Panasonic CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CS-F50DD2E5 / CU-L24DBE5 / CU-L28DBE5 / CU-L34DBE5 / CU-L43DBE5 / CU-L50DBE8 Service Manual ▷ View online
1
SERVICE INFORMATION
3
1.1.
Example of trouble at test operation
3
1.2.
Caution of test operation
3
1.3.
Caution during automatic address setting
3
1.4.
Operation Range
3
CS-F24DD2E5 CU-L24DBE5
CS-F28DD2E5 CU-L28DBE5
CS-F34DD2E5 CU-L34DBE5
CS-F43DD2E5 CU-L43DBE5
CS-F28DD2E5 CU-L28DBE5
CS-F34DD2E5 CU-L34DBE5
CS-F43DD2E5 CU-L43DBE5
CS-F50DD2E5 CU-L50DBE8
2
FEATURES
4
2.1.
Hide-away type
4
2.2.
Outdoor unit
4
2.3.
A brand-new control method using the latest in technology
5
Air Conditioner
CONTENTS
Page
Page
ORDER NO. MAC0504057C2
3
SPECIFICATION
6
3.1.
CS-F24DD2E5 CU-L24DBE5
6
3.2.
CS-F28DD2E5 CU-L28DBE5
7
3.3.
CS-F34DD2E5 CU-L34DBE5
8
3.4.
CS-F43DD2E5 CU-L43DBE5
9
3.5.
CS-F50DD2E5 CU-L50DBE8
10
4
DIMENSIONS
11
4.1.
CS-F24DD2E5 CS-F28DD2E5
11
4.2.
CS-F34DD2E5 CS-F43DD2E5 CS-F50DD2E5
12
4.3.
CU-L24DBE5 CU-L28DBE5
13
4.4.
CU-L34DBE5 CU-L43DBE5 CU-L50DBE8
14
5
REFRIGERATION CYCLE
15
6
BLOCK DIAGRAM
16
6.1.
CS-F24DD2E5 CS-F28DD2E5 CS-F34DD2E5 CS-
F43DD2E5 CS-F50DD2E5
16
6.2.
CU-L24DBE5 CU-L28DBE5
17
6.3.
CU-L34DBE5 CU-L43DBE5
18
6.4.
CU-L50DBE8
19
7
WIRING DIAGRAM
20
7.1.
CS-F24DD2E5 CS-F28DD2E5 CS-F34DD2E5 CS-
F43DD2E5 CS-F50DD2E5
20
7.2.
CU-L24DBE5 CU-L28DBE5
21
7.3.
CU-L34DBE5 CU-L43DBE5
22
7.4.
CU-L50DBE8
23
8
WIRED REMOTE CONTROL OPERATING INSTRUCTIONS 24
8.1.
Name and function of each part
24
8.2.
Remote control - display
25
8.3.
Remote control - panel
26
8.4.
How to set remote control day and time
27
8.5.
How to select the timer
27
8.6.
Daily timer setting
28
8.7.
Weekly timer setting
29
9
OPERATION CONTROL
31
9.1.
Operation mode
31
9.2.
Compressor start control
31
9.3.
Cooling operation
31
9.4.
Heating mode operation
33
9.5.
Odour removing operation
35
9.6.
Energy save operation
36
9.7.
Outdoor fan remaining heat removal control
37
9.8.
Crank case heater control
37
9.9.
Valve error
37
9.10. Pump down operation
37
10 INSTALLATION INSTRUCTION
39
10.1. Pipe length
39
10.2. Position of the centre gravity
41
10.3. Indoor unit installation
42
10.4. Outdoor unit installation
52
10.5. Wired remote controller installation
63
10.6. Twin systems installation
70
11 INSTALLATION & SERVICING AIR CONDITIONER
71
11.1. Outline
71
11.2. Tools for installing/servicing refrigerant piping
72
11.3. Refrigerant piping work
76
11.4. Installation, transferring, servicing
78
12 TROUBLE SHOOTING GUIDE
82
12.1. For standard installation
82
12.2. During twin operation
84
12.3. During group control operation
86
12.4. Address setting for twin system
87
12.5. Address setting for group control system
88
12.6. Wiring mistake prevention
90
12.7. Test operation and self diagnosis
91
12.8. Emergency operation
94
12.9. Self-diagnosis
95
13 TECHNICAL DATA
97
13.1. Sound data
97
13.2. Sound measurement point
103
13.3. Discharge and suction pressure
104
13.4. Capacity and power consumption
109
13.5. Fan performance
136
13.6. Safety device
141
13.7. Operating characteristics
142
14 REPLACEMENT PARTS
143
14.1. Indoor unit
143
14.2. Outdoor unit
145
15 ELECTRONIC CIRCUIT DIAGRAM
157
15.1. Indoor unit
157
15.2. Outdoor unit
161
15.3. Wired remote control
173
15.4. Print pattern
174
2
1 SERVICE INFORMATION
Notice of Address setting for NEW Duct / NEW Outdoor Unit.
