Panasonic CS-ME7CB1P / CS-ME10CB1P / CS-ME12CB1P / CS-ME14CB1P / CS-ME10CD3P / CS-ME14CD3P Simplified Service Manual ▷ View online
Symbol
Diagnosis
Diagnosis method
F96
IPM (Power transistor
module) or
compressor
overheating
module) or
compressor
overheating
When this trouble is detected from the electrical parts radiation fin temperature sensor and OLP output during
operation, operation stops, and it is restarted 3 minutes later. If the trouble occurs on 4 occasions, operation
stops, and the trouble display appears.
<Diagnosis checkpoint>
1.
operation, operation stops, and it is restarted 3 minutes later. If the trouble occurs on 4 occasions, operation
stops, and the trouble display appears.
<Diagnosis checkpoint>
1.
Something may be interfering with the dissipation of the heat outdoors or the outdoor unit fan may be
defective. (The outdoor unit fan is not running.)
defective. (The outdoor unit fan is not running.)
2.
Defective IPM (outdoor unit control P.C. Board)
3.
Gas leaks. Shutting valve is not opened.
F97
Compressor high
discharge
temperature
discharge
temperature
This trouble display appears and operation stops when this happens on 6 occasions (it is cleared when the
operation is normal for 20 minutes).
<Diagnosis checkpoint>
1.
operation is normal for 20 minutes).
<Diagnosis checkpoint>
1.
Check the refrigerating cycle: Gas may be leaking (the amount of refrigerant is low). The stopping of the
outdoor unit from time to time is a symptom of this trouble.
outdoor unit from time to time is a symptom of this trouble.
2.
When operation steps with this trouble display appearing, check the compressor temperature sensor
(check for changes in its characteristics and check its resistance).
(check for changes in its characteristics and check its resistance).
3.
Something may be interfering with the dissipation of the heat outdoors or the outdoor unit fan may be
defective. (The fan will not run because of an open circuit.)
defective. (The fan will not run because of an open circuit.)
(The protection function may be activated by an overload, and the F97 trouble display will remain stored
in the memory.)
in the memory.)
F98
Total running current
protection
protection
When the total current exceeds the setting (17A to 20A), frequency control is started, and if it then exceeds the
setting, operation stops, and the trouble display appears.
<Diagnosis checkpoint>
1.
setting, operation stops, and the trouble display appears.
<Diagnosis checkpoint>
1.
Check the AC voltage at the outdoor unit terminal board during operation: The voltage drop must be within
5% of the voltage when operation has stopped (± 110% of rated voltage even during operation). If the
voltage drop exceeds 5% or if the voltage changes suddenly, inspect whether the power supply cord and
indoor/outdoor unit connection cables are too long or too small in diameter, etc.
5% of the voltage when operation has stopped (± 110% of rated voltage even during operation). If the
voltage drop exceeds 5% or if the voltage changes suddenly, inspect whether the power supply cord and
indoor/outdoor unit connection cables are too long or too small in diameter, etc.
2.
Check whether something is interfering with the dissipation of the heat outdoors (during cooling
operations): Normally, the capacity is limited by the current so that the outdoor unit don’t stop, and the
diagnostic display does not appear.
operations): Normally, the capacity is limited by the current so that the outdoor unit don’t stop, and the
diagnostic display does not appear.
F99
DC peak detection
When “Output current trouble”, which occurs when the prescribed current level is exceeded, has occurred on
16 consecutive occasions, operation stops, and the trouble display appears.
<Diagnosis checkpoint>
1.
16 consecutive occasions, operation stops, and the trouble display appears.
<Diagnosis checkpoint>
1.
Check whether the compressor is defective (locked up or shorted winding). Check the outdoor unit control
P.C. Board.
P.C. Board.
