8.5.7. Anti-Dew Formation Control
 • Purpose is to prevent dew formation on indoor unit air discharge area.
 • When room temperature is constant (±1°C) the following conditions occur for 30 minutes continuously, anti-dew formation will
activate:
 − Remote Control setting temperature is less than 25°C.
 − Compressor is on.
 − Cooling operation mode.
 − Indoor Fan motor operate at Low fan speed or QLo.
 • This control is cancelled immediately when above condition is changed.
 • Anti-Dew formation is control by:
 1. Increasing Air Flow Volume
 a. Lo fan speed
Lo fan speed is changed to Lo+ after 30 min to prevent dew formation.
 b. QLo fan speed
Dew formation may occurs at QLo cool, therefore QLo cool is operated only 1 hr 30 min (1 hr QLo, 30 min QLo +100
rpm). After that, it operates at QLo +180rpm (However Quiet LED remains on).
 2. Norrowing
Vertical Airflow Direction
 − During Anti-dew condensation prevention, Airflow Direction Auto-control angle change from 10° - 38° to 10° - 27° under
Cooling and Soft Dry operation mode.
21
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
 − During Anti-dew condensation prevention, Airflow Direction Manual control angle change from 10°, 14°, 18°, 22°, 27° to
10°, 13°, 16°, 19°, 22° under Cooling and Soft Dry operation mode.
 3. Narrowing
Horizontal Airflow Direction
 − During Anti-dew condensation prevention, Airflow Direction Auto-control angle change from 0° - 44° to 14° - 30° under
Cooling and Soft Dry operation mode.
 − During Anti-dew condensation prevention, Airflow Direction Manual control angle change from 0°, 11°, 22°, 33°, 44° to
14°, 18°, 22°, 26°, 30° under Cooling and Soft Dry operation mode.
(For 8.5.8. to 8.5.13. information applies only to Heating Operation)
8.5.8. Overload Protection Control
 • Outdoor Fan Control
 − If the temperature of the Outdoor Heat Exchanger less than -3°C, Outdoor Fan is ON. The Outdoor Fan stop, when Outdoor
Heat Exchanger temperature is T or more according to Outdoor Air Temperature region as table below:
The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49°C.
 − During starting of Heating mode and after deice, Outdoor Fan ON for 90 sec. (Hi).
22
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
 • Compressor high pressure protection
 − If the indoor heat exchanger becomes 68°C or more, the compressor will stop and restart automatically.
 − Time Delay Safety Control is activated before the compressor restart.
8.5.9. 4-Way Valve Control
 • 4-way valve always on during Heating operation. (except deicing operation)
 • When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating position for 5 minutes.
 • This is to prevent the refrigerant flow process sound for being occur.
8.5.10. Outdoor Fan Motor Control
 • When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds (forced operation).
 • This is to release the heat and to obtain the lowest pressure as fast as possible.
8.5.11. Hot Start Control
 • Hot Start Control is to prevent cool air discharge into the room when heating operation start.
 • When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
 • Hot start is completed when indoor heat exchanger rises to 42°C or operation over 4 minutes.
23
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
8.5.12. Anti Cold Draft Control
 • This operation is to prevent the Cold Draft during Heating mode operation.
 • The operation will start when compressor OFF (Thermo OFF) during Heating operation.
 • For the first 30 sec. from compressor OFF (Termo OFF), Indoor fan speed will operate accordingly to the Indoor heat exchanger
temperature as shown below:
 • After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run at SSLo speed only.
 • Anti Cold Draft Control will stop when:
 − Intake temperature < set temperature. (Time Delay Safety Control 4 minutes waiting is valid)
 − 30 Minutes Time Save Control activates.
8.5.13. Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
 • Normal Deicing
Deice operations detection commences after 60 minutes of Heating operation starts or 60 minutes after previous deice
operation. If the TRS (Thermal Read Switch) senses the outdoor piping temperature drops to -4°C (TRS CLOSE) or less for 50
sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
 • Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and after
compressor starts for 1 minutes, deicing starts.
 • Deicing ends when
 1. 12 minutes after deicing operation starts;
 2. The outdoor piping temperature rises to 12°C.
 • After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.
24