2.
Protection Control For Cooling & Soft Dry
Fan Speed
Shift
Hi
2 rank down
Me+
3 rank up
Me
unchange
Me
-
unchange
Lo
2 rank up
a. Anti-Freezing Control
  • 
When the temperature of the indoor heat exchanger becomes low, the compressor operating frequency is reduced and
stopped when the temperature falls to lower than 2°C continuously for 6 minutes. This is to prevent freezing of indoor heat
exchanger. When the temperature rises to 10°C or above, the compressor restarts with 3 minutes. The compressor
operating frequency will resume to normal when the temperature reaches 14°C.
  • 
Indoor fan speed will increase when the temperature falls and it will resume to original speed when the temperature
increases to 14°C for 5 minutes continuously.
Note: The above phenomenon occurs when the fan is running at Me+ or below.
b. Anti-Dew Formation Control
  • 
When the following conditions occurs for 20 minutes continuously, anti-dew formation is controlled:
 1. Indoor intake air temperature is 24°C or above.
 2. Outdoor air temperature is less than 30°C.
 3. Remote control setting temperature is less than 25°C.
  • 
During anti-dew formation control, compressor operates at 36 Hz (CS-G95KE) or 44 Hz (CS-G125KE) and airflow direction
vane move slightly (as shown in Airflow Direction Control). Indoor fan speed will shift as below:
  • 
This control is cancelled immediately when either condition 1-3 as written above is changed, or remote control setting
temperature or fan speed is changed.
45
CS-G95KE CU-G95KE / CS-G125KE CU-G125KE
C. Anti-Fog Discharge Control
  • 
The compressor operating frequency is regulated by operation time to prevent fog discharged from indoor until as shown in
the table below.
Compressor operating frequency
Operation
Time, T (min)
0
T < 30
50Hz
70Hz
30
T < 90
46Hz
64Hz
T
90
43Hz
58Hz
Model No.
CU-G95KE
CU-G125KE
Note:
  • 
Indoor fan is running at Me
-
or below.
  • 
After 420 minutes from the start of operation, the operation timer counting is restarted from “0”.
d. High Pressure Control at Minimum Frequency Control
  • 
When the outdoor air temperature increases to 38.6°C, compressor operating frequency reduces to minimum of 31 Hz.
Compressor operating frequency will resume to normal when outdoor air temperature decreases to 37.8°C.
46
S-G95KE CU-G95KE / CS-G125KE CU-G125KE
3.
Protection Control For Heating Operation
a. Intake Air Temperature Control
  • 
When the intake air temperature is 10°C or above and remote control setting fan speed is less than Me
-
, the compressor
operates maximum at 71 Hz (CU-G95KE) or 90 Hz (CU-G125KE).
  • 
When the intake air temperature is 30°C and above, the compressor operates maximum at 71 Hz (CU-G95KE) or 90 Hz
(CU-G125KE).
b. Outdoor Air Temperature Control
  • 
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram
below. This control will begin 50 seconds after the compressor starts.
C. High Pressure Control
  • 
The compressor operating frequency is regulated in accordance to the indoor heat exchanger temperature.
47
CS-G95KE CU-G95KE / CS-G125KE CU-G125KE
9 Operating Instructions
This room air conditioner must be earthed.
Improper grounding could cause
electric shock.
Do not install the unit in a place where there
may be explosive gas leaks.
Gas leaks near the unit could
cause fires.
Ensure that drainage piping is connected
properly.
Otherwise, water will leak out.
SAFETY PRECAUTIONS
Do not install, remove and reinstall the unit yourself.
Improper installation will cause leakage, electric shock or fire. Please consult an authorized dealer or
specialist for the installation work.
Warning
:
This sign warns of death or serious injury.
Caution
:
This sign  warns of injury or damage to property.
!
!
The instructions to be followed are classified by the following symbols:
This symbol (with a white background) denotes an action that is
PROHIBITED.
These symbols (with a black background) denotes an action that is
COMPULSORY.
OFF
Before operating, please read the following “Safety Precautions” carefully.
To prevent personal injury, injury to others and property damage, the following instructions must be followed.
Incorrect operation due to ignoring of instructions will cause harm or damage, the seriousness of which is
classified as follows:
!
 
Caution
Warning
Installation precautions
48
S-G95KE CU-G95KE / CS-G125KE CU-G125KE