29
CS-ME7CB1P / CS-ME10CB1P / CS-ME12CB1P / CS-ME14CB1P / CS-ME10CD3P / CS-ME14CD3P
10 Installation Instructions
10.1. Cassette Type
1. Philips screw driver
2. Level gauge
3. Electric drill, hole core drill
(ø70
2. Level gauge
3. Electric drill, hole core drill
(ø70
mm)
4. Hexagonal wrench (4 mm)
5. Spanner
6. Pipe cutter
5. Spanner
6. Pipe cutter
7. Reamer
8. Knife
9. Gas leak detector
10. Measuring tape
11. Thermometer
12. Megameter
13. Multimeter
8. Knife
9. Gas leak detector
10. Measuring tape
11. Thermometer
12. Megameter
13. Multimeter
14. Torque wrench
18 N•m (1.8 kgf.m)
42 N•m (4.2 kgf.m)
15. Vacuum pump
18 N•m (1.8 kgf.m)
42 N•m (4.2 kgf.m)
15. Vacuum pump
16. Gauge manifold
Required tools for Installation Works
SAFETY PRECAUTIONS
• Read the following “SAFETY PRECAUTIONS” carefully before installation.
• Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main
• Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main
circuit for the model to be installed.
• The caution items stated here must be followed because these important contents are related to safety. The meaning of
each indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the
seriousness is classified by the following indications.
seriousness is classified by the following indications.
• Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation,
care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future
reference.
reference.
WARNING
This indication shows the possibility of causing death or serious injury.
CAUTION
This indication shows the possibility of causing injury or damage to properties only.
Symbol with background white denotes item that is PROHIBITED from doing.
WARNING
1)
Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage,
electrical shock or fire.
2)
Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical
shock or fire.
3)
Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage,
fire or electrical shock.
4)
Install at a strong and firm location which is able to withstand the set's weight. If the strength is not enough or
installation is not properly done, the set will drop and cause injury.
1)
This equipment must be earthed. It may cause electrical shock if grounding is not perfect.
5)
For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent
circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will
cause electrical shock or fire.
cause electrical shock or fire.
3)
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and
damage the furniture.
7)
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed
perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
6)
Use the specified cable (1.5 mm
2
) and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable
so that no
externa
l force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the
connection.
8)
When carrying out piping connection, take care not to let air substances other than the specified
refrigerant go into refrigeration cycle.
8)
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and
injury.
9)
When connecting the piping, do not allow air or any substances other than the specified refrigerant
(R410A) to enter the refrigeration cycle. Otherwise, this may lower the capacity, cause abnormally high
pressure in the refrigeration cycle, and possibly result in explosion and injury.
pressure in the refrigeration cycle, and possibly result in explosion and injury.
10) Do not modify the length of the power supply cord or use of the extension cord, and do not share the
single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.
2)
Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and
accumulates at surrounding of the unit, it may cause fire.
2)
Do not release refrigerant.
3)
Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take
care of the liquid refrigerant, it may cause frostbite.
3)
Installation work.
4)
It may need two people to carry out the installation work.
4)
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
1)
Selection of the installation location.
1)
Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy
maintenance.
The items to be followed are classified by the symbols:
CAUTION
ATTENTION
Installation Instructions
CS
-M
-M
E
7C
B
1P
/
/
C
S
-M
E
10CB1
P
/
CS
-M
E
-M
E
12CB1
P
/
CS
-M
E
-M
E
14CB1
P
/
CS
-M
E
-M
E
10CD3
P
/
CS
-M
-M
E
14
CD3P
30
Selecting the Installation Location
1
Selecting the Piping
2
3
No.
No.
No.
Accessory part
Accessory part
Accessory part
Qty.
Qty.
Qty.
Piping insulation
Band
Remote control
Battery
Remote control holder
Drain joint
Pattern
Remote control holder
fixing screw
fixing screw
Pattern fixing screw
1
2
6
3
4
5
7
8
9
Indoor Unit Accessory Parts
2
4
2
1
2
1
1
1
4
Required Materials
Product name Remarks
VP20 (outer diameter ø26) ; also sockets, elbows and other
parts as necessary
parts as necessary
PVC adhesive
For refrigerant piping insulation
(foamed polyethylene with a thickness of 8 mm or more)
For drain piping insulation
(foamed polyethylene with a thickness of 10 mm or more)
(foamed polyethylene with a thickness of 8 mm or more)
For drain piping insulation
(foamed polyethylene with a thickness of 10 mm or more)
4×1.5 mm
2
flexible cord, type designation 245 IEC 57 (H05RN-F)
(See "Connecting the Indoor/Outdoor Connecting Cable".)
