11 Installation Instructions
Required tools for Installation Works
1.
Philips screw driver
5.
Spanner
9.
Gas leak detector
13. Multimeter
2.
Level gauge
6.
Pipe cutter
10. Measuring tape
14. Torque wrench
18 N.m (1.8 kgf.m)
42 N.m (4.2 kgf.m)
55 N.m (5.5 kgf.m)
3.
Electric drill, hole core drill
(ø70 mm [ø2.76 inch])
7.
Reamer
11. Thermometer
15. Vacuum pump
4.
Hexagonal wrench
(4 mm [0.16 inch])
8.
Knife
12. Megameter
16. Gauge manifold
11.1. Safety Precautions
  • Read the following “SAFETY PRECAUTIONS” carefully before installation.
  • Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit
for the model to be installed.
  • The caution items stated here must be followed because these important contents are related to safety. The meaning of each
indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the
seriousness is classified by the following indications.
This indication shows the possibility of causing death or serious injury.
This indication shows the possibility of causing injury or damage to properties only.
The items to be followed are classified by the symbols:
Symbol with background white denotes item that is PROHIBITED from doing.
  • Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
1.
Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire.
2.
Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
3.
Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or
electrical shock.
4.
Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
done, the set will drop and cause injury.
5.
For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
6.
Use the UL listed or CSA approved AWG16 wire (or heavier wire) and connect tightly for indoor/outdoor connection. Connect tightly and
clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at
the connection.
7.
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
cause heat-up at connection point of terminal, fire or electrical shock.
8.
When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
45
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
1.
The equipment must be earthed. It may cause electrical shock if grounding is not perfect.
2.
Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.
3.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
furniture.
1.
Selection of the installation location.
Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
2.
Power supply connection to the room air conditioner.
Connect the power supply cord of the room air conditioner to the mains.
Power supply point should be in an easily accessible place for power disconnection in case of emergency.
Power supply connection to a circuit breaker for the permanent connection. Use an approved 15A (CU-A9CKP6G) and 20A (CU-
A12CKP6G) fuse or circuit breaker for the permanent connection.
It must be a double pole switch with a minimum 3 mm (0.12 inch) contact gap.
3.
Do not release refrigerant.
Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take care of the
liquid refrigerant, it may cause frostbite.
4.
Installation work.
It may need two people to carry out the installation work.
5.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
6.
It is not possible to carry out installation when the outdoor unit temperature reach -12°C (10.4°F).
46
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
Applicable piping kit
CZ-3F5, 7AEN (CS-A9CKPG)
CZ-4F5, 7, 10AN (CS-A12CKPG)
SELECT THE BEST LOCATION
INDOOR UNIT
  • There should not be any heat source or steam near the
unit.
  • There should not be any obstacles blocking the air
circulation.
  • A place where air circulation in the room is good.
  • A place where drainage can be easily done.
  • A place where noise prevention is taken into
consideration.
  • Do not install the unit near the door way.
  • Ensure there is adequate space (indicated by arrows)
from the wall, ceiling, fence or other obstacles.
  • Recommended installation height for indoor unit shall be
at least 7.5 ft. (2.3 m).
OUTDOOR UNIT
  • If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
  • Keep animals or plants away from the unit as they may
be affected by the hot air discharged.
  • Keep the spaces (indicated by arrows) from wall, ceiling,
fence or other obstacles.
  • Do not place near any obstacles which may cause a
short circuit of the discharged air.
  • If piping length is over the common length, additional
refrigerant should be added as shown in the table.
Indoor/Outdoor Unit Installation Diagram
  • This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
Attached accessories
47
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
11.2.1. SELECT THE BEST LOCATION
(Refer to “Select the best location”
section)
11.2.2. HOW TO FIX INSTALLATION
PLATE
The mounting wall is strong and solid enough to prevent it from
the vibration.
The centre of installation plate should be at more than 550 mm
(21.65 inch) at right and left of the wall.
The distance from installation plate edge to ceiling should more
than 67 mm (2.64 inch).
From installation plate left edge to unit’s left side is 47 mm
(1.85 inch).
From installation plate right edge to unit’s right is 73 mm (2.87
inch).
:
:
:
For left side piping, piping connection for liquid should be
about 126 mm (4.96 inch) from this line.
For left side piping, piping connection for gas should be
about 174 mm (6.85 inch) from this line.
For left side piping, piping connecting cable should be
about 984 mm (38.74 inch) from this line.
 1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall consider using
anchor bolts.)
  • Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge.
 2. Drill the piping plate hole with ø70 mm (ø2.76 inch) hole-
core drill.
  • Line according to the arrows marked on the lower left
and right side of the installation plate. The meeting point
of the extended line is the centre of the hole. Another
method is by putting measuring tape at position as
shown in the diagram above. The hole centre is
obtained by measuring the distance namely 150 mm
(5.91 inch) and 125 mm (4.92 inch) for left and right hole
respectively.
  • Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
11.2.3. TO DRILL A HOLE IN THE WALL
AND INSTALL A SLEEVE OF
PIPING
 1. Insert the piping sleeve to the hole.
 2. Fix the bushing to the sleeve.
 3. Cut the sleeve until it extrudes about 15 mm (0.59 inch)
from the wall.
Caution
When the wall is hollow, please be sure to use the
sleeve for tube ass’y to prevent dangers caused by
mice biting the connecting cable.
 4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
11.2.4. INDOOR UNIT INSTALLATION
 1. For the right rear piping
11.2. INDOOR UNIT
48
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
Page of 82