Panasonic WH-SDC03H3E5-1 / WH-SDC05H3E5-1 / WH-SDC07H3E5-1 / WH-SDC09H3E5-1 / WH-UD03HE5-1 / WH-UD05HE5-1 / WH-UD07HE5-1 / WH-UD09HE5-1 Simplified Service Manual ▷ View online
125
12.22 External OFF/ON Control
Communication circuit between indoor unit and external controller is as per below.
External
Controller
Controller
Panasonic
PCB
CN-THERMO
5V
12V
1
2
2
mico
Maximum length of communication cable is 50 meter.
Control
content:
External Control Switch
Control Panel OFF/ON
Control Panel Power LED
System Status
ON ON ON ON
ON OFF OFF OFF
ON OFF OFF OFF
OFF ON ON OFF
OFF OFF OFF OFF
OFF OFF OFF OFF
Remocon Screen Display and Control Detail:
REMOTE
ON
ON
ON
ON
OFF
OFF
UNIT
OFF
OFF
OFF
ON
CONTROLLER
LED
REMOTE
CONTROLLER
SIGNA
LED
REMOTE
CONTROLLER
SIGNA
L
EXTERNA
L
CONTROLLER
SWITCH
SWITCH
23
1
44
40
10:34am , Mon
18
˚
c
˚
c
˚
c
˚
c
2
Turned off by external switch.
CANCEL
When External SW connection select "YES" from remocon installer menu:
Heating or Cooling system will operate normally if the External Switch signal is ON.
Once the External Switch turn OFF, System Turn OFF ( Heat pump, water pump, heater etc…)
Remocon LED remain ON or OFF according to the current operation request.
Pop up menu at remocon main screen as above screen to inform customer system stop by External Switch.
It is possible to press cancel and return to main screen to do change of operation setting while waiting the
External Switch turn ON back.
Remocon LED will always follow the latest changes from remocon.
If no action on remocon for continuous 5 minutes, the pop up screen will show again on the screen.
But once the External Switch Turn ON back, pop up screen will disappear and system can operate normally
according to the latest operation setting and request.
126
12.23 External Compressor Switch (Optional PCB)
External compressor switch port can have two purpose of control as below:
Heat source ON/OFF function (Dip switch Pin 3 on PCB "OFF")
Heater ON/OFF function (Dip switch Pin 3 on PCB "ON")
Heat source ON/OFF function
Purpose:
Purpose:
Heat pump ON/OFF function is use to turn OFF the high power consumption device (Heat pump, & Heater) when
there is energy or electric current limitation. Other optional function still can be operate under heat pump and
heater OFF condition.
heater OFF condition.
Control Detail:
This
External
Compressor
Switch is possible to connect to Optional PCB only.
Once the remocon select External Compressor Switch connection "YES", & Dip Switch on PCB "OFF"
This heat pump ON/OFF function will activate
The ON/OFF signal of this External Compressor Switch is same as External Switch.
When the External Compressor Switch is ON:
o Heat pump system operate normally
When the External Compressor Switch is OFF:
o Heat pump, Indoor water pump & Heater ( Booster heater & Backup Heater ) need to turn OFF
o Solar, Boiler and zone control can be operate follow normal control condition.
o Solar, Boiler and zone control can be operate follow normal control condition.
* pump delay OFF also included in this control
(There is NO pop up screen like External Switch when this External Compressor Switch is OFF.)
Heater ON/OFF function
Purpose:
Purpose:
Heater ON/OFF function is use to turn OFF the heater (backup heater & booster heater) when there is energy or
electric current limitation. Heat pump and other optional function still can operate.
Control detail:
This
External
Compressor
Switch is possible to connect to Optional PCB only.
Once the remocon select External Compressor Switch connection "YES", & Dip Switch on PCB "ON"
This heater ON/OFF function will activate
When the External Compressor Switch is ON:
o Heat pump and heater operate normally
When the External Compressor Switch is OFF:
o Backup heater and booster heater cannot operate even heater request is ON.
o Heat pump and option function (Solar, Boiler and zone control) can be operate follow normal control
o Heat pump and option function (Solar, Boiler and zone control) can be operate follow normal control
condition.
(There is NO pop up screen like External Switch when this External Compressor Switch is OFF.)
12.24 Heat/Cool Switch (Optional PCB)
Purpose:
User can switch the running mode from heat to cool or cool to heat through external installed Heat/Cool switch.
This kind of heat / cool switch may built in inside the field supply room remocon as well.
Control contents:
Heat/Cool Switch can only be set when Cool Function is "enable" at custom menu setting, & Extension PCB
select "YES" & Zone 1 not set "Pool" condition.
This heat/cool switch control will be activate only when installer set the Heat/Cool Switch "USE" through remocon.
Once the Heat/Cool Switch Set "USE", remocon will check indoor send Signal to judge the option of mode select.
o When Heat/Cool Switch Contact Open : Remocon only can select Heat Mode, or Heat + Tank Mode, or Tank
Mode
o When Heat/Cool Switch Contact Close : Remocon only can select Cool Mode, or Cool + Tank Mode, or Tank
Mode
127
Operation ON/OFF will depend on remocon request.
When Heat Mode is running with Contact Open, user change this setting to contact close, indoor will this signal to
remocon judge and change mode to cool and send back to indoor. And it is same as from cool mode change to
heat mode.
* This switch have higher priority, remocon follow indoor send signal when control activated.
* There is no effect to the operation when the mode running is only Tank Mode.
heat mode.