Hanging bolts (M10) (4) and nuts (12), Flat washers (8)
Rigid PVC pipe
Adhesive
Insulation
Indoor/outdoor
connecting cable
connecting cable
Hanging bolt related parts
Other Items to be Prepared (Locally Purchased )
Determine the location with the agreement of the customer.
Indoor unit
The location should be strong enough to support the main unit without vibration.
There should not be any heat or steam sources nearby.
Drainage should be easy. Avoid locating the drain port close to ditches
(domestic wastewater).
Avoid locations above entrances and exits.
Ensure the distances indicated by the marks in the illustration.
Ensure sufficient space for installation and servicing.
The ceiling surface (lower surface) should be level.
Locate the indoor unit at least 1 m or more away from a TV, radio, wireless
equipment, antenna cables and fluorescent lights, and 2 m or more away
from a telephone.
There should not be any heat or steam sources nearby.
Drainage should be easy. Avoid locating the drain port close to ditches
(domestic wastewater).
Avoid locations above entrances and exits.
Ensure the distances indicated by the marks in the illustration.
Ensure sufficient space for installation and servicing.
The ceiling surface (lower surface) should be level.
Locate the indoor unit at least 1 m or more away from a TV, radio, wireless
equipment, antenna cables and fluorescent lights, and 2 m or more away
from a telephone.
Note that if the air conditioning unit is installed near an electronically lit
fluorescent light (inverter, rapid start type, etc.), it may not receive the
remote control signals.
fluorescent light (inverter, rapid start type, etc.), it may not receive the
remote control signals.
To Drill a Hole in the Wall and
Install a Sleeve of Piping
Install a Sleeve of Piping
Indoor Unit Installation Diagram
Part name Part number
Decorative grille
CZ-BT20P
(white)
(white)
* See the Outdoor Unit Installation
Instructions.
Instructions.
CAUTION
When the wall is hollow,
please be sure to use the
sleeve for tube ass'y to
prevent dangers caused by
mice biting the connecting
cable.
please be sure to use the
sleeve for tube ass'y to
prevent dangers caused by
mice biting the connecting
cable.
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes
about 15 mm from the wall.
4. Finish by sealing the sleeve with
putty or caulking compound at the
final stage.
final stage.
Liquid side
Gas side
ø 6.35 (1/4") t 0.8
ø 9.52 (3/8") t 0.8
• Prepare the piping set shown in the table
below or equivalent products for the
refrigerant piping.
refrigerant piping.
Attaching the remote control holder to the wall
Remote control mounting location
Signals may not be transmitted and received correctly when
the remote control is operated while in the holder. Take the
remote control in your hand to operate the unit.
Mount the holder in a location that is not subject to the
effects of heat (direct sunlight and stoves, etc.).
the remote control is operated while in the holder. Take the
remote control in your hand to operate the unit.
Mount the holder in a location that is not subject to the
effects of heat (direct sunlight and stoves, etc.).
Bushing for
tube ass'y
tube ass'y
15 mm
Wall
Sleeve for
tube ass'y
ø70 through
hole
hole
Putty or caulking
compound
compound
Approx.
5 - 7 mm
5 - 7 mm
Outdoor
Indoor
Remote control holder
fixing screws
fixing screws
Remote control
holder
holder
Remote
control 3
control 3
5
6
Ceiling
Indoor unit
20 cm
or more
or more
Decorative grille
Wall
Discharge vent
Intake
19 cm or
more
more
30 cm or
more
more
30 cm or
more
CS
-M
-M
E
7C
B
1P
/
/
C
S
-M
E
10CB1
P
/
CS
-M
E
-M
E
12CB1
P
/
CS
-M
E
-M
E
14CB1
P
/
CS
-M
E
-M
E
10CD3
P
/
CS
-M
-M
E
14
CD3P
31
90
Wooden structure
Reinforced concrete
(Unit: mm)
(Unit: mm)
Connecting and Insulating the Refrigerant Piping
Lay the drain piping so as to ensure drainage.
