DOWNLOAD Panasonic CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CS-F50DD2E5 / CU-L24DBE5 / CU-L28DBE5 / CU-L34DBE5 / CU-L43DBE5 / CU-L50DBE8 Service Manual ↓ Size: 24.74 MB | Pages: 127 in PDF or view online for FREE

Model
CS-F24DD2E5 CS-F28DD2E5 CS-F34DD2E5 CS-F43DD2E5 CS-F50DD2E5 CU-L24DBE5 CU-L28DBE5 CU-L34DBE5 CU-L43DBE5 CU-L50DBE8
Pages
127
Size
24.74 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-f24dd2e5-cs-f28dd2e5-cs-f34dd2e5-cs-f43dd2e5-cs.pdf
Date

Panasonic CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CS-F50DD2E5 / CU-L24DBE5 / CU-L28DBE5 / CU-L34DBE5 / CU-L43DBE5 / CU-L50DBE8 Service Manual ▷ View online

 1 
SERVICE INFORMATION 
3
 1.1. 
Example of trouble at test operation 
3
 1.2. 
Caution of test operation 
3
 1.3. 
Caution during automatic address setting 
3
 1.4. 
Operation Range 
3
CS-F24DD2E5 CU-L24DBE5
CS-F28DD2E5 CU-L28DBE5
CS-F34DD2E5 CU-L34DBE5
CS-F43DD2E5 CU-L43DBE5
CS-F50DD2E5 CU-L50DBE8
 2 
FEATURES 
4
 2.1. 
Hide-away type 
4
 2.2. 
Outdoor unit 
4
 2.3. 
A brand-new control method using the latest in technology
 
