45
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
Indoor unit 
operating
Outdoor unit 
completely stopped
Serial short
Serial open
1. Check the wiring between units.
1. Check the wiring between units.
1. Check the wiring between units.
2. Check the fuse in the outdoor unit.
3. Outdoor control board.
1. Rewire.
1. Rewire.
Indoor fan out 
of order
1. Is the fan motor locked ?
2. Is the wiring connector firmly fitted ?
3. Is the rotation pulse signal applied to the motor ?
1. Rewire.
2.Replace the fuse, replace the 
outdoor board assembly.
3. Replace the board.
1. Replace fan motor
2. Reattach.
3.Replace the indoor control 
board assembly.
: Blinks at 1-second intervals
: OFF
: ON
: Blinks 3 times at 0.1-second intervals
Display by indoor unit operation lamp
Displayed in a pattern which comes on at  the 
same time as the timer lamp
4 seconds off
What to check, procedure
Display by 
outdoor 
unit lamp 
LED 
51 ~ 52
Diagnosis
Solution
Condition 
of indoor 
and 
outdoor 
unit
46
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
100
80
60
40
20
0
-10
0
1
0
2
0
3
0
4
0
Resistance
Thermistor
Room temperature
Heat exchange
Pipe temperature
Color
Yellow
Orange
Black
Room temperature 
thermistor TH1 (CN6  3   -   4  )
Heat exchange 
thermistor TH2 (CN6  1   -   2  )
Pipe temperature 
thermistor TH3 (CN6  5   -   6  )
Tester
CN6
1
6
Signal
TH1
TH2
TH3
Figure 1     Temperature properties of  indoor thermistors
kΩ
500k
400k
300k
200k
100k
0
-20
0
2
0
6
0
8
0
100
120
3.06k
5.78k
2.28k
1.72k
40k
30k
20k
10k
0
-20
0
2
0
6
0
40
Figure 2     Temperature properties of outdoor thermistors
Connector
CN8B
1
6
TH1 compressor thermistor
(CN8A  1   -   2  )
TH2 - TH7
Temperature (
°C)
Temperature (
°C)
Thermistor
Color
No.
 Connector
Compressor thermistor
Heat exchanger pipe thermistor
Connector pin
Outdoor temp. thermistor
TH1
TH2
TH3
CN8A
 CN8A
Red
No. 1 to 2
No. 3 to 4
No. 5 to 6
No. 7 to 8
No. 1 to 2
No. 3 to 4
No. 5 to 6
Orange
Suction thermistor
TH4
CN8A
Black
Thermistor unit A (suction)
TH5
CN8B
Blue
Thermistor unit B (suction)
TH6
CN8B
White
Thermistor unit C (suction)
TH7
 CN8B
Brown
 CN8A
Green
Connector
CN8A
18
25
°C resistance
45 k
Resistance (
Ω)
Resistance (
Ω)
C resistance
14.5 k
25
°C resistance
4.431 k
Cautions when attaching or removing the board
When oper
ating only the outdoor unit (cooling 55 Hz fix
ed mode) 
T
o
 mak
only the outdoor unit r
un in cooling mode
, and apply a v
oltage of 230 
V A
C
 
to 1 and N on the ter
minal board and push the pump do
wn s
witch.
  (SW51)
(A
v
oid oper
ating the outdoor unit alone f
or long per
iods of time
.)
To measure the resistance, first remove 
the soldering as shown at right.
Room temperature 
thermistor TH1 (Yellow)
25
°C resistance 10 k
Heat exchange thermistor 
TH2 (Orange), TH3 (Black)
25
°C resistance 4.431 k
 
To measure the resistance, first remove the connector from the board. 
4.17k
TH2 : Heat exchanger pipe thermistor (CN8A  3   -   4  )
TH3 : Outdoor temp. thermistor (CN8A  5   -   6  )
TH4 : Suction thermistor (CN8A   7   -   8  )
TH5 : Thermistor unit A (CN8B   1   -   2  )
TH6 : Thermistor unit B (CN8B   3   -   4  )
TH7 : Thermistor unit C (CN8B   5   -   6  )
47
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
TROUBLESHOOTING OF CONTROL CIRCUIT
1
Yes
Yes
Yes
No
No
No
No
How to distinguish the defective parts
When all rooms are not cooled
Are the timer lamps of the in-
door units in all rooms flashing ?
Is the compressor of the outdoor 
unit operating ?
Are the timer lamps of the indoor 
units in all rooms flashing ?
Check the failure symptom with 
the failure diagnosis mode.
The cooling cycle is abnormal.
Check the pressure.
Check that the power between 
the terminal board " N " and " 1 " 
of the indoor unit is AC 230V, 
50Hz.
Repair the wiring between the 
units.
Press the OPERATION button 
to start operating the air-condi-
tioner. (One-room operation ON)
(Set the cooling mode to 18˚C.)
(Check the failure with the outdoor unit.)
TO
A
48
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
Yes
No
Yes
Yes
Yes
Yes
No
No
No
Yes
No
No
No
No
(Lamp : OFF)
(Lamp : ON)
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Open circuit of the 
outdoor thermistor
Replace the 
thermistor. 
Replace the 
Fan motor.
Replace the outdoor control PWB.
Replace the 
Compressor.
Replace the 
Power module.
Fix the power 
module with 
screws securely.
Replace the 
current 
transformer
Connect CN15.
Connect CN6.
Overheat of the 
compressor
Is CN9 connected ?
Is CN9B connected ?
Is CN1 connected ?
Is CN7 connected ?
Is CN16 connected ?
Is CN14 connected ?
Replace the outdoor 
Power supply P.W.B.
Check the voltage 
(18V) between CN14
  3   and   4    ? )
Replace the Power 
module
Connect CN9
Connect CN9B
Connect CN91
Connect CN7
Connect CN16
Connect CN14
Replace the 
outdoor relay P.W.B.
Check the voltage 
(13V) between CN9
  2   and   3    ? )
Replace the Power 
module
AC overcurrent
Rotation error of 
the compressor
Power module 
(IPM) abnormality
Abnormal 
AC current
Is the winding of 
the current 
transformer 
broken ?
Is the resistance 
value of the 
winding in the 
current 
transformer ? 
720
Open circuit of 
serial signal line
Short circuit of 
serial signal line
Power factor 
module (AF1) error
Is the Power factor
module in a state 
of flaoting from the 
heat sink ? 
Is the resistance 
value among the 
terminal of the 
Power factor 
module 0
 ?
Fix the Power 
factor module with 
screws secuely
Replace the Power 
factor module
Are two or three 
lamps switched 
off ?
Is CN15 
connected ?
Is CN6 
connected ?
Is the resistance 
value of the 
thermistor for 
the compressor 
(TH1), heat ex-
changer (TH2) 
or outdoor 
temperature 
correct (TH3) 
or suction (TH4) ?
Is the outdoor 
fan motor 
operating ?
Is the resistance 
value of the winding 
in the fan motor 
 ?
The cycle is 
abnormal.
The compressor 
is abnormal.
Is each of the 
resistance values 
among the 
terminals of the 
power module 
0Ω
 ?
P - U, N - U
P - V, N - V
P - W, N - W
Is the power 
module in a state 
of floating from 
the heat sink ?
Inspect the
compressor, 
heat exchanger 
and piping.
A
Replace the outdoor 
Power supply P.W.B.
Page of 88