Use a locally purchased VP20 rigid PVC pipe (outer diameter ø26) for the
drain piping, and connect it to the drain port of the indoor unit using the
drain joint 7 . Coat both sides with a PVC adhesive and adhere them firmly.
Drain piping located indoors should always be insulated by wrapping with locally
purchased insulation (foamed polyethylene with a thickness of 10 mm or more).
The drain piping should have a downward gradient (1/50 or more), and should be
secured using pipe hanging equipment to avoid creating hills or traps partway.
Use a locally purchased VP20 rigid PVC pipe (outer diameter ø26) for the
drain piping, and connect it to the drain port of the indoor unit using the
drain joint 7 . Coat both sides with a PVC adhesive and adhere them firmly.
Drain piping located indoors should always be insulated by wrapping with locally
purchased insulation (foamed polyethylene with a thickness of 10 mm or more).
The drain piping should have a downward gradient (1/50 or more), and should be
secured using pipe hanging equipment to avoid creating hills or traps partway.
Note that if the main unit
is not level or if the
height relative to the
ceiling surface is not
appropriate, water may
leak or condense around
the discharge vent.
is not level or if the
height relative to the
ceiling surface is not
appropriate, water may
leak or condense around
the discharge vent.
Hold the half-union with a
wrench, and do not rotate
the male side.
wrench, and do not rotate
the male side.
Absolutely do not install and
extend the drain piping from the
main unit drain water outlet
horizontally or upward or raise it
20cm or more. Doing so may
result in poor drainage or cause
of drain motor failure.
extend the drain piping from the
main unit drain water outlet
horizontally or upward or raise it
20cm or more. Doing so may
result in poor drainage or cause
of drain motor failure.
Tighten the refrigerant piping using the torque
shown in the table to the right.
Cover the piping joint with piping insulation 1 and
tie the insulation firmly using two bands 2 on both
sides. Be sure to adhere the insulation closely so
that there is no gap between the main unit and the
piping insulation.
When the relative humidity inside the ceiling
(indoors) is thought to exceed 80% such as in a
new building during the rainy season or a new
reinforced concrete structure, moisture may
condense on the outer surface of the piping
insulation. In this case be sure to add further
insulation to the refrigerant piping.
shown in the table to the right.
Cover the piping joint with piping insulation 1 and
tie the insulation firmly using two bands 2 on both
sides. Be sure to adhere the insulation closely so
that there is no gap between the main unit and the
piping insulation.
When the relative humidity inside the ceiling
(indoors) is thought to exceed 80% such as in a
new building during the rainy season or a new
reinforced concrete structure, moisture may
condense on the outer surface of the piping
insulation. In this case be sure to add further
insulation to the refrigerant piping.
Liquid side
ø6.35 (1/4")
Gas side
ø9.52 (3/8")
Pipe diameter
Tightening
torque
18N • m
(1.8 kgf • m)
42N • m
(4.2 kgf • m)
Installation Dimensions
(Unit: mm)
• Select the unit position and airflow direction so that the
cool and warm air spreads throughout the whole room.
• Secure the hanging bolts (M10, locally purchased) firmly
in the manners shown below in a location that is
capable of supporting the unit weight.
capable of supporting the unit weight.
• When the ceiling materials insufficient strength, it may
be necessary to make an opening in the ceiling and add
a framework or other reinforcing structure to maintain
the levelness of the ceiling and prevent ceiling vibration.
Consult a construction or interior contractor for details.
a framework or other reinforcing structure to maintain
the levelness of the ceiling and prevent ceiling vibration.
Consult a construction or interior contractor for details.
Decorative grille
dimensions
Ceiling opening
dimensions
Hanging bolt pitch
dimensions
Main unit
dimensions
Ceiling depth
dimension
1070
× 460
1010
× 390
830
× 240
H185
× W770 × D360
190 or more
Attach the nuts and washers to the
hanging bolts, then lift up and hook
the main unit onto the hanging
fixtures.
Adjust the lower surface of the
indoor unit relative to the ceiling
surface as shown in the illustration
below.
Check the levelness using a level or
a vinyl hose filled partially with
water before tightening the nuts.
hanging bolts, then lift up and hook
the main unit onto the hanging
fixtures.
