Air Circulation Mode Operation Time Diagram
Standard for Determining Operation Mode
8.3. Air Circulation Mode Operation
  • 
When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences at low
airflow volume. It stops when the temperature drops to 2°C below the setting temperature.
8.4. Automatic Mode Operation
  • 
Indoor fan operates at Lo fan speed for 20 seconds.
  • 
After judging indoor air temperature, the operation mode is determined and operation continued at the mode determined.
  • 
After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation includes
Cooling mode operation.
  • 
Room temperature adjustment.
The following are added to the setting temperature specified as above.
  • 
The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX2 at indoor
electronic controller.
37
CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE
Cooling or Soft Dry Operation
When you press the SLEEP Mode, the following movement will
start to avoid overcooling.
  • 
When
the
room
temperature
reaches
the
setting
temperature or after 1 hour of operation, sleep shift
operation starts and the airflow volume will automatically
change to low.
  • 
The setting temperature will be risen by 0.5°C at the start of
operation and by 0.5°C one hour later.
  • 
The operation will stop after 8 hours.
8.5. Sleep Mode Auto Operation
8.6. Powerful Mode Operation
  • 
Purpose of this operation is to obtain the setting temperature quickly.
  • 
When the Powerful Mode is set, the set temperature will be automatically decreased 3°C against the present setting
temperature.
This operation automatically will be running under Super High Fan speed.
  • 
Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically swing down 10° lower than previous setting.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
  • 
Powerful Mode will operate for 15 minutes only.
  • 
Powerful Mode will stop if:-
- Powerful mode button is pressed again.
- Stopped by ON / OFF switch.
- Timer OFF activates.
- Economy mode button is pressed.
- Sleep mode is pressed.
- Operation mode button is changed.
8.7. Economy Mode Operation
  • 
Purpose of this operation is to save or reduced electrical power consumption of the room air conditioner.
  • 
When the Economy Mode is set, the set temperature will be automatically increased 0.5°C against the preset setting
temperature. This operation automatically will be running under Random Fan speed.
(Refer operation details no. 8.9)
  • 
Vertical Airflow Direction:-
In “Manual” or “Auto” setting, the vane will automatically change to Auto Air Swing.
  • 
Economy Mode will stop if:-
- Economy Mode button is pressed again.
- Stopped by ON / OFF switch.
- Timer OFF activates.
- Powerful mode button is pressed.
- Auto or Manual air swing button is pressed.
- Fan Speed control button is pressed.
- Sleep Mode button is pressed ON.
- Operation Mode is changed.
38
CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE
8.8. Random Auto Restart Control
  • 
If there is a power failure, operation will be automatically restarted after 3 to 5 1/2 minutes when the power is resumed.
It will start with previous operation mode and airflow direction.
  • 
Restart time is decided randomly using 4 parameter:-
Intake air temperature, setting temperature, fan speed and Air Swing Blade position.
  • 
Auto Restart Control is not available when Timer or Sleep Mode is set.
  • 
This control can be omitted by open the circuit of JX1. (Refer Circuit Diagram)
8.9. Indoor Fan Speed Control
  • 
Auto Fan Speed Control
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
  • 
Manual Fan Speed Control
Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection button.
Random Fan Speed
The fan is turning at pattern A or B or C randomly, for an interval of 10” each during Random Fan Speed.
39
CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE
Airflow Direction Auto-Control
  • 
When set a Airflow Direction Auto-Control with remote
control, the louver swings up and down as shown in the
diagram.
  • 
The louver does not swing when the Indoor Fan stops
during operation.
  • 
When stopped with remote control, the discharge vent is
closed with the louver.
Airflow Direction manual Control
  • 
When the manual Airflow Direction Selection Button is
pressed, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in
the diagram.
The louver can be adjusted by pressing the button to the
desired louver position.
  • 
When the remote control is used to stop the operation, the
discharge vent is closed with airflow direction louver.
8.10. Airflow Direction Control
1. There is no swinging while indoor fan is stopped during Cooling and Soft Dry operation.
2. In Air Circulation operation, when the intake air temperature reaches set temperature, the airflow direction is changed from upper limit to
lower limit. When the intake air temperature falls to 2°C lower than set temperature, the airflow direction is changed from lower limit to
upper limit.
8.11. Delay ON Timer Control
  • 
When the Delayed ON Timer is set by using the remote control, the unit will start operate slightly before the set time, so that
the room will reach nearly to the set temperature by the desired time.
  • 
For Cooling and Soft Dry mode, the operation will start 15 minutes before the set time.
  • 
For Automatic mode, the indoor fan will operate at Lo speed for 20 seconds, 15 minutes before the set time to detect the intake
air temperature to determine the operation mode. The operation indication lamp will blink at this time.
8.12. Remote Control Signal Receiving Sound
  • 
Long beep sound will be heard when:-
  − 
Stopping the Air Conditioner using ON/OFF switch.
  − 
Stopping the Sleep Mode.
  − 
Stopping the Powerful Mode.
  − 
Stopping the Economy Mode.
  • 
Short beep sound will be heard for others.
  • 
To switch off the beep sound:-
Press the “Automatic Operation Button” continuously for 10 seconds or more (“beep” “beep” will be heard at the 10th second).
Repeat the above if you want to switch ON the beep sound.
However, if the “Automatic Operation Button” has been pressed the Automatic cooling operation will be activated.
If you do not require this operation, you may change it by using the remote control.
40
CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE
Page of 126