8.9.1. Auto Control
 • When the horizontal airflow direction is set to Auto using the
remote control, the vanes swings left and right as shown in
the diagram.
 • When stopped with remote control, the discharge vane is
reset, and stop at the reset position.
 • During Cooling operation or Soft Dry operation, indoor fan
motor may stop to rotate at certain periods. At that
condition, the vane will stop swinging and rest at 22° angle.
 • When the horizontal airflow direction is set to Manual using
the remote control, the automatic airflow is released and the
airflow direction vane move left and right in the range shown
in the diagram.
The louver can be adjusted by pressing the button to the
desired vane position.
 • When stopped with remote control, the vanes is reset, and
stopped at reset position.
8.9. Horizontal Airflow Direction Control
8.9.2. Manual Control
29
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
8.10. Powerful Operation
 • The Powerful operation is to achieve the setting temperature quickly.
(Cooling and Soft Dry Operation condition)
 • When Powerful operation is set, the setting temperature will be automatically decreased 3°C internally against the present
setting temperature (Lower temperature limit: 16°C).
 • This operation automatically will be running under SHi Fan Speed (Cooling), Lo- Fan Speed (Soft Dry).
 • Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically shift down 10° lower than previous.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
(Heating Operation condition)
 • When Powerful operation is set, the setting temperature will be automatically increased 3°C against the present setting
temperature (Higher temperature: 30°C).
 • The Fan Speed will shift as shown below:
 • Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically shift down 5° lower than previous setting.
- In “Auto” setting, the vane will automatically shift between upper and lower limit depending on the intake air temperature as
Heating Mode, Airflow Direction Auto-Control. However the upper and lower limit will be shifted 5° downward.
 • Powerful Mode will operate for 15 minutes only and operation will shift back to previous setting mode.
 • Powerful operation stops when:-
- Powerful operation has operate for 15 minutes.
- Powerful button is pressed again.
- Quiet button is pressed.
- Stopped by OFF/ON operation button.
- Timer OFF activates.
- Operation mode is changed.
8.11. Quiet Operation
 • The Quiet operation is to provide quiet cooling/heating operation condition compare to normal operation.
(Cooling and Soft Dry Operation condition)
 • Once the Quiet Mode is set at the remote control, the Quiet Mode LED illuminated. The sound level will reduce either around
2 dB(A) for Lo fan speed or 3 dB(A) for Hi/Me fan speed against the present sound level operation.
 • Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1hr 30 min (1hr QLo, 30 min QLo +
50rpm). After that, it goes back to Lo cool (However Quiet LED remains on).
30
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
 • Manual Airflow Direction:-
 − RPM control during Lo cool
 − RPM control during Hi & Me cool
 • Auto Airflow Direction:-
(Heating Operation condition)
 • When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates. The sound level will reduce either around 2
dB(Lo) or 3 dB(Hi, Me), against the present sound level operation.
 • Quiet setting of fan speed rpm refer to Indoor Fan Speed Control.
 • Manual Airflow Direction:-
 − Rpm control during Lo, Me & Hi Cool
31
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
 • Auto Airflow Direction:-
 − Rpm control depends on the piping air temperature sensor of Indoor heat exchanger
 • Quiet operation stops when:-
 − Quiet/Powerful button is pressed again.
 − Stopped by OFF/ON operation button.
 − Timer OFF activates.
 − Operating mode is changed.
8.12. Ionizer Operation
 • The Ionizer operation is to provide fresh air effect to user by producing minus ion in discharge air.
8.12.1. Operation Control
 1. Ionizer individual operation
 a. When air-conditioner unit is at “OFF” condition (standby) and ION operation button at the remote control is pressed, the
Ionizer and Air Circulation operations will turn on. Only ION LED will illuminates. Power LED maintain off. (1
→ 2)
 b. Ionizer individual operation can be turned off by pressing the ION button again. (2
→ 1)
 c. Fan speed can be adjusted later by customer during this operation.