5
Air Conditioner
CONTENTS
 Page 
Page
ORDER NO. MAC0504057C2
 3 
SPECIFICATION 
6
 3.1. 
CS-F24DD2E5 CU-L24DBE5 
6
 3.2. 
CS-F28DD2E5 CU-L28DBE5 
7
 3.3. 
CS-F34DD2E5 CU-L34DBE5 
8
 3.4. 
CS-F43DD2E5 CU-L43DBE5 
9
 3.5. 
CS-F50DD2E5 CU-L50DBE8 
10
 4 
DIMENSIONS 
11
 4.1. 
CS-F24DD2E5 CS-F28DD2E5 
11
 4.2. 
CS-F34DD2E5 CS-F43DD2E5 CS-F50DD2E5 
12
 4.3. 
CU-L24DBE5 CU-L28DBE5 
13
 4.4. 
CU-L34DBE5 CU-L43DBE5 CU-L50DBE8 
14
 5 
REFRIGERATION CYCLE 
15
 6 
BLOCK DIAGRAM 
16
 6.1. 
CS-F24DD2E5 CS-F28DD2E5 CS-F34DD2E5 CS-
F43DD2E5 CS-F50DD2E5 
16
 6.2. 
CU-L24DBE5 CU-L28DBE5 
17
 6.3. 
CU-L34DBE5 CU-L43DBE5 
18
 6.4. 
CU-L50DBE8 
19
 7 
WIRING DIAGRAM 
20
 7.1. 
CS-F24DD2E5 CS-F28DD2E5 CS-F34DD2E5 CS-
F43DD2E5 CS-F50DD2E5 
20
 7.2. 
CU-L24DBE5 CU-L28DBE5 
21
 7.3. 
CU-L34DBE5 CU-L43DBE5 
22
 7.4. 
CU-L50DBE8 
23
 8 
WIRED REMOTE CONTROL OPERATING INSTRUCTIONS  24
 8.1. 
Name and function of each part 
24
 8.2. 
Remote control - display 
25
 8.3. 
Remote control - panel 
26
 8.4. 
How to set remote control day and time 
27
 8.5. 
How to select the timer 
27
 8.6. 
Daily timer setting 
28
 8.7. 
Weekly timer setting 
29
 9 
OPERATION CONTROL 
31
 9.1. 
Operation mode 
31
 9.2. 
Compressor start control 
31
 9.3. 
Cooling operation 
31
 9.4. 
Heating mode operation 
33
 9.5. 
Odour removing operation 
35
 9.6. 
Energy save operation 
36
 9.7. 
Outdoor fan remaining heat removal control 
37
 9.8. 
Crank case heater control 
37
 9.9. 
Valve error 
37
 9.10. Pump down operation 
37
 10 INSTALLATION INSTRUCTION 
39
 10.1. Pipe length 
39
 10.2. Position of the centre gravity 
41
 10.3. Indoor unit installation 
42
 10.4. Outdoor unit installation 
52
 10.5. Wired remote controller installation 
63
 10.6. Twin systems installation 
70
 11 INSTALLATION & SERVICING AIR CONDITIONER 
71
 11.1. Outline 
71
 11.2. Tools for installing/servicing refrigerant piping 
72
 11.3. Refrigerant piping work 
76
 11.4. Installation, transferring, servicing 
78
 12 TROUBLE SHOOTING GUIDE 
82
 12.1. For standard installation 
82
 12.2. During twin operation 
84
 12.3. During group control operation 
86
 12.4. Address setting for twin system 
87
 12.5. Address setting for group control system 
88
 12.6. Wiring mistake prevention 
90
 12.7. Test operation and self diagnosis 
91
 12.8. Emergency operation 
94
 12.9. Self-diagnosis 
95
 13 TECHNICAL DATA 
97
 13.1. Sound data 
97
 13.2. Sound measurement point 
103
 13.3. Discharge and suction pressure 
104
 13.4. Capacity and power consumption 
109
 13.5. Fan performance 
136
 13.6. Safety device 
141
 13.7. Operating characteristics 
142
 14 REPLACEMENT PARTS 
143
 14.1. Indoor unit 
143
 14.2. Outdoor unit 
145
 15 ELECTRONIC CIRCUIT DIAGRAM 
157
 15.1. Indoor unit 
157
 15.2. Outdoor unit 
161
 15.3. Wired remote control 
173
 15.4. Print pattern 
174
2
1 SERVICE INFORMATION
Notice of Address setting for NEW Duct / NEW Outdoor Unit.
The new Duct Type / New Outdoor models are possible to have address setting for twin control by automatic when main
power supply is switched on.
(Manual address setting is also possible by using Dip switch on Indoor unit P.C. board.) However, this address setting is only
possible when made proper wiring connection and also Indoor unit should be original virgin unit
.
1.1. Example of trouble at test operation
If found out as following phenomenon at test operation on site, it may have possibility of wrong address setting.
Therefore, please ensure of the address setting.
 1. LCD display of wired remote control had not illuminate although the main power supply switch is ‘on’.
 2. LCD display had indicated as normal illumination when power supply switch is ‘on’, however outdoor unit cannot be operated.
(But, it is necessary to take 3 to 5 minutes for outdoor unit to start from the timing of remote control ON/OFF switch is ‘on’.)
 3. P.C. board had memorized wrong setting information.
 a. If main power supply is switched ‘on’ with the wrong connection.
 b. When changing the connection or combination of units due to re-installation etc.
 • When changing the system from twin control to normal one to one system.
 • When making the replacement of units as master and slave etc.
1.2. Caution of test operation
Do not touch the remote control switch and do not change any wirings for one minute when the main power supply switch is ‘on’.
(Because the unit is having automatic address setting during the first one minute.)
1.3. Caution during automatic address setting
When main power supply switch is ‘on’, the P.C. board will automatically memorized the connecting system.
Consequently, when initial power supply is ‘on’, there will not be interchangeability of units even of the same type and same
capacity unit. Therefore unable to connect the unit to another system.
1.4. Operation Range
The applicable voltage range for each unit is given in “the following table”. The working voltage among the three phases must be
balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the
rated voltage.
1.4.1. Power Supply
Model
CU-
Unit Main Power
Applicable Voltage
Phase, Volts
Hz
Maximum
Minimum
L24DBE5
L28DBE5
L34DBE5
L43DBE5
1~220
50
242
198
1~230
50
253
207
1~240
50
264
216
L50DBE8
3N~380
50
418
342
3N~400
50
440
360
3N~415
50
457
374
1.4.2. Indoor and Outdoor Temperature
Model 50Hz ... L24DBE5, L28DBE5, L34DBE5, L43DBE5, L50DBE8
Operating
Hz
Indoor Temp. (D.B./W.B.) (°C)
Outdoor Temp. (D.B./W.B.) (°C)
Maximum
Minimum
Maximum
Minimum
Cooling
50
32/23
21/15
43/-
-15/-
Heating
50
27/-
16/-
24/18
-20/-
3
2.1. Hide-away type
2.1.1. Thin, lightweight design
 • The unit has a low height, so it allows installation in limited
ceiling spaces. The lightweight, attractive design simplifies
installation, and matches virtually all room interiors.
2.1.2. Flexible installation
 • The powerful airflow enables a longer duct to be used.
Since the air outlet can be installed away from the main
unit, a variety of air conditioner layouts become possible.
2.1.3. Easy maintenance
 • Maintenance works can be done from the underside of the
indoor unit.
2.2. Outdoor unit
2.2.1. Flexible installation in smaller
spaces
 • Space-saving outdoor unit with the improvement of the
outdoor unit fan makes it possible to install the outdoor unit
into a smaller space where the conventional model cannot
be installed.
 • Long pipe design with a maximum piping length of 50m.
 • Additional charging of refrigerant are not required for 30m
of pipe length.
 • Flexible 4-way piping.
 • Centralized drain method gather multiple outdoor units’
drain pipes into a single drain pipe to make installation
easier and also improve appearance.
 • Side-by-side continuous installation is possible even for
outdoor units with different capacities.
2.2.2. Quiet, efficient design
 • A host of silencing technologies achieves super-quiet
operation.
 • The noise-suppressing winglet fan is a result of new
research into vane design theory. The unique curved shape
suppresses the generation of vortexes, thus reduces air
flows noise.
 • Operating efficiency is improved and energy consumption is
reduced.
2.2.3. Low ambient cooling operation
 • The unit can set for cooling even when the outdoor
temperature drops to -5°C for regular cooling condition.
 • However, cooling operation at -15°C is possible in non-
residential computer rooms, etc., where the temperature is
not less than 21°C and humidity is not more than 45%.
2 FEATURES
4
Page of 127
Display

