DOWNLOAD Panasonic CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CS-F50DD2E5 / CU-L24DBE5 / CU-L28DBE5 / CU-L34DBE5 / CU-L43DBE5 / CU-L50DBE8 Service Manual ↓ Size: 24.74 MB | Pages: 127 in PDF or view online for FREE

Model
CS-F24DD2E5 CS-F28DD2E5 CS-F34DD2E5 CS-F43DD2E5 CS-F50DD2E5 CU-L24DBE5 CU-L28DBE5 CU-L34DBE5 CU-L43DBE5 CU-L50DBE8
Pages
127
Size
24.74 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-f24dd2e5-cs-f28dd2e5-cs-f34dd2e5-cs-f43dd2e5-cs.pdf
Date

Panasonic CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CS-F50DD2E5 / CU-L24DBE5 / CU-L28DBE5 / CU-L34DBE5 / CU-L43DBE5 / CU-L50DBE8 Service Manual ▷ View online

Part name
Q’ty
Diagram
Application
Protective
bushing
2
For protecting electrical
wires
Banding
strap
3
For tying electrical wires
together
Heat pump-types only
Part name
Q’ty
Diagram
Application
Drain elbow AS
1
For connecting the drain
pipe (with ring seat)
Warnings
Wiring shall be connected securely using specified cables and
fix them securely so that external force of the cables may not
transfer to the terminal connection section.
Imperfect connection and fixing leads to fire, etc.
Cautions
Carry out Earthing work.
Do not connect the Earth return to the gas pipe,
water line pipe, lightning rod and telephone lines.
Imperfection in Earth return may lead to electric
shock.
Drain piping should be made to ensure secure drainage
according to the manual for installation work and carry out the
thermal insulation to prevent the occurrence of condensation.
Imperfection in piping work leads to water leakage and may
cause the house and property, etc. to become wet
Do not install the unit at the place where the possibility of
inflammable gas leakage exists. If such gas leakages should arise
and the gas builds up around the unit, such situation may lead to
ignition.
Position the indoor unit and outdoor unit, power cords and
indoor/outdoor unit connection cables in a way so that they are
at least 1 meter away from televisions and radios.
This is to avoid problem such as interference with picture and/or
sound. (However, note that depending on the electromagnetic
wave conditions, interference may still occur even if the
separation distance is more than 1 meter.)
Mounting of the earth leakage circuit breaker is required.
Omission in mounting of the earth leakage circuit breaker may
lead to electric shock.
10.4.1. Accessories supplied with outdoor unit
 • The following parts are supplied as accessories with each outdoor unit.
Check that all accessory parts are present before installing the outdoor unit.
10.4.2. Before installation work
 • This product is using new refrigeration (R410A). The basic way of installation work is the same as usual, but water and
impurities should be controlled more strictly than before due to characteristic of refrigerating machine oil. Therefore, selection
of materials to use and processing, storing and brazing need appropriate construction and control.
 1. Tools and materials
There are tools and materials for both new refrigeration and usual refrigeration you can use together and for either two of
them you can use. Use the below for new refrigeration.
 − Vacuum pump (with back flow preventor system)
 − Gas leakage detection warning device
 − Gauge manifold
 − Charge hose
 2. Installation work
 a. Brazing work
Brazing work needs replacing air inside pipe with nitrogen gas in order to prevent oxidation scale from occurring. This
is called nitrogen replacement, and one of very important work in brazing refrigerant piping. (Oxidation preventive is not
possible to use)
53
 b. Prevention measure for refrigerant piping
Prevention measure for refrigerant piping is very important work to prevent water-dust-rubbish from getting in. All piping
terminals needs sealing such as shown below.
Place
Period of work
Method of seal
Outside
More than 1 month
Pinch
Less than 1 month
Pinch or taping
Inside
Not specified
 − How to pinch
Close terminal part of piping with pliers and seal the gap with brazing.
 − How to tape
Seal terminal part of piping with vinyl tape.
 3. Vacuum pumping
The purpose of vacuum pumping work is to remove and dry air inside the piping or nitrogen at air tightness test.
Perform the work carefully.
Caution
Use the vacuum pump with the backflow prevention mechanism to prevent backflow of oil.
Vacuuming time
60 minutes or more
Vacuum pump capacity
60 l/min or more
 4. Refrigerant filling
Refrigerant filling must be done in the state of liquid refrigerant. If this is done in gas refrigerant, the balance of refrigerant
composition will collapse and damage the operation.
54
For the use of a gas cylinder without siphon inside, turn it upside down and use it.
(We recommend manifold with sight glass.)
Caution
Do not use a “CHARGE CYLINDER”.
Caution
As a rule, please collect all existing refrigerants in the system outside the system when the refrigerant leakage occurs by the
system.
