10.3.3. Installation of indoor unit
POSITION OF SUPENSION BOLT
 • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
 • Install the unit learning to a drainage hole side as a figure for easy water drainage.
45
 1. Brazing for piping.
 a. Execute brazing before tightening the flare nut.
 b. Brazing must be executed while blowing nitrogen gas.
(This prevents generation of oxidized scale in copper
pipe.)
 2. When there is a lot of brazings for long piping, install a
strainer midway of the piping. (The strainer is locally
supplied.)
 3. Use clean copper pipe with inner wall surface free from mist
and dust. Blow nitrogen gas or air to blow off dust in the
pipe before connection.
 4. Form the piping according to its routing. Avoid bending and
bending back the same piping point more than three times.
(This will result in hardening of the pipe).
 5. After deforming the pipe, align centers of the union fitting of
the indoor unit and the piping, and tighten them firmly with
wrenches.
 6. Connect pipe to the service valve or ball valve which is
located below the outdoor unit.
 7. After completed the piping connection, be sure to check if
there is gas leakage in indoor and outdoor connection.
Flare nut fastening torque N.m (kgf.cm)
ø6.35 mm 18 (180)
ø12.7 mm
55 (560) ø19.05 mm 100 (1020)
ø9.52 mm 42 (430) ø15.88 mm 65 (660)
 • The unit has two drainage holes at both side.
The drainage hole without connection needs seal and thermal
insulation with accessories.
 • Always lay the drain with downward inclination (1/50 to 1/100).
Prevent any upward flow or reverse flow in any part.
 • 5mm or thicker formed thermal insulator shall always be
provided for the drain pipe.
 • Confirm the red mark of the union (thin side) is always at
lower direction after connecting piping.
Liquid side piping
Gas side piping
ø9.52 mm
ø15.88 mm
10.3.4. Refrigerant piping
 • Refrigerant is charged to the outdoor unit. For details, see the manual for installation work of outdoor unit. (Additional charging,
etc.)
Vacuum drying
After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit.
The vacuum drying must be carried out by using the service ports of both the liquid and gas side valves.
CAUTION
Use two wrenches and tighten with regular torque.
10.3.5. Indoor unit drain piping
46
10.3.6. Heat Insulation
Caution
Be sure to perform heat insulation on the drain, liquid and gas piping. Imperfection in heat insulation work leads to water leakage.
 1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C).
 2. Precautions in high humidity circumstance.
This air conditioner has been tested according to the “JIS Standard Conditions with Mist” and have been confirmed that there
are no faults. However, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 23°C),
water drops are liable to fall. In this case, add heat insulation material according to the following procedure:
 • Heat insulation material to be prepared... Adiabatic glass wool with thickness 10 to 20mm.
 • Stick glass wool on all air conditioners that are located in ceiling atmosphere.
 • In addition to the normal heat insulation (thickness: more than 8mm) for refrigerant piping (gas piping: thick piping) and drain
piping, add a further of 10mm to 30mm thickness material.
Wall seal
 • When the outdoor unit is installed on a higher position than the indoor unit, install the trap so as not to instill rain water into
the wall by transmitting in piping.
 • Stuff the space among piping, the electric wire, and the drain hose with “Putty” and seal the penetration wall hole.
Make sure that rain water do not instill into the wall.
*Put the incision at the trap part of the heat insulator (for water drain)
 3. The duct connection of the air outlet needs thermal insulation.
47
10.3.7. Electrical wiring
As to main power source and cable size of outdoor unit, read the installation manual attached to the outdoor unit.
The units must be installed in accordance with applicable national and local regulations.
Warning
The units installed by a professional installer must be supplied from a dedicated electrical circuit.
All electrical work must be carried out by a qualified technician according to proper technical standards for electrical work and
according to installation manual for installation work.
If circuit with insufficient capacity are used, or if electrical work is not carried out properly, electric shocks or fire may result.
Caution
Be sure to install a current leakage breaker or circuit breaker to the main power supply, otherwise electric shocks may result.
Caution
Be sure to connect the unit to secure earth connection. (with an earth resistance of 100
Ω or less)
If the earthing work is not carried out properly, electric shocks may result.
Warning
Wiring shall be connected securely using specified cables and fix them securely so that external force of the cables may not
transfer to the terminal connection section. Imperfect connection and fixing leads to fire, etc.
 1. Select a power source that is capable of supplying the current required by the air conditioner.
 2. Feed the power source to the unit via a distribution switch board designed for this purpose, the switch should disconnected all
poles with a contact separation of at least 3 mm.
 3. Always ground the air conditioner with a grounding wire and screw to meet the LOCAL REGULATIONS.
 4. Be sure to connect the wires correctly to terminal board with connecting the crimp type ring terminal to the wires.
 5. Be sure to turn off the main power before installing and connecting the remote controller.
Note
If momentarily turning on the power supply for both the indoor and outdoor units, do not turn the power off after at least 1 minute has
passed. (For the system’s automatic setting.)
Turning off the power supply on the way may cause an abnormal operation.
 • Use the standard power cord for Europe (such as H05RN-F or H07RN-F which conforms to CENELEC (HAR) rating
specifications) or use the cables based on IEC standard. (245IEC57, 245IEC66)