DOWNLOAD Panasonic CS-MC95KE / CS-MC125KE / CS-MC76KE / CS-MC126KE / CU-MC145KE / CU-MC185KE / CU-MC205KE / CU-MC245KE / CU-MC196KE Service Manual ↓ Size: 13.02 MB | Pages: 126 in PDF or view online for FREE

Model
CS-MC95KE CS-MC125KE CS-MC76KE CS-MC126KE CU-MC145KE CU-MC185KE CU-MC205KE CU-MC245KE CU-MC196KE
Pages
126
Size
13.02 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / SPLIT TYPE
File
cs-mc95ke-cs-mc125ke-cs-mc76ke-cs-mc126ke-cu-mc145.pdf
Date

Panasonic CS-MC95KE / CS-MC125KE / CS-MC76KE / CS-MC126KE / CU-MC145KE / CU-MC185KE / CU-MC205KE / CU-MC245KE / CU-MC196KE Service Manual ▷ View online

Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Save Control
Starting Current Control
Anti-Freezing Control
  • 
If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
  • 
Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Compressor Reverse Rotation Protection Control
8 Operation Details
8.1. Cooling Mode Operation
  • 
When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
  • 
When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
  • 
The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
  • 
When the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
second later.
  • 
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
s
T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
33
CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE
Automatic Fan Speed Mode
Cooling Operation Time Diagram
When Automatic Fan Speed is selected at Remote Control during cooling operation.
  • 
Fan speed rotates in the range of Hi to Me.
  • 
Deodorizing Control.
34
CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE
Time Delay Safety Control
Starting Current Control
Anti-Freezing Control
Compressor Reverse Rotation Protection Control
Automatic Fan Speed Mode
8.2. Soft Dry Mode Operation
  • 
The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
  • 
During Soft Dry operation, the Indoor Fan will operate at low speed.
  • 
The operation will be switched on and off for up to 10 minutes “ON” and 6 minutes “OFF”. Once Soft Dry operation is turned
off, it stops for 6 minutes.
  • 
Once the compressor stops, it will not start for 3 minutes during Cooling operation.
  • 
Same as Starting Current Control for Cooling Mode operation.
  • 
Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)
  • 
Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting
is valid during compressor stops.)
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
  • 
Fan speed off and on at Lo speed.
  • 
Deodorizing Control.
35
CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE
Soft Dry Operation Time Diagram
36
CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE
Page of 126
Display

Click on the first or last page to see other CS-MC95KE / CS-MC125KE / CS-MC76KE / CS-MC126KE / CU-MC145KE / CU-MC185KE / CU-MC205KE / CU-MC245KE / CU-MC196KE service manuals if exist.