After that, please fill new refrigerant of a regulated amount again.
DRY VACUUMING
 • If vacuum pump possible vacuuming until less than -100.7kpa.
 1. Running vacuum pump at both liquid and gas side for more than 1 hour and vacuuming until -100.7kpa.
 2. After that keep the pressure -100.7kpa for 1 hour and confirm the vacuum gauge value not increasing.
 3. If vacuum gauge value is increase, there is possibility of water inside the unit or there is any leakage.
10.4.3. Regarding handling
Handling the unit by hold the handle at compressor side and hold the basepan bottom at fan side.
10.4.4. Selecting the outdoor unit installation locations
 • Select location which satisfies the following condition, and then confirm with the customer that such a place is satisfactory
before installing the outdoor unit.
1.
There should be sufficient ventilation.
2.
The outdoor unit should be sheltered as much as possible from rain and direct sunlight, and the air should be able to move around so
that hot and cold air do not build up.
3.
There should not be animals or plants near the air outlet which could be
adversely affected by hot or cold air coming out from the unit.
4.
The outlet air and operating noise should not be a nuisance to other occupants
nearby.
5.
The location should be able to withstand the full weight and vibration of the
outdoor unit, and it should also be level and safe for the unit to be installed.
6.
The intake and outlet should not be covered.
7.
There should not be danger of flammable gas or corrosive gas leaks.
8.
There should be as little back-ventilation (air blowing directly onto the fan) as
possible.
(If strong wind blows directly onto the fan, it may cause problems with normal
operation.)
 • If you know which direction the prevailing wind comes from during the
operating season, set the outdoor unit at a right-angle to this wind direction,
or so that air outlet faces toward a wall or fence.
 • If there are obstructions near the outdoor unit and the wind direction is not
constant, install an optional air guider.
9.
Do not allow any obstacles near the outdoor unit which will interfere with air flow around the air intake and air outlet.
10. If installing in a location which is prone to snowfall, place the installation base as high as possible, and be sure to install a roof or
enclosure which does not allow snow to accumulate.
11. Avoid installing the unit in places where petroleum products (such as machine oil), salinity, sulphurous, gases or high-frequency noise are
present.
55
12. Be sure to leave enough space around the outdoor unit to maintain proper performance and to allow access for routine maintenance.
 • Allow enough space from any obstacles as shown in Fig. 1.2 below in order to prevent short-circuits from occurring.
(If installing more than one outdoor unit, make the necessary space available as outlined in 13.)
However, there should be at least 1 meter of free space above the unit.
 • The height of any obstacles at the air intake and outlet sides should not be greater than the height of the outdoor unit.
13. If installing more than one outdoor unit, allow enough space around each unit as shown below.
Maintain sufficient space above the unit.
Values inside brackets indicate distances when installing the 4HP - 6HP.
 • The distance given above are the minimum distance required in order to maintain proper performance.
Allow as much space as possible in order to get the best performance from the units.
10.4.5. Transporting and installing the outdoor unit
 • Transporting
 1. The outdoor unit should be transported in its original packaging as close to the installation location as possible.
 2. If suspending the outdoor unit, use a rope or belt, and use cloth or wood as padding in order to avoid damaging the unit.
 • Installation
 1. Read the “Selecting the outdoor unit installation location” section thoroughly before installing the outdoor unit.
 2. If installing the unit to a concrete base or other solid base, use M10 or W3/8 bolts and nuts to secure the unit, and ensure
that the unit is fully upright and level.
(The anchor bolt positions are shown in the diagram at the right side.)
In particular, install the unit at a distance from the neighbouring building which conforms to regulations specified by local
noise emission regulation standards.
 3. Do not install the outdoor unit to the building’s roof.
 4. If there is a possibility that vibration may be transmitted to the rooms of the building, place rubber insulation between the unit
and the installation surface.
 5. Drain water will be discharged from the outdoor unit when operating the system in heating or defrosting modes. Select an
installation location which will allow the water to drain away properly, or provide a drainage channel so that the water can
drain away.
(If this is not done, the drain water may freeze during winter, or the water may spill down to areas underneath the installation
location.)
56
Page of 127