DOWNLOAD Panasonic CS-F24DB4E5 / CU-B24DBE5 / CS-F28DB4E5 / CU-B28DBE5 / CS-F28DB4E5 / CU-B28DBE8 / CS-F34DB4E5 / CU-B34DBE5 / CS-F34DB4E5 / CU-B34DBE8 / CS-F43DB4E5 / CU-B43DBE8 / CS-F50DB4E5 / CU-B50DBE8 Service Manual ↓ Size: 9.48 MB | Pages: 127 in PDF or view online for FREE

Model
CS-F24DB4E5 CU-B24DBE5 CS-F28DB4E5 CU-B28DBE5 CS-F28DB4E5 CU-B28DBE8 CS-F34DB4E5 CU-B34DBE5 CS-F34DB4E5 CU-B34DBE8 CS-F43DB4E5 CU-B43DBE8 CS-F50DB4E5 CU-B50DBE8
Pages
127
Size
9.48 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-f24db4e5-cu-b24dbe5-cs-f28db4e5-cu-b28dbe5-cs-f.pdf
Date

Panasonic CS-F24DB4E5 / CU-B24DBE5 / CS-F28DB4E5 / CU-B28DBE5 / CS-F28DB4E5 / CU-B28DBE8 / CS-F34DB4E5 / CU-B34DBE5 / CS-F34DB4E5 / CU-B34DBE8 / CS-F43DB4E5 / CU-B43DBE8 / CS-F50DB4E5 / CU-B50DBE8 Service Manual ▷ View online

