 2. For the embedded piping
(This can be used for left rear piping & left bottom piping also.)
49
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
 1. Remove the control board metal cover.
 2. Unscrew the conduit cover & fix the conduit connector to
conduit cover with lock nut, then secure it against chassis.
 3. Connecting between indoor unit and outdoor unit should be
UL listed or CSA approved 6 × AWG16 wire.
  • Ensure the color of wires of outdoor unit and the
terminal Nos. are the same as the indoor’s respectively.
  • Earth lead wire should be longer than the other lead
wires as shown in the figure for the electrical safety in
case the cord slips out from the anchorage.
  • Secure the wire onto the control board with the holder
(clamper).
 4. After completed wiring connection, fix back the metal cover
to the original location.
INSTALLATION OF AIR PURIFYING FILTERS
 1. Open the front panel.
 2. Remove the air filters.
 3. Put air purifying filters (left) and solar refreshing deodorizing
filter (right) into place as shown in illustration below.
11.2.5. INDOOR UNIT ELECTRICAL WIRING
50
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
HOW TO TAKE OUT FRONT GRILLE
Please follow the steps below to take out front grille if
necessary such as when servicing.
 1. Set the vertical airflow direction louver to the horizontal
position.
 2. Slide down the three caps on the front grille as shown in the
illustration below, and then remove the three mounting
screws.
 3. Pull the lower section of the front grille towards you to
remove the front grille.
When reinstalling the front grille, first set the vertical
airflow direction louver to the horizontal position and
then carry out above steps 2 - 3 in the reverse order.
AUTO SWITCH OPERATION
The below operations will be performed by pressing the
“AUTO” switch.
 1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the
Auto Switch is pressed.
 2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING
PURPOSE)
The Test Run operation will be activated if the Auto Switch
is pressed continuously for more than 5 sec. to below 10
sec.. A “pep” sound will occur at the fifth sec., in order to
identify the starting of Test Run operation
 3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote Controller receiving sound can be
change over by pressing the “AUTO” Switch continuously
for 10 sec. and above. A “pep”, “pep” sound will occur at the
tenth sec., in order to indicate the “ON/OFF” change over of
remote control receiving sound.
11.3. OUTDOOR UNIT
11.3.1. SELECT THE BEST LOCATION
(Refer to “Select the best location”
section)
11.3.2. INSTALL THE OUTDOOR UNIT
  • After selecting the best location, start installation according
to Indoor/Outdoor Unit Installation Diagram.
 1. Fix the unit on concrete or rigid frame firmly and horizontally
by bolt nut. (ø10 mm [ø0.39 inch]).
 2. When installing at roof, please consider strong wind and
earthquake. Please fasten the installation stand firmly with
bolt or nails.
11.3.3. CONNECTING THE PIPING
Connecting The Piping To Indoor Unit
Please make flare after inserting flare nut (locate at joint portion
of tube assembly) onto the copper pipe. (In case of using long
piping)
Connect the piping
  • Align the center of piping and sufficiently tighten the flare
nut with fingers.
  • Further tighten the flare nut with torque wrench in specified
torque as stated in the table.
MODEL
Piping size (Torque)
Gas
Liquid
CS-A9CKPG
3/8” (42 N.m)
1/4” (18 N.m)
CS-A12CKPG
1/2” (55 N.m)
1/4” (18 N.m)
Connecting The Piping To Outdoor Unit
Decide piping length and then cut by using pipe cutter. Remove
burrs from cut edge. Make flare after inserting the flare nut
(located at valve) onto the copper pipe.
Align center of piping to valves and then tighten with torque
wrench to the specified torque as stated in the table.
51
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
CUTTING AND FLARING THE PIPING
 1. Please cut using pipe cutter and then remove the burrs.
 2. Remove the burrs by using reamer. If burrs is not
removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder
entering the pipe.
 3. Please make flare after inserting the flare nut onto the
copper pipes.
11.3.4.  EVACUATION OF THE EQUIPMENT
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
 1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve.
  • Be sure to connect the end of the charging hose with the push pin to the service port.
 2. Connect the center hose of the charging set to a vacuum pump.
 3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
 4. Close the valve of both the Low and High sides of the charging set and turn off the vacuum pump. Make sure that the needle
in the gauge does not move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
 5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
 6. Tighten the service port caps of the 3-way valve at a torque of 18 N.m with a torque wrench.
 7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm [0.16 inch]).
 8. Mount valve caps onto the 2-way valve and the 3-way valve.
  • Be sure to check for gas leakage.
CAUTION
  • If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
  • If the leak stops when the piping connections are tightened further, continue working from step 3.
  • If the leak does not stop when the connections are retightened, repair the location of leak.
  • Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause
frostbite.
52