Adjust the lower surface of the
indoor unit relative to the ceiling
surface as shown in the illustration
below.
Check the levelness using a level or
a vinyl hose filled partially with
water before tightening the nuts.
Should some obstacle prevent the drain piping from being extended
smoothly, the drain piping can be raised outside the main unit as
shown in the illustration below.
smoothly, the drain piping can be raised outside the main unit as
shown in the illustration below.
Check the drainage Check after connecting the power supply.
Pour approximately 300 to 400 cc of water into the drain pan of the main unit.
(Pour the water from a squeeze bottle or other vessel as shown in the illustration
below.)
Press the “DRAIN TEST” switch located on the control box to start the drain
motor, and check that the water drains normally.
(The drain motor operates for approximately 5 minutes and then stops automatically.)
(Pour the water from a squeeze bottle or other vessel as shown in the illustration
below.)
Press the “DRAIN TEST” switch located on the control box to start the drain
motor, and check that the water drains normally.
(The drain motor operates for approximately 5 minutes and then stops automatically.)
CAUTION
CAUTION
CAUTION
Installation Dimensions
4
Connecting the Drain Piping
6
7
Installing the Indoor Unit
5
20 cm
or less
or less
7 cm
or less
or less
VP20 elbow VP20 pipe
Upward
gradient
or level
gradient
or level
Connect the VP20 elbow directly
to the main unit outlet.
to the main unit outlet.
Drain joint 7
Trap
No insulation
Insulation (thickness
10 mm or more)
Downward gradient
1/50 or more
1/50 or more
Rise
Hill
Downward gradient
1/50 or more
1/50 or more
0 2 mm
0 2 mm
Ceiling surface
Hanging bolt (M10)
(Locally Purchased)
(Locally Purchased)
Hexagonal nut (M10)
(Locally Purchased)
(Locally Purchased)
Flat washer
(Locally Purchased)
(Locally Purchased)
135
55
30
100
70
Refrigerant piping
(gas side) 3/8"
(gas side) 3/8"
Refrigerant piping
(liquid side) 1/4"
(liquid side) 1/4"
Drain connection port
(connect to VP20)
(connect to VP20)
185
190
95
168
or more
145
30
36.5
770
505
1010
30
505
90
Ceiling opening
415
15
30
415
11
30
Grille center
Hanging bolt
770 Main unit
175
200
125
185
860
115
190
75
67
72
Grille
Control box position
Connecting cable
Insertion position
Insertion position
Ceiling opening
230
230
1070 Grille
75
Discharge vent
(lower surface)
(lower surface)
60
40
60
390
240 Hanging bolt
360 Main unit
460
40
30
830
Bands 2
Adhere closely
Piping
insulation
insulation
Insulation
(locally purchased)
Thickness:
8 mm or more
Main
unit
unit
Half-union
Flare nut
Wrench
Torque wrench
for flare nuts
for flare nuts
(Auxiliary pipe)
(17 mm and 12 mm end
wrench or adjustable spanner)
wrench or adjustable spanner)
(Connection pipe)
Female side
Male side
Drain pan
“DRAIN TEST”
switch
“AUTO” switch
switch
“AUTO” switch
Intake side
Squeeze bottle
Airflow direction
control vanes
Hanging
bolt M10
bolt M10
Ceiling surface
80
Reinforcing materials
(60 to 90 mm square)
(60 to 90 mm square)
Roof beam
Appro
x.
Hanging
bolt M10
bolt M10
Insert hole-in
anchor, etc.
anchor, etc.
Ceiling surface
80
Appro
x.
1
CS
-M
-M
E
7C
B
1P
/
/
C
S
-M
E
10CB1
P
/
CS
-M
E
-M
E
12CB1
P
/
CS
-M
E
-M
E
14CB1
P
/
CS
-M
E
-M
E
10CD3
P
/
CS
-M
-M
E
14
CD3P
32
Click on the first or last page to see other CS-ME7CB1P / CS-ME10CB1P / CS-ME12CB1P / CS-ME14CB1P / CS-ME10CD3P / CS-ME14CD3P service manuals if exist.