45
9.7.10.
High Temperature Protection
• During heating operation, when outdoor temperature is more than 35°C for 15 minutes, compressor stops in order to protect the
compressor.
• After 3 minutes (restart delay control) of waiting, if thermostat is ON, outdoor unit restart.
9.7.11.
Pump-down Control
• To enable pump down operation, at outdoor PCB, set the DS1and DS2 to OFF position.
• Press Test Run button for 1 second.
• During Pump Down operation, push the Test Run button again for 1 second to stop the pump down operation.
• The pump down operation run for 10 minutes.
9.7.12.
Thermostat Control
• Depending on differences between room temperature and setting temperature, compressor operation is decided and starts
operation.
• If temperature difference matches values shown below, thermostat switches off or on accordingly.
9.8.
Protection Control
9.8.1.
Outdoor Low-pressure Protection Control
• The purpose of low-pressure protection control is gas leakage detection control.
• The low-pressure protection control starts when low-pressure switch is activated less than 15 minutes after compressor startup.
During heating operation or defrost control low-pressure detection does not start.
• During this protection control, compressor is shut down, indoor unit is set to thermo-off status.
• After 6 occasions, suction pressure error is displayed; all operation stopped except outdoor fan remaining heat removal control.
Thermostat OFF
Thermostat ON
Cooling Mode
-1.5
°C
-0.5
°C
Soft Dry Mode
-2.5
°C
-2.5
°C
Heating Mode
3.5
°C
2.5
°C
46
9.8.2.
Outdoor High-pressure Protection Control
• The high-pressure protection control starts when high-pressure switch is activated less than 15 minutes after compressor
startup.
• During this protection control, compressor is shut down. And indoor unit is set to thermo-off status.
• After 6 occasions, high-pressure protection error is displayed; all operation stopped except outdoor fan remaining heat removal
control.
9.8.3.
Discharge Temperature Protection Control
• The discharge temperature protection control starts when abnormal compressor temperature 115°C is detected when outdoor
unit is operating in cooling or heating operation.
• During this protection control, compressor is shut down. And indoor unit is set to thermo-off status.
• After 6 occasions, high-pressure protection error is displayed; all operation stopped except outdoor fan remaining heat removal
control.
9.8.4.
Over Current Protection Control
• The purpose of over current protection control is to protect the air conditioner from over current.
• The over current protection control starts when input current from CT is maintained at 20A or more for 2 seconds when the
outdoor unit is starting up or during cooling or heating operation.
• During this protection control, compressor is shut down. And indoor unit is set to thermo-off status.
• After 4 occasions, over current protection error is displayed; all operation stopped except outdoor fan remaining heat removal
control.
9.8.5.
CT Disconnection Detection Control
• CT disconnection detection control detects if the CT sensor works normally.
• The CT disconnection detection activates when:
- CT input value is maintained at compressor shutdown status (1.5A or less) consecutively for 2 seconds when the compressor
is operating; except deice mode. 
- During this condition, compressor is shut down and indoor unit is set to thermo-off status.
- After 4 occasions, CT sensor error is displayed; all operation stopped except outdoor fan remaining heat removal control.
- CT input value is maintained at compressor operation status (5A or more) consecutively for a period of 60 seconds when the
compressor is shut down.
- During this condition, CT sensor error is displayed.
9.8.6.
Connection Capacity Protection Control
• The purpose of connection capacity protection control is to ensure the total capacity of connected indoor units is within
acceptable range.
• During this protection control, connection capacity error is displayed; all operations stopped.
9.8.7.
Sensor Disconnection Detection Control
• The sensor disconnection detection control activates when the following condition comply:
• During sensor disconnection, sensor error is displayed; all operations stops except outdoor fan remaining heat removal control.
9.8.8.
Four-way Valve Error Detection Control
• The four-way valve error detection control starts when:
- During cooling operation, when indoor heat exchanger temperature exceeds 45°C in 5 minutes after compressor starts.
- During heating operation, when indoor heat exchanger temperature is below 5°C in 5 minutes after compressor starts.
• During four-way valve error, compressor is shut down and indoor unit is set to thermo-off status.
• After 3 occasions, four-way valve error is displayed; all operation stopped except outdoor fan remaining heat removal control.
Model Number
Min. Capacity (kW)
Max. Capacity (kW)
Model Number
Min. Capacity (kW)
Max. Capacity (kW)
CU-B14DBE5
5.3
6.9
CU-B28DBE8
6.3
9.8
CU-B18DBE5
5.3
6.9
CU-B34DBE8
7.3
12.3
CU-B24DBE5
6.3
9.8
CU-B43DBE8
10.2
13.8
CU-B28DBE5
7.3
12.3
CU-B50DBE8
12.7
15.8
Sensor
Detection Threshold
Duration (Sec.)
Detection Condition
Discharge Temperature
< -4.5
°C or 201.8°C
5
Other than compressor start control
and compressor ON
Outdoor Heat Exchanger
< -50.5
°C or 103.7°C
5
Regularly
47
9.8.9.
Valve Error Detection Control
• This control is to protect the compressor.
• Valve error is detected if comply with condition below:
- Power is on for the first time and within 5 minutes from compressor starts (However, the unit is considered power on for first
time when compressor starts operating continuously for 7 minutes). 
- Indoor heat exchanger temperature at compressor start -3°C < current heat exchanger temperature for 1 minutes.
• During this error, four-way valve error is displayed; compressor is shutdown.
9.8.10.
High-pressure Switch Disconnection Error Detection Control
• High-pressure switch disconnection is detected when high-pressure switch input continuously open for 1 minutes while the
compressor shutdown.
• During this error, high-pressure switch error is displayed.
9.8.11.
Low-pressure Switch Disconnection Error Detection Control
• Low-pressure switch disconnection is detected when low-pressure switch input continuously open for 1 minutes while
compressor shutdown.
• During this error, low-pressure switch error is displayed.
9.9.
Test Run
• Test run is necessary after installation is completed.
• To enable forced cooling test run, at outdoor PCB, set the DS1 to ON position and DS2 to OFF position.
• To enable forced heating test run, at outdoor PCB, set the DS1 to ON position and DS2 to ON position. 
• Press Test Run button at outdoor pcb for 1 second.
48
10 Installation Instruction
10.1. Pipe length
• CORRECTION OF CAPACITIES
1. Correction of capacities according to the connecting pipe length.
The data of rated capacities (marked on the name plate) are based on 7.5 meters connecting pipe and horizontal installation.
2. For other pipe length of other installation multiply by the following correction factor to determine the revised cooling capacity. 
Note:
Piping elevation B = outdoor unit installed at top
Piping elevation C = outdoor unit installed at bottom
• Calculation 1
In case of CU-B28DBE5, CU-B28DBE8, CU-B34DBE5, CU-B34DBE8
When pipe length exceed 30m calculated by formula 1, adding refrigerant amount should be calculated by formula 2. If
calculation result is less than 30m, it is not necessary to add refrigerant.
Pipe length = main pipe + (branch pipe La + branch pipe Lb)/2.78...formula 1
Add refrigerant = (main pipe + (branch pipe La + branch pipe Lb)/2.78-30) * 50...formula 2
• Calculation 2
In case of CU-B43DBE8, CU-B50DBE8
When pipe length exceed 30m calculated by formula 3, adding refrigerant amount should be calculated by formula 4. If
calculation result is less than 30m, it is not necessary to add refrigerant.
Pipe length = main pipe + branch pipe La + branch pipe Lb... formula 3
Add refrigerant = (main pipe + branch pipe La + branch pipe Lb-30) * 50...formula 4
Piping Size / Length & Elevation
Model No.
Piping size
Piping 
length      
(A)
Piping     
elevation 
(B)
Piping     
elevation 
(C)
Piping 
Chargeless 
Add        
Refrigerant
Liquid / 
High
Valve
Gas / 
Low
Valve
Max(m)
Max(m)
Max(m)
Max(m)
(g/m)
R
CS-F24DB4E5
Cassette
4
CS-F28DB4E5
type
1
CS-F34DB4E5
9.52
3-ways
15.88
3-ways
50
30
20
30
50
0
CS-F43DB4E5
A
CS-F50DB4E5
Page of 127
Display

Click on the first or last page to see other CS-F24DB4E5 / CU-B24DBE5 / CS-F28DB4E5 / CU-B28DBE5 / CS-F28DB4E5 / CU-B28DBE8 / CS-F34DB4E5 / CU-B34DBE5 / CS-F34DB4E5 / CU-B34DBE8 / CS-F43DB4E5 / CU-B43DBE8 / CS-F50DB4E5 / CU-B50DBE8 service manuals if exist.