Panasonic CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CS-F50DD2E5 / CU-L24DBE5 / CU-L28DBE5 / CU-L34DBE5 / CU-L43DBE5 / CU-L50DBE8 Service Manual ▷ Download

  • DOWNLOAD Panasonic CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CS-F50DD2E5 / CU-L24DBE5 / CU-L28DBE5 / CU-L34DBE5 / CU-L43DBE5 / CU-L50DBE8 Service Manual ↓ Size: 24.74 MB | Pages: 127 in PDF or view online for FREE
  • Here you can View online or download the Service Manual for the Panasonic CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CS-F50DD2E5 / CU-L24DBE5 / CU-L28DBE5 / CU-L34DBE5 / CU-L43DBE5 / CU-L50DBE8 in PDF for free, which will help you to disassemble, recover, fix and repair Panasonic CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CS-F50DD2E5 / CU-L24DBE5 / CU-L28DBE5 / CU-L34DBE5 / CU-L43DBE5 / CU-L50DBE8 Air Conditioner. Information contained in Panasonic CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CS-F50DD2E5 / CU-L24DBE5 / CU-L28DBE5 / CU-L34DBE5 / CU-L43DBE5 / CU-L50DBE8 Service Manual (repair manual) includes:
  • Disassembly, troubleshooting, maintenance, adjustment, installation and setup instructions.
  • Schematics, Circuit, Wiring and Block diagrams.
  • Printed wiring boards (PWB) and printed circuit boards (PCB).
  • Exploded View and Parts List.