12. Operation
Control
12.1 Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air
temperature.
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air
temperature.
12.1.1 Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting
processes. These shifting processes are depending on the air conditioner settings and the operation environment.
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the
electrical power is supplied to the unit.
processes. These shifting processes are depending on the air conditioner settings and the operation environment.
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the
electrical power is supplied to the unit.
12.1.2 Cooling
Operation
12.1.2.1 Thermostat
Control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C continue for 3 minutes.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point.
12.1.3 Dry
Operation
12.1.3.1 Thermostat
Control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.5°C continue for 3 minutes.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point.
34
12.1.4 Heating
Operation
12.1.4.1 Thermostat
Control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature ≥ +2.0°C continue for 3 minutes.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature <
Compressor OFF point.
12.1.5 Automatic
Operation
This mode can be set using remote control and the operation is decided by remote control setting temperature,
remote control operation mode, indoor intake air temperature and outdoor air temperature.
During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 30
seconds to detect the indoor intake and outdoor air temperature. The operation mode is decided based on below
chart.
chart.
Every 30 minutes, the indoor and outdoor temperature is judged.
The Auto Operation Mode shifting will take place whenever operation mode changed from Cooling/Dry to Heating or
vice versa.
35
12.2 Indoor Fan Motor Operation
12.2.1 CS-VE9NKE
Indicates the changeable range using the remote control
Stop
SSLo
SLo
Quiet
Lo-
Lo
Me-
Me
Hi
SHi
Fan speed: Manual
O
---
---
(600)
---
640
800
960
1110
---
Normal (with programmed air)
O
860 ~ 960
Powerful
1190
Initial airflow
Human search
area control
area control
740
Powerful
620 980
COOL / C
O
OL R
ange
Airflow stable
Human search
area control
area control
620 980
Normal Cool
dry O
470
640
Powerful
640
Initial airflow
Human search
area control
area control
740
Powerful
510 980
COOL DRY
Ran
ge
Fan
speed:
Auto
Airflow stable
Human search
area control
area control
510 980
Fan speed: Manual
O
---
---
650
---
720
850
980
1110
---
Normal 680 1020
Powerful
780 1060
680 1110
Initial airflow
Human search
area control
area control
680 1210
Powerful
850 980
HEAT
Fan
speed:
Auto
Airflow stable
Human search
area control
area control
850 980
Hot Dry
640
Fan speed: Manual
O
---
600
---
640
800
960
1110
---
Normal
500
Individual
nanoe-G
nanoe-G
Fan speed:
Auto
Powerful
1190
Individual +8/10°C HEAT
1110
Odor Cut Shift
Only for the COOL and DRY range
Only for the COOL and DRY range
Below Lo: No shifting Me and above: -90
Lo and above, below Me and fan speed auto: -20
Lo and above, below Me and fan speed auto: -20
* Lock detection: When the rotation speed of 2550rpm and above or below 50rpm is detected for 10 consecutive seconds during the feedback
control, H19 is indicated (the TIMER indicator flashes) if normal rotation speed is not detected even after the retry is performed 7 times.
* Refer to the attached list of “Indoor Unit Fan Operation Status” for the operations of the indoor unit fan while the thermostat is OFF.
36
(1) When the area control is in operation, the minimum rotation speed is limited as outlined below depending on the human position area.
COOL & COOL DRY
Same as the fan speed in the powerful mode. When the airflow is stable, the minimum rotation speed is limited to
“1+2+3” as in the table below.
“1+2+3” as in the table below.
HEAT
Same as the fan speed in the powerful mode. In the range where the airflow is stable and the pipe temperature is high,
the minimum rotation speed is limited to “1+3” as in the table below.
the minimum rotation speed is limited to “1+3” as in the table below.
FULL DRY
The rotation speed is fixed at “1+2+3” as in the table below.
Min. rotation speed for each field
The minimum rotation speed is limited based on
the following area information.
Corresponding
Area
Field 2
LM, RM
Field 3
CM
1
COOL
COOL
DRY
HEAT
Field
2
880 740 990
Field
3
840 700 970
2
During the ceiling airflow, a correction is performed
for the minimum rotation speed as follows.
In COOL or COOL
DRY mode
100
3
When making the air blow towards human
body/object, a correction is performed for the minimum
rotation speed as follows.
rotation speed as follows.
In COOL or COOL
DRY mode
60