 3. For the embedded piping
45
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
 1. The inside and outside connecting cable can be connected
without removing the front grille.
 2. Connecting cable between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 3 × 2.5 mm
2
(C24DK) or 5 × 2.5 mm
2
(A18DK, A24DK) flexible cord,
type designation 245 IEC 57 or heavier cord.
 • Ensure the colour of wires of outdoor unit and the
terminal Nos. are the same to the indoor’s respectively.
 • Earth lead wire shall be longer than the other lead wires
as shown in the figure for the electrical safety in case of
the slipping out of the cord from the anchorage.
 • Secure the cable onto the control board with the holder
(clamper).
INSTALLATION OF SUPER ALLERU-BUSTER FILTER
 1. Open the front panel.
 2. Remove the air filter.
 3. Remove Supersonic air purifying device.
 4. Open the Supersonic air purifying device frame.
 5. Insert the super alleru-buster filter and close the Supersonic
air purifying device frame as shown in illustration at right.
10.2.5. CONNECT THE CABLE TO THE INDOOR UNIT
46
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
HOW TO TAKE OUT FRONT GRILLE
Please follow the steps below to take out front grille if
necessary such as when servicing.
 1. Open the intake grille.
 2. Set the vertical airflow direction louver to the horizontal
position.
 3. Slide down the 3 caps on the front grille as shown in the
illustration below, and then remove the 3 mounting screws.
 4. Pull the lower section of the front grille towards you to
remove the front grille.
When reinstalling the front grille, first set the vertical
airflow direction louvers to the horizontal position and
then carry out above steps 2 - 3 in the reverse order.
AUTO SWITCH OPERATION
The below operations will be performed by pressing the
“AUTO” switch.
 1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the
Auto Switch is pressed.
 2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING
PURPOSE)
The Test Run operation will be activated if the Auto Switch
is pressed continuously for more than 5 sec. A “beep”
sound will occur at the fifth sec., in order to identify the
starting of Test Run operation.
 3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of remote controller receiving sound can be
changed over by the following step:
 a. Release the Auto Switch after Test Run operation is
activated.
 b. Then, within 20 sec after (a), press Auto Switch for more
than 5 sec.
A “beep” “beep” sound will occur at the fifth sec., then
release the Auto switch.
 c. Within 20 sec after (b), press Auto Switch again.
Everytime Auto Switch is pressed (within 20 sec
interval), remote controller receiving sound status will be
reversed between ON and OFF.
Long “beep” sound indicates that remote controller
receiving sound is OFF.
Short “beep” sound indicates that remote controller
receiving sound is ON.
47
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
 • After selecting the best location, start installation according
to Indoor/Outdoor Unit Installation Diagram.
 1. Fix the unit on concrete or rigid frame firmly and horizontally
by bolt nut. (ø10 mm).
 2. When installing at roof, please consider strong wind and
earthquake. Please fasten the installation stand firmly with
bolt or nails.
10.3.3. CONNECTING THE PIPING
Connecting The Piping To Indoor Unit
Please make flare after inserting flare nut (locate at joint portion
of tube assembly) onto the copper pipe. (in case of using long
piping)
Connect the piping
 • Align the center of piping and sufficiently tighten the flare
nut with fingers.
 • Further tighten the flare nut with torque wrench in specified
torque as stated in the table.
CUTTING AND FLARING THE PIPING
 1. Please cut using pipe cutter and then remove the burrs.
 2. Remove the burrs by using reamer. If burrs is not
removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder
entering the pipe.
 3. Please make flare after inserting the flare nut onto the
copper pipes.
MODEL
Piping size (Torque)
Gas
Liquid
A18DK
1/2” (55 N.m)
1/4” (18 N.m)
C24DK, A24DK
5/8” (65 N.m)
1/4” (18 N.m)
10.3. Outdoor Unit
10.3.1. SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
10.3.2. INSTALL THE OUTDOOR UNIT
Connecting The Piping To Outdoor Unit
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut
(located at valve) onto the copper pipe.
Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table.
48
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
Page of 86