DOWNLOAD Panasonic CS-F24DB4E5 / CU-B24DBE5 / CS-F28DB4E5 / CU-B28DBE5 / CS-F28DB4E5 / CU-B28DBE8 / CS-F34DB4E5 / CU-B34DBE5 / CS-F34DB4E5 / CU-B34DBE8 / CS-F43DB4E5 / CU-B43DBE8 / CS-F50DB4E5 / CU-B50DBE8 Service Manual ↓ Size: 9.48 MB | Pages: 127 in PDF or view online for FREE

Model
CS-F24DB4E5 CU-B24DBE5 CS-F28DB4E5 CU-B28DBE5 CS-F28DB4E5 CU-B28DBE8 CS-F34DB4E5 CU-B34DBE5 CS-F34DB4E5 CU-B34DBE8 CS-F43DB4E5 CU-B43DBE8 CS-F50DB4E5 CU-B50DBE8
Pages
127
Size
9.48 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-f24db4e5-cu-b24dbe5-cs-f28db4e5-cu-b28dbe5-cs-f.pdf
Date

Panasonic CS-F24DB4E5 / CU-B24DBE5 / CS-F28DB4E5 / CU-B28DBE5 / CS-F28DB4E5 / CU-B28DBE8 / CS-F34DB4E5 / CU-B34DBE5 / CS-F34DB4E5 / CU-B34DBE8 / CS-F43DB4E5 / CU-B43DBE8 / CS-F50DB4E5 / CU-B50DBE8 Service Manual ▷ View online

37
8.8.
Wireless Remote Control (Optional part)
Name and function of each part
NOTES
• Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct.
• The illustration above is for explanatory purpose only. The appearance will be different during actual operation.
• If using the wireless remote control in conjunction with the wired remote control, the settings made from the wireless remote
control will appear on the wired remote control display (except when making timer settings).
• Buttons marked with * are not needed for normal operation. If one of these buttons is pressed by mistake, press the same button
once more to cancel the operation.
• When the power resumed after power failure, the unit will restart automatically with all previous settings preserved by the
memory function. (Auto restart function)
Transmitter
Transmits the remote control signal.
Airflow direction setting display
Fan speed display
Temperature setting display (16
°C - 31°C)
Time/time setting display
Shows the timer operation setting time or the current time.
Address number display
Operation selection display
 
OFF/ON button
Used to start and stop the operation.
ODOUR WASH button
FILTER RESET button
Press to cancel the “FILTER” indicator light on the control panel.
FAN SPEED button
Used to select the fan speed of high (HI), medium (MED), low
(LO) or auto (AUTO).
SET button*
Local setting function.
ADDRESS SET button*
Used to change the address setting when using more than one
indoor unit.
RESET button
Pressing this button will clear all the settings from memory.
You will then need to make the settings again.
TIMER/CLOCK SET buttons
Used to set the timer operation and the current time.
AIR SWING (AUTO/MANUAL) buttons
Used to determine the air swing condition, either auto or manual.
MODE button
Used to select the operation of AUTO, HEAT, FAN, COOL or
DRY.
TEMP (UP/DOWN) buttons
Used to select the desired temperature.
ECONOMY operation button
38
9 Operation Details
9.1.
Cooling Operation
• Cooling operation can be set using remote control.
• This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control.
• Cooling Operation Time Diagram.
39
9.2.
Heating Operation
• Heating operation can be set using remote control.
• This operation is applied to warm up the room temperature reaches the setting temperature set on the remote control.
• Heating Operation Time Diagram.
9.3.
Soft Dry Operation
• Soft Dry Operation can be set using remote control.
• Soft Dry operation is applied to dehumidify the room.
• When operation begins, the fan speed is fixed at Low speed while cooling operation is running until reaches the remote control
setting temperature.
9.4.
Auto Operation
• Automatic Mode can be set using remote control.
• This operation starts to judge the intake air temperature, setting temperature, and outdoor piping temperature. Then the unit
starts to operate at determined operation mode.
9.5.
Fan Operation
• Fan operation can be set using remote control.
• The indoor fan is operated at High, Medium or Low speed according to remote control setting.
40
9.6.
Normal Control
9.6.1.
Cooling Indoor Fan Control
• Manual Fan Speed
Operation starts at High, Medium or Low speed set by remote control.
• Auto Fan Speed
When operation start, or shifting to thermostat ON condition from thermostat OFF condition, indoor fan operates as below.
9.6.2.
Heating Indoor Fan Control
• Manual Fan Speed
Operation starts at High, Medium or Low speed set by remote control.
However, when operation start, or during operation, fan speed control is limited due to prevent a cold draft, for example, when
heating operation start.
• Auto Fan Speed
When operation start, or shifting to thermostat ON condition from thermostat OFF condition, indoor fan operates as below.
• If thermostat is off, indoor fan fixed low speed; Louver angle fixed at upper limit, regardless remote control setting.
9.6.3.
Louver Control
• When power is on, at the same time, louver start initializing toward to close Direction.
• During operation, stopping, thermostat off condition, louver angle set manual or auto depend on remote controller setting.
Thermostat & Compres-
sor ON/OFF
Thermostat &
Compressor ON
Thermostat &
Compressor OFF
Thermostat &
Compressor ON
Time
40 sec.
50 sec.
-
20 sec.
120 sec.
20 sec.
40 sec.
50 sec.
-
Cool
Auto
Off
Lo
Hi
Lo
Off
Lo
Off
Lo
Me
Soft Dry
Auto
Off
Lo
Lo
Lo
Off
Lo
Off
Lo
Lo
Page of 127
Display