The new Duct Type / New Outdoor models are possible to have address setting for twin control by automatic when main
power supply is switched on.
power supply is switched on.
(Manual address setting is also possible by using Dip switch on Indoor unit P.C. board.) However, this address setting is only
possible when made proper wiring connection and also Indoor unit should be original virgin unit.
possible when made proper wiring connection and also Indoor unit should be original virgin unit.
1.1. Example of trouble at test operation
If found out as following phenomenon at test operation on site, it may have possibility of wrong address setting.
Therefore, please ensure of the address setting.
Therefore, please ensure of the address setting.
1. LCD display of wired remote control had not illuminate although the main power supply switch is ‘on’.
2. LCD display had indicated as normal illumination when power supply switch is ‘on’, however outdoor unit cannot be operated.
(But, it is necessary to take 3 to 5 minutes for outdoor unit to start from the timing of remote control ON/OFF switch is ‘on’.)
3. P.C. board had memorized wrong setting information.
a. If main power supply is switched ‘on’ with the wrong connection.
b. When changing the connection or combination of units due to re-installation etc.
• When changing the system from twin control to normal one to one system.
• When making the replacement of units as master and slave etc.
• When making the replacement of units as master and slave etc.
1.2. Caution of test operation
Do not touch the remote control switch and do not change any wirings for one minute when the main power supply switch is ‘on’.
(Because the unit is having automatic address setting during the first one minute.)
(Because the unit is having automatic address setting during the first one minute.)
1.3. Caution during automatic address setting
When main power supply switch is ‘on’, the P.C. board will automatically memorized the connecting system.
Consequently, when initial power supply is ‘on’, there will not be interchangeability of units even of the same type and same
capacity unit. Therefore unable to connect the unit to another system.
Consequently, when initial power supply is ‘on’, there will not be interchangeability of units even of the same type and same
capacity unit. Therefore unable to connect the unit to another system.
1.4. Operation Range
The applicable voltage range for each unit is given in “the following table”. The working voltage among the three phases must be
balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the
rated voltage.
balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the
rated voltage.
1.4.1. Power Supply
Model
CU-
Unit Main Power
Applicable Voltage
Phase, Volts
Hz
Maximum
Minimum
L24DBE5
L28DBE5
L34DBE5
L43DBE5
L28DBE5
L34DBE5
L43DBE5
1~220
50
242
198
1~230
50
253
207
1~240
50
264
216
L50DBE8
3N~380
50
418
342
3N~400
50
440
360
3N~415
50
457
374
1.4.2. Indoor and Outdoor Temperature
Model 50Hz ... L24DBE5, L28DBE5, L34DBE5, L43DBE5, L50DBE8
Operating
Hz
Indoor Temp. (D.B./W.B.) (°C)
Outdoor Temp. (D.B./W.B.) (°C)
Maximum
Minimum
Maximum
Minimum
Cooling
50
32/23
21/15
43/-
-15/-
Heating
50
27/-
16/-
24/18
-20/-
3
2.1. Hide-away type
2.1.1. Thin, lightweight design
• The unit has a low height, so it allows installation in limited
ceiling spaces. The lightweight, attractive design simplifies
installation, and matches virtually all room interiors.
installation, and matches virtually all room interiors.
2.1.2. Flexible installation
• The powerful airflow enables a longer duct to be used.
Since the air outlet can be installed away from the main
unit, a variety of air conditioner layouts become possible.
unit, a variety of air conditioner layouts become possible.
2.1.3. Easy maintenance
• Maintenance works can be done from the underside of the
indoor unit.
2.2. Outdoor unit
2.2.1. Flexible installation in smaller
spaces
• Space-saving outdoor unit with the improvement of the
outdoor unit fan makes it possible to install the outdoor unit
into a smaller space where the conventional model cannot
be installed.
into a smaller space where the conventional model cannot
be installed.
• Long pipe design with a maximum piping length of 50m.
• Additional charging of refrigerant are not required for 30m
• Additional charging of refrigerant are not required for 30m
of pipe length.
• Flexible 4-way piping.
• Centralized drain method gather multiple outdoor units’
drain pipes into a single drain pipe to make installation
easier and also improve appearance.
easier and also improve appearance.
• Side-by-side continuous installation is possible even for
outdoor units with different capacities.
2.2.2. Quiet, efficient design
• A host of silencing technologies achieves super-quiet
operation.
• The noise-suppressing winglet fan is a result of new
research into vane design theory. The unique curved shape
suppresses the generation of vortexes, thus reduces air
flows noise.
suppresses the generation of vortexes, thus reduces air
flows noise.
• Operating efficiency is improved and energy consumption is
reduced.
2.2.3. Low ambient cooling operation
• The unit can set for cooling even when the outdoor
temperature drops to -5°C for regular cooling condition.
• However, cooling operation at -15°C is possible in non-
residential computer rooms, etc., where the temperature is
not less than 21°C and humidity is not more than 45%.
not less than 21°C and humidity is not more than 45%.
2 FEATURES
4