12.12.2.1 Demo Mode 
The air conditioner starts the operation in the Demo mode as described below when 2 minutes have elapsed after the 
protection control was started subsequent to the confirmation of communication error.  
(At this time, a strong warning sound is emitted for 3 minutes if the test run memory is “incomplete”.) 
 
Condition to stop the mode 
The operation is stopped by turning off the air conditioner on the remote control or pressing the EMERGENCY 
OPERATON switch during the Demo mode. 
(“TIMER” LED flashes.) 
 
Zone B 
Airflow Unit Operation Mode (Normal Operation) 
Transition time to Demo 
Mode 
180sec from  
the demo starts 
360 sec from  
the demo starts 
540 sec from  
the demo starts 
660 sec from  
the demo starts 
[POWER] LED 
ON 
OFF 
[NANOE-G] LED 
Follow the remote control settings 
OFF 
[+8/10°C HEAT] LED 
Follow the remote control settings 
OFF 
[ECONAVI] LED 
Follow the remote control settings 
OFF 
[TIMER] LED 
When in Product Demo mode: Always OFF (Timer is cancelled due to H11) 
Front panel STM 
Open 
Stop position 
Vertical louver STM 
Ceiling airflow 
Heating 5 
Swing 
Stop position 
Horizontal louver STM 
Area OFF is set: Swing from the front side 
Others: Area control under Heating, Range B, Airflow stable 
Reset 
Fan motor 
Fan speed is set to Auto on the remote control: OFF 
Fan speed is set to Manual on the remote control: Remote controller 
setting tap 
Stop position 
Human activity sensor 
Area ON: Repeat the scan detection and fixed detection. 
Area OFF: Standby position (Default position) 
Standby position 
(Default position) 
Sunlight sensor 
LED brightness changes (Bright-Dim) when ECONAVI is ON.  Confirmed time is for Demo only. 
NANOE output 
OFF 
12.12.2.2    Infrared Sensor Check Mode 
1  Conditions to start the mode 
The infrared sensor check mode starts when all of the following conditions are met: 
The infrared sensor error is not being detected. 
Not in Demo mode. 
An error of Error Level 20 or higher is not present. 
The signal for infrared sensor check is received. (Long-press the “AUTO COMFORT” button on the 
remote control for 10 seconds) 
 
2  Conditions to end the mode 
The infrared sensor check mode ends when any of the following conditions is met: 
A signal other than the signal for infrared sensor check is received; or the Auto OFF/ON button is 
pressed → The signal received is followed. 
5 minutes have elapsed since the signal for infrared sensor check was received → The mode is stopped. 
The infrared sensor error is confirmed → The mode is stopped. 
An error of Error Level 20 or higher has occurred → Follow the processing of each error. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
50 
3  Descriptions of the mode 
Every time the signal for infrared sensor check is received, the fixed detection is performed at a different 
human activity sensor angle. The result is displayed on LED every 3 seconds. 
 
Operation mode 
OFF (Cleaning is also stopped) 
Panel 
Ordinary operating position (It opens even if the mode signal received is “OFF”) 
Every time the signal for infrared sensor check is received, the position is shifted in the sequence of 
“Front   Left  Right  Front …” 
It starts operation from the front position when the check mode starts. 
Front 
Direction towards detection of middle area 
Left 
Direction towards detection of left area 
Human activity sensor 
STM 
Right 
Direction towards detection of right area 
[TIMER] LED 
Sensor responded: ON       Sensor not responded: OFF 
[ECONAVI] LED 
The status in which the detection is not allowed : OFF 
The status in which the detection is allowed: ON 
LED 
Other LEDs 
OFF 
Other parts 
Follow the case of OFF mode 
 
 
 
 Conditions in which detection is not allowed 
o  For 65 seconds after the infrared sensor is powered ON. 
o  While the human detection sensor STM is in operation and for 10 seconds after the human activity sensor 
STM turns off. 
 
 Operation command by HA and ON timer is not valid during check mode. 
(OFF mode continues even after the check mode stops at the expiry time.) 
12.12.3 Sunlight Sensor 
  During ECONAVI operation, the sunlight sensor detects sunlight intensity coming through windows and 
differentiates between sunny and cloudy or night to further optimize energy saving by adjusting the temperature. 
  Sunlight judgment is as following. 
 
 
12.12.3.1  Sunlight Intensity Reset 
  The sunlight intensity will to reset to zero (no sunlight condition) when 
o  Each time ECONAVI is activated. 
o  Setting temperature is changed. 
o  Operation mode is changed (exception interchanging COOL ↔ DRY). 
o  Open the Front Panel (Front Panel switch open). 
51 
12.12.3.2 Judge Sunlight Intensity 
  Based on sunlight sensor output voltage, the sunlight intensity value will be computed and logged to sunlight 
intensity database. 
  The sunlight sensor sensitivity could be adjusted: 
 
 
 
  Function MENU button: 
1  Selection of installation location. 
2  Selection of indicators’ brightness. 
3 ECONAVI 
indicator 
OFF. 
4  Selection of Contrast of LCD on remote. 
12.12.3.3  Judge Ambient Condition 
  According to sunlight intensity over a period of time, the system will analyze the ambient condition is sunny, 
cloudy or night. 
12.12.3.4 Temperature Shift 
 
 
52 
12.12.3.5 Sunlight Sensor Check Mode 
  Operation details (to check, press ECONAVI button for 10 sec). 
o  The sunlight sensor check mode will be operated for 5 minutes. 
o  During check mode, the ON and OFF timer will be memorized but it operation be ignored. 
o  During check mode, if the sunlight sensor check code is retransmitted, the 5 minutes counter will be reset. 
o  During check mode, if sunlight sensor detected the sunlight intensity value above minimum level, the 
ECONAVI indicator turns ON. Else if sunlight sensor detected sunlight intensity value below minimum level, 
the ECONAVI indicator is OFF. 
  To disable sunlight sensor check mode 
o  After check mode is ended (5 minutes counter elapsed), press AUTO OFF/ON button at indoor unit. 
o  If the sunlight sensor detected sunlight intensity is at abnormal range, the check mode will be ended. 
Please check for error code. 
12.12.3.6  Sunlight Sensor Abnormality 
 Abnormality 
detection: 
o  When ECONAVI is ON, if the sunlight intensity value below minimum level continuously for 24 hours, the 
sunlight sensor disconnection error counter will increase by 1 time. If the ECONAVI is OFF, the 24 hours 
timer will be reset, but the sunlight sensor disconnection error counter will not be reset. 
  Error Code judgment 
o  When sunlight sensor disconnection error counter reached 15 times. H70 occurred. 
o  No TIMER indicator or ECONAVI indicator blink. 
  When error code happened, the unit is able to operate without sunlight sensor. 
 