* This switch have higher priority, remocon follow indoor send signal when control activated.
* There is no effect to the operation when the mode running is only Tank Mode.
(Weekly Timer are ignored and cannot be set during Heat / Cool Switch is "Enable" Condition.)
12.25 SG Ready Control (Optional PCB)
Purpose:
To set ON/OFF of heat pump and target temperature by digital input of third party device if necessary in field.
Optional PCB
D
igi
ta
l I
nput
Remote Station
+ DI2 Com
+ DI1 Com
- Com
Remote control setting
For this function, following items need to be set on R/C (installer menu) –
For this function, following items need to be set on R/C (installer menu) –
SG control = YES or NO
Capacity up setting 1
o Heating capacity [50 ~ 150 %]
o DHW capacity [50 ~ 150 %]
o DHW capacity [50 ~ 150 %]
Capacity up setting 2
o Heating capacity [50 ~ 150 %]
o DHW capacity [50 ~ 150 %]
o DHW capacity [50 ~ 150 %]
Control contents:
If SG control on remote control = "Yes", then following control only activate by digital input.
While Digital input is " 00 " (Normal operation)
o Normal operation. Once detect '00' system will operate back to normal condition.
(All the target set temperature for heating side and DHW side will return back to previous set temperature
when digital signal change from "10' or"11" back to "00".)
when digital signal change from "10' or"11" back to "00".)
While digital input is detected " 01 " (HP stop)
o Heat pump & room heater & tank heater cannot operate.
(Solar control and Boiler back up and 2 Zone control can activate.)
While digital input is detected " 10 " (Capacity 1)
o Target temperature for heating and DHW Tank is changed according to the percentage set by Remote
control setting. However, which setting temperature is change depend on system setting.
While digital input is detected " 11 " (Capacity 2)
o Target temperature for heating and DHW Tank is changed according to the percentage set by Remote
control setting. However, which setting temperature is change depend on system setting.
While digital input is detected " 10 " (Capacity 1)
o Setting temperature for heating and Tank is changed.
However, which setting temperature is change depend on system setting.
128
If Buffer selection is “YES”
Room side
New Target Buffer tank temperature = Current Target Buffer Tank Temperature * Remote Control setting
(" capacity 1) %
* Max Min regulation is follow Target Buffer tank temperature control specification
** No change of Target zone water temperature, only set higher buffer tank temperature.
Room side
New Target Buffer tank temperature = Current Target Buffer Tank Temperature * Remote Control setting
(" capacity 1) %
* Max Min regulation is follow Target Buffer tank temperature control specification
** No change of Target zone water temperature, only set higher buffer tank temperature.
DHW Tank side
New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 1) % *
(Max regulation depend on the tank max setting limit)
New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 1) % *
(Max regulation depend on the tank max setting limit)
If Buffer selection is “NO”
Room side
New Target Zone Water Temperature = Current Target Zone Water Temperature * Remote Control Setting
(*Capacity 1) %
(Zone 1 and Zone 2 will change according to its own target zone water temperature.)
(Max regulation depend on the temperature control type select)
Room side
New Target Zone Water Temperature = Current Target Zone Water Temperature * Remote Control Setting
(*Capacity 1) %
(Zone 1 and Zone 2 will change according to its own target zone water temperature.)
(Max regulation depend on the temperature control type select)
DHW Tank side
New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 1) %
* (Max regulation depends on the tank max setting limit)
New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 1) %
* (Max regulation depends on the tank max setting limit)
While digital input is detected " 11 " (Capacity 2)
o Setting temperature for heating and Tank is changed.
However, which setting temperature is change depend on system setting.
If Buffer selection is “YES”
Room side
New Target Buffer tank temperature = Current Target Buffer Tank Temperature * Remote Control setting
(" capacity 2) %
* Max Min regulation is follow Target Buffer tank temperature control specification
** No change of Target zone water temperature, only set higher buffer tank temperature.
Room side
New Target Buffer tank temperature = Current Target Buffer Tank Temperature * Remote Control setting
(" capacity 2) %
* Max Min regulation is follow Target Buffer tank temperature control specification
** No change of Target zone water temperature, only set higher buffer tank temperature.
DHW Tank side
New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 2) %
* (Max regulation depends on the tank max setting limit)
New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 2) %
* (Max regulation depends on the tank max setting limit)
If Buffer selection is “NO”
Room side
New Target Zone Water Temperature = Current Target Zone Water Temperature * Remote Control Setting
(*Capacity 2) %
(Zone 1 and Zone 2 will change according to it's own target zone water temperature.)
(Max regulation depend on the temperature control type select)
Room side
New Target Zone Water Temperature = Current Target Zone Water Temperature * Remote Control Setting
(*Capacity 2) %
(Zone 1 and Zone 2 will change according to it's own target zone water temperature.)
(Max regulation depend on the temperature control type select)
DHW Tank side
New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 2) %
* (Max regulation depends on the tank max setting limit)
** This function is not applicable for Cooling mode.
New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 2) %
* (Max regulation depends on the tank max setting limit)
** This function is not applicable for Cooling mode.
12.26 Demand Control (Optional PCB)
Remote control setting:
When Optional PCB connection select 'YES", Demand Control function can select "YES" or "NO".
Purpose:
Purpose:
After the demand control select YES, below control will activated.
o 0-10V
Demand
control
0-10V Demand control
Demand control is use to reduce the current usage of heat pump unit by third party device.
Control start condition:
Select “YES” at Demand control at installer menu.
0-10V input for this electrical current control is detected.