Panasonic CS-VE9NKE / CS-VE12NKE / CU-VE9NKE / CU-VE12NKE Service Manual ▷ View online
49
12.12.2.1 Demo Mode
The air conditioner starts the operation in the Demo mode as described below when 2 minutes have elapsed after the
protection control was started subsequent to the confirmation of communication error.
(At this time, a strong warning sound is emitted for 3 minutes if the test run memory is “incomplete”.)
Condition to stop the mode
The operation is stopped by turning off the air conditioner on the remote control or pressing the EMERGENCY
OPERATON switch during the Demo mode.
(“TIMER” LED flashes.)
protection control was started subsequent to the confirmation of communication error.
(At this time, a strong warning sound is emitted for 3 minutes if the test run memory is “incomplete”.)
Condition to stop the mode
The operation is stopped by turning off the air conditioner on the remote control or pressing the EMERGENCY
OPERATON switch during the Demo mode.
(“TIMER” LED flashes.)
Zone B
Airflow Unit Operation Mode (Normal Operation)
Transition time to Demo
Mode
180sec from
the demo starts
360 sec from
the demo starts
540 sec from
the demo starts
660 sec from
the demo starts
[POWER] LED
ON
OFF
[NANOE-G] LED
Follow the remote control settings
OFF
[+8/10°C HEAT] LED
Follow the remote control settings
OFF
[ECONAVI] LED
Follow the remote control settings
OFF
[TIMER] LED
When in Product Demo mode: Always OFF (Timer is cancelled due to H11)
Front panel STM
Open
Stop position
Vertical louver STM
Ceiling airflow
Heating 5
Swing
Stop position
Horizontal louver STM
Area OFF is set: Swing from the front side
Others: Area control under Heating, Range B, Airflow stable
Reset
Fan motor
Fan speed is set to Auto on the remote control: OFF
Fan speed is set to Manual on the remote control: Remote controller
setting tap
Stop position
Human activity sensor
Area ON: Repeat the scan detection and fixed detection.
Area OFF: Standby position (Default position)
Standby position
(Default position)
Sunlight sensor
LED brightness changes (Bright-Dim) when ECONAVI is ON. Confirmed time is for Demo only.
NANOE output
OFF
12.12.2.2 Infrared Sensor Check Mode
1 Conditions to start the mode
The infrared sensor check mode starts when all of the following conditions are met:
o
The infrared sensor error is not being detected.
o
Not in Demo mode.
o
An error of Error Level 20 or higher is not present.
o
The signal for infrared sensor check is received. (Long-press the “AUTO COMFORT” button on the
remote control for 10 seconds)
remote control for 10 seconds)
2 Conditions to end the mode
The infrared sensor check mode ends when any of the following conditions is met:
o
A signal other than the signal for infrared sensor check is received; or the Auto OFF/ON button is
pressed → The signal received is followed.
pressed → The signal received is followed.
o
5 minutes have elapsed since the signal for infrared sensor check was received → The mode is stopped.
o
The infrared sensor error is confirmed → The mode is stopped.
o
An error of Error Level 20 or higher has occurred → Follow the processing of each error.
50
3 Descriptions of the mode
Every time the signal for infrared sensor check is received, the fixed detection is performed at a different
human activity sensor angle. The result is displayed on LED every 3 seconds.
human activity sensor angle. The result is displayed on LED every 3 seconds.
Operation mode
OFF (Cleaning is also stopped)
Panel
Ordinary operating position (It opens even if the mode signal received is “OFF”)
Every time the signal for infrared sensor check is received, the position is shifted in the sequence of
“Front Left Right Front …”
It starts operation from the front position when the check mode starts.
Front
Every time the signal for infrared sensor check is received, the position is shifted in the sequence of
“Front Left Right Front …”
It starts operation from the front position when the check mode starts.
