DOWNLOAD Sharp AY-XP13CR (serv.man15) Service Manual ↓ Size: 4.26 MB | Pages: 48 in PDF or view online for FREE

Model
AY-XP13CR (serv.man15)
Pages
48
Size
4.26 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
ay-xp13cr-sm15.pdf
Date

Sharp AY-XP13CR (serv.man15) Service Manual ▷ View online

13
AY-XP08CR
AY-XP10CR
AY-XP13CR
Figure L-3. Electronic Control Circuit Diagram for
AE-X08CR / AE-X10CR
14
AY-XP08CR
AY-XP10CR
AY-XP13CR
Figure L-4. Electronic Control Circuit Diagram for AE-X13CR
15
AY-XP08CR
AY-XP10CR
AY-XP13CR
Figure L-5. Printed Wiring Board for AE-X08CR / AE-X10CR  / AE-X13CR
TO DIODE BRIDGE
DB1 " ~ "
OPTION
(FROM WINTER KIT)
FROM 
FAN MOTOR
FROM 
4 WAY VALVE
(EXCEPT FOR 
AU-X08CR/10CR/13CR)
FROM 
IPM PWB " U ", " V" , " W "
TO
ACTIVE FILTER
MODULE ACT
FROM
ELECTLYTIC
CAPACTITOR C8
FROM T6
TO MRY1 IN
FROM 
CONTROL BOX
FROM 
TERMINAL 
BOARD " 1 "
TO IPM PWB CN101
OPTION
(FROM WINTER KIT)
FROM
THERMISTOR
COMP. TEMP.
HEAT-EXCHANGR TEMP.
OUTDOOR TEMP.
FROM
HEAT-SINK
THERMISTOR
FROM
TERMINAL
BOARD " 2 "
FROM
TERMINAL
BOARD " N "
15A : CWI080H / CWI100H
20A : CWI130H
16
AY-XP08CR
AY-XP10CR
AY-XP13CR
FUNCTIONS
1. INDOOR UNIT
1-1 Temperature Adjustment
(1) Cooling
When the room temperature is higher than the preset
temperature by 2˚C or more, the unit runs at the
maximum operation frequency until the temperature
comes down to the preset temperature.
When reaching the preset temperature, the unit runs
at the frequency calculated by the fuzzy operation
and switches to the normal control.
(2) Heating
When the room temperature is lower than the preset
temperature by 3.5˚C or more, the unit runs at the
maximum operation frequency until the temperature
comes down to the preset temperature.
When reaching the preset temperature, the unit runs
at the frequency calculated by the fuzzy operation
and switches to the normal control.
(3) Dry
After operation begins, 2 minutes of the room
temperature is stored in memory, and that becomes
the set value.
1-2 Indoor fan control
(1) Cooling
The fan speed can be selected from "Auto",
"Soft", "Low",and "HIgh".When "Soft", "Low" or
"HIgh" is selected, the fanspeed is constant
regardless of the room temperature.When "Auto"
is selected, the fan speed automatically changes
between "Soft" and "HIgh" depending on the
d i f f e r e n c e   b e t w e e n   t h e   r o o m   a n d   p r e s e t
temperature.
Control for indoor freezing prevention
If the temperature of the indoor heat exchanger
stays below approximately 1˚C for four minutes
during cooling or dry, this control stops the
compressor. Over 3˚C the compressor will run
again.
(2) Heating
Control for cold air blowing prevention
When heating begins, this control stops the
indoor fan until the temperature of the indoor heat
exchanger reaches 23˚C. It also stops the fan if
t h e   t e m p e r a t u r e   g o e s   b e l o w   2 1 ˚ C   d u r i n g
operation.
1-3 Hot keep
If the room temperature is enough high during heating,
the compressor is turned on and off to prevent
overheating.
The fan goes off 30 seconds after the compressor
goes off.
The indoor fan stops.
Temperature of the indoor heat exchanger
Preset Fan speed
The indoor fan operates at low speed.
35˚C
23˚C
32˚C
21˚C
1-4 Automatic operation
The operating mode and temperature setting are
determined by the room temperature and the external
air temperature.
The operating mode will changeover automatically
with the following condition.
1. From cooling to heating
Cooling mode will changeover to heating mode when
condition of indoor temperature 1.7˚C lower than the
set temperature conditions for 5 minutes.
2. From heating to cooling
Heating mode will change over to cooling mode when
condition of indoor temperature 1.3˚C higher than the
set temperature conditions for 25 minutes under Hot
keep condition.
3. When the set temperature is adjusted within the
range of ±2˚C by the remote control’s key.
 ( 
 ), the changeover judgement room temp. will
also be shifted within the range of ±2˚C.
1-5 ON-timer
The ON-timer is set by pressing the ON-timer button.
In order to attain the set temperature at the set time,
the operation starting time is corrected by neuro and
fuzzy computing one hour before the set time.
Compressor
intermittent time
Fan
After "3 min. on - 3 min.off" is 
repeated 4 times, the compressor 
goes off, and only the fan 
continues to repeat “3 min. on - 8 
min.off”.
3 min. on - 3 min. off
3 min. on - 8 min. off
Same as Compressor
Heating
(24˚C)
Heating
(23˚C)
Cooling
(24˚C)
Cooling
(24˚C)
(Room temperature 
- 2
°C)
Cooling
(25˚C)
Cooling
(26˚C)
(Dry)
Room 
temperature
(˚C)
When the cooling operation only can use winter kit
21
29
0
10
18
28
34
Outdoor
temperature (
°C)
Cooling
(25˚C)
Cooling
(26˚C)
Heating
(22˚C)