Normal Deicing Time Diagram
Overload Deicing Time Diagram
25
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
8.6. Indoor Fan Speed Control
 • Indoor Fan Speed can be set using remote control.
8.6.1. Fan Speed Rotation Chart
Fan Speed
CS-A18DKD
CS-A24DKD
Cool, Dry
Heat
SHi
Hi
1460
1650
Hi
-
1400
1590
Me
Me
1320
1480
Lo+
Lo
1270
1380
Lo
-
1190
1280
Lo-
Lo-
980
1070
SLo
SLo
760
830
-
SSLo
300
300
QSHi
QHi
1360
1550
QHi
-
1300
1490
QMe
QMe
1220
1380
-
QLo
1170
1280
QLo
-
1090
1180
8.6.2. Automatic Fan Speed Control
 • When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
 − Fan speed rotates in the range of Hi and Me.
 − Deodorizing Control will be activated.
26
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
 • Auto Fan Speed during Cooling operation:
 1. Indoor fan will rotate alternately between off and on as shown in below diagram.
 2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
 3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from SLo after 70 seconds from the
start of compressor. This cause the room temperture to achieve the setting temperature quickly.
 4. During compressor stop, indoor fan will operate at SLo for the beginning 20 seconds to prevent higher volume of refrigerant
in liquid form returning to the compressor.
 5. After the compressor at turn off condition for 3 minutes, indoor fan will start to operate at SLo to circulate the air in the room.
This is to obtain the actual reading of the intake air temperature.
 6. When the compressor resume operation, indoor fan will operate at Me fan speed (after 70 seconds from the restart of
compressor) to provide comfort and lesser noise environment.
 • Auto Fan Speed during Soft Dry operation:
 1. Indoor fan will rotate alternately between off and Lo-.
 2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
 3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in the room.
This is to obtain the actual reading of intake air temperature.
 • Auto Fan Speed during Heating operation.
 1. Indoor fan will rotate in the range of SLo
→ Me according to the heat exchanger temperature.
27
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
(Cooling and Soft Dry Operation condition)
 • When the vertical airflow direction is set to Auto using the
remote control, the louver swings up and down as shown in
the diagram.
 • When stop operation using the remote control, the
discharge vent is reset, and stop at the closing position.
 • During Cooling operation or Soft Dry operation, indoor fan
motor may stop to rotate at certain periods. At that
condition, the louver will stop swinging and rest at the upper
limit.
(Heating Operation condition)
 • When the intake air temperature reaches 38°C, the louver
is changed from upper to lower limit. When the intake air
temperature falls to 35°C, the louver is changed from louver
to upper limit.
Cooling and Soft Dry Operation
Heating Operation
8.6.3. Manual Fan Speed Control
 • Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control.
 • There are 3 types of fan speed settings: Lo, Me, Hi.
8.7. Outdoor Fan Speed Control
 • There is only one speed for outdoor fan motor.
 • When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
 • Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
8.8. Vertical Airflow Direction Control
8.8.1. Auto Control
8.8.2. Manual Control
 • When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in the diagram.
 • The louver can be adjusted by pressing the button to the desired louver position.
 • When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.