinks. 
 
o Troubleshooting 
method 
  Press nanoe-G button or OFF button to stop the operation and check the nanoe-G connector at PCB. 
  After that, press nanoe-G button again to confirm the nanoe-G indicator do not blinks. 
  The 24 timer counter will be clear after 10 minutes of normal operation or when operation stops. 
 
o  Error reset method 
  Press OFF button to OFF the operation. 
  Press AUTO OFF/ON button at indoor unit to OFF the operation. 
  OFF Timer activates. 
  Power supply reset. 
Page of 127