Front
Direction towards detection of middle area
Left
Direction towards detection of left area
Human activity sensor
STM
STM
Right
Direction towards detection of right area
[TIMER] LED
Sensor responded: ON Sensor not responded: OFF
[ECONAVI] LED
The status in which the detection is not allowed : OFF
The status in which the detection is allowed: ON
The status in which the detection is allowed: ON
LED
Other LEDs
OFF
Other parts
Follow the case of OFF mode
Conditions in which detection is not allowed
o For 65 seconds after the infrared sensor is powered ON.
o While the human detection sensor STM is in operation and for 10 seconds after the human activity sensor
o While the human detection sensor STM is in operation and for 10 seconds after the human activity sensor
STM turns off.
Operation command by HA and ON timer is not valid during check mode.
(OFF mode continues even after the check mode stops at the expiry time.)
12.12.3 Sunlight Sensor
During ECONAVI operation, the sunlight sensor detects sunlight intensity coming through windows and
differentiates between sunny and cloudy or night to further optimize energy saving by adjusting the temperature.
Sunlight judgment is as following.
12.12.3.1 Sunlight Intensity Reset
The sunlight intensity will to reset to zero (no sunlight condition) when
o Each time ECONAVI is activated.
o Setting temperature is changed.
o Operation mode is changed (exception interchanging COOL ↔ DRY).
o Open the Front Panel (Front Panel switch open).
o Setting temperature is changed.
o Operation mode is changed (exception interchanging COOL ↔ DRY).
o Open the Front Panel (Front Panel switch open).
51
12.12.3.2 Judge Sunlight Intensity
Based on sunlight sensor output voltage, the sunlight intensity value will be computed and logged to sunlight
intensity database.
The sunlight sensor sensitivity could be adjusted:
Function MENU button:
1 Selection of installation location.
2 Selection of indicators’ brightness.
3 ECONAVI
2 Selection of indicators’ brightness.
3 ECONAVI
indicator
OFF.
4 Selection of Contrast of LCD on remote.
12.12.3.3 Judge Ambient Condition
According to sunlight intensity over a period of time, the system will analyze the ambient condition is sunny,
cloudy or night.
12.12.3.4 Temperature Shift
52
12.12.3.5 Sunlight Sensor Check Mode
Operation details (to check, press ECONAVI button for 10 sec).
o The sunlight sensor check mode will be operated for 5 minutes.
o During check mode, the ON and OFF timer will be memorized but it operation be ignored.
o During check mode, if the sunlight sensor check code is retransmitted, the 5 minutes counter will be reset.
o During check mode, if sunlight sensor detected the sunlight intensity value above minimum level, the
o During check mode, the ON and OFF timer will be memorized but it operation be ignored.
o During check mode, if the sunlight sensor check code is retransmitted, the 5 minutes counter will be reset.
o During check mode, if sunlight sensor detected the sunlight intensity value above minimum level, the
ECONAVI indicator turns ON. Else if sunlight sensor detected sunlight intensity value below minimum level,
the ECONAVI indicator is OFF.
the ECONAVI indicator is OFF.
To disable sunlight sensor check mode
o After check mode is ended (5 minutes counter elapsed), press AUTO OFF/ON button at indoor unit.
o If the sunlight sensor detected sunlight intensity is at abnormal range, the check mode will be ended.
o If the sunlight sensor detected sunlight intensity is at abnormal range, the check mode will be ended.
Please check for error code.
12.12.3.6 Sunlight Sensor Abnormality
Abnormality
detection:
o When ECONAVI is ON, if the sunlight intensity value below minimum level continuously for 24 hours, the
sunlight sensor disconnection error counter will increase by 1 time. If the ECONAVI is OFF, the 24 hours
timer will be reset, but the sunlight sensor disconnection error counter will not be reset.
timer will be reset, but the sunlight sensor disconnection error counter will not be reset.
Error Code judgment
o When sunlight sensor disconnection error counter reached 15 times. H70 occurred.
o No TIMER indicator or ECONAVI indicator blink.
o No TIMER indicator or ECONAVI indicator blink.
When error code happened, the unit is able to operate without sunlight sensor.
Click on the first or last page to see other CS-VE9NKE / CS-VE12NKE / CU-VE9NKE / CU-VE12NKE service manuals if exist.