89 
17. Circulation Liquid
Initial setting: Water
System setup
17:26, Wed
Demand control
SG ready
External compressor SW
Circulation liquid
Select
Confirm
Set circulation of heating water.
There are 2 types of settings, water and anti-freeze function.
(CAUTION)  Please set glycol when using anti-freeze function.
It may cause error if setting is wrong.
18. Heat-Cool SW
Initial setting: Disable
System setup
17:26, Wed
SG ready
External compressor SW
Circulation liquid
Heat-Cool SW
Select
Confirm
Able to switch (fix) heating & cooling by external switch.
(Short)
: Fix at Heating (Heating +DHW)
(Open)         : Fix at Cooling (Cooling +DHW)
(CAUTION) This setting is disabled for model without Cooling.
(CAUTION) Does not display if there is no Optional PCB.
Timer function cannot be used. Cannot use Auto mode.
19. Force Heater
Initial setting: Manual
System setup
17:26, Wed
External compressor SW
Circulation liquid
Heat-Cool SW
Force heater
Select
Confirm
Under manual mode, user can turn on force heater through quick menu.
If selection is 'auto', force heater mode will turn automatically if pop up error
happen during operation.
Force heater will operate follow the latest mode selection, mode selection is
dsiable under force heater operation.
Heater source will ON during force heater mode
 
11.3.4 Operation 
Setup 
Heat 
20. Water temp. for heating ON
Initial setting: compensation curve
35°C
-5°C
15°C
55°C
Hot water temperature
compensation curve
Outdoor
temperature
Decide temperature
of 4 points as shown
in diagram
Set target water temperature to operate heating operation.
Compensation curve: Target water temperature change in conjunction with
outdoor ambient temperature change.
Direct: Set direct circulation water temperature.
In 2 zone system, zone 1 and zone 2 water temperature can be set separately.
21. Outdoor temp. for heating OFF
Initial setting: 24°C
24°C
OFF
ON
Set outdoor temp to stop heating.
Setting range is 5°C ~ 35°C
22. ∆T for heating ON
Initial setting: 5°C
Out
Return
Out — Return = 1°C ~ 15°C
Set temp difference between out temp & return temp of circulating water of
Heating operation.
When temp gap is enlarged, it is energy saving but less comfort. When the
gap gets smaller, energy saving effect gets worse but it is more comfortable.
Setting range is 1°C ~ 15°C
23. Outdoor temp. for heater ON
Initial setting: 0°C
0°C
OFF
ON
Set outdoor temp when back-up heater starts to operate.
Setting range is -15°C ~ 20°C
User shall set whether to use or not to use heater.
 
90 
Cool 
24. Water temp. for cooling ON
Initial setting: compensation curve
20°C
30°C
5°C
20°C
compensation curve
Set target water temperature to operate cooling operation.
Compensation curve: Target water temperature change in conjunction with
outdoor ambient temperature change.
Direct : Set direct circulation water temperature.
In 2 zone system, zone 1 and zone 2 water temperature can be set separately.
25. ∆T for cooling ON
Initial setting: 5°C
Out
Return
Return — Out = 1°C ~ 15°C
Set temp difference between out temp & return temp of circulating water of
Cooling operation.
When temp gap is enlarged, it is energy saving but less comfort. When the
gap gets smaller, energy saving effect gets worse but it is more comfortable.
Setting range is 1°C ~ 15°C
 
Auto 
26. Outdoor temp. for (Heat to Cool)
Initial setting: 15°C
15°C
Heat
Cool
Outdoor temp. rising
Set outdoor temp that switches from heating to cooling by Auto setting.
Setting range is 5°C ~ 25°C
Timing of judgement is every 1 hour
27. Outdoor temp. for (Cool to Heat)
Initial setting: 10°C
10°C
Heat
Cool
Outdoor temp. dropping
Set outdoor temp that switches from Cooling to Heating by Auto setting.
Setting range is 5°C ~ 25°C
Timing of judgement is every 1 hour
 
Tank 
28. Floor operation time (max)
Initial setting: 8h
Heat
Tank
30min ~ 10h
Set max operating hours of heating.
When max operation time is shortened, it can boil the tank more frequently.
It is a function for Heating + Tank operation.
29. Tank heat up time (max)
Initial setting: 60min
Heat
Tank
5min ~ 4h
Set max boiling hours of tank.
When max boiling hours are shortened, it immediately returns to Heating
operation, but it may not fully boil the tank.
 
91 
30. Tank re-heat temp.
Initial setting: -8°C
-12°C ~ -2°C
Set temp to perform reboil of tank water.
(When boiled by heat pump only, (51°C – Tank re-heat temp) shall become
max temp.)
Setting range is -12°C ~ -2°C
31. Sterilization
Initial setting: 65°C 10min
①  ③
Set timer to perform sterilization.
1  Set operating day & time. (Weekly timer format)
2  Sterilization temp (55~75°C
 If use back-up heater, it is 65°C)
3  Operation time (Time to run sterilization when it reached setting temp
5min ~ 60min)
User shall set whether to use or not to use sterilization mode.
 
11.3.5 Service 
Setup 
32. Pump maximum speed
Initial setting: Depend on model
Service setup
17:26, Wed
Flow rate
Max. Duty
Operation
88:8 L/min
0xCE
Air Purge
Select
Normally setting is not necessary.
Please adjust when need to reduce the pump sound etc.
Besides that, it has Air Purge function.
33. Pump down
Service setup
17:26, Wed
Pump down:
ON
Confirm
Service setup
17:26, Wed
Pump down:
ON
Confirm
Pump down operation
in progress!
OFF
Operate pump down operation
34. Dry concrete
30°C
1
2
3
4
5
6
35°C
35°C
40°C
40°C
45°C
Stage
Operate concrete curing operation.
Select Edit, set temp for every stage (1~99 1 is for 1 day).
Setting range is 25~55°C
When it is turned ON, dry concrete starts.
When it is 2 zone, it dries both zones.
35. Service contact
Contact-1: Bryan Adams
ABC/ abc
0-9/ Other
A B C D E F G H I J K L M N O P Q R
S T U V W X Y Z
a b c d e f g h i
j k l m n o p q r s t u v w x y z
Select
Enter
Service setup
17:26, Wed
Service contact:
Contact 1
Contact 2
Select
Confirm
Able to set name & tel no. of contact
person when there is breakdown
etc. or client has trouble. (2 items)
 
 
 
 
 
 
 
 
92 
11.4 Outdoor Unit 
11.4.1  Select the Best Location 
  If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the 
condenser is not obstructed. 
  Avoid installations in areas where the ambient temperature may drop below -20°C. 
  Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles. 
  Do not place any obstacles which may cause a short circuit of the discharged air. 
  If outdoor unit installed near sea, region with high content of sulphur or oily location (e.g. machinery oil, etc), it 
lifespan maybe shorten. 
  When installing the product in a place where it will be affected by typhoon or strong wind such as wind blowing 
between buildings, including the rooftop of a building and a place where there is no building in surroundings, fix 
the product with an overturn prevention wire, etc. (Overturn prevention fitting model number: K-KYZP15C) (For 
UD07*E5* and UD09*E5* only) 
 
 
 
  If piping length is over 10 m, additional refrigerant should be added as shown in the table.  
 
Model 
Piping size 
Rated 
Length 
(m)
Max. 
Elevation 
(m)
Min. Piping 
Length 
(m) 
Max. Piping 
Length 
(m) 
Additional 
Refrigerant 
(g/m)
Gas Liquid 
UD03*E5* and 
UD05*E5* 
ø12.7 mm (1/2") 
ø6.35 mm (1/4") 
15 
20 
UD07*E5* and 
UD09*E5* 
ø15.88 mm (5/8") 
ø6.35 mm (1/4") 
20 
30 
30 
 
Example: For UD03*E5* 
If piping length is 15m, the quantity of additional refrigerant should be 100g. [(15-10)m × 20 g/